• Title/Summary/Keyword: 피난용량

Search Result 28, Processing Time 0.029 seconds

Derivations of Positive Pressure Condition for Development of Foldable Safe Pathway in Railway Tunnel Fires (철도터널화재용 접이식 대피통로 개발을 위한 양압 조건 도출)

  • Kim, JiTae;Ro, Kyoungchul
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.20 no.1
    • /
    • pp.284-289
    • /
    • 2019
  • The Korea Foldable safe pathway system is an evacuation support system to get temporary evacuation route in railway tunnel and large space fires. A prevention smoke screen is unfolded in fires and it is needed to prevent heat and smoke from fire source. Therefore, ventilation system for positive pressure condition is equipped with foldable safe pathway system. Numerical analyses of temperature and pressure distribution with distance from fire source were performed considering fire scenario of new train vehicle. The smoke temperatures did not exceed $200^{\circ}C$ that distance from the fire source was more than 20 m and smoke pressure was reduced with distance from fire source. Maximum smoke pressure was 14 Pa and average pressure was 6 Pa in position of prevention smoke screen. As results, to install foldable safe pathway system, ventilation system is need to maintain 6 Pa positive pressure condition.

Flow Analysis of Building Pressurization System for Smoke Control (건물의 가압방연시스템 설계를 위한 유동해석에 관한 연구)

  • 김명배;한용식
    • Fire Science and Engineering
    • /
    • v.14 no.2
    • /
    • pp.14-20
    • /
    • 2000
  • Many pressurization systems are designed and built with the goal of providing a smoke-free escape route in the event of a building fire. A secondary objective is to provide a smoke-free staging area for fire fighters. In the present study, a computer program is developed to calculate pressure loss and flow rate at several building elements such as a room, a ]tabby a staircase and an air supply shaft. By the program as the dosing tool for the pressurization system, the capacity of the injection fan is calculated, and the design method is proposed for the optimization of the fan capacity.

  • PDF

A Guidance Methodology Using Ubiquitous Sensor Network Information in Large-Sized Underground Facilities in Fire (대형 지하시설물에서 화재발생 시 USN정보를 이용한 피난 유도 방안)

  • Seo, Yonghee;Lee, Changju;Jung, Jumlae;Shin, Seongil
    • KSCE Journal of Civil and Environmental Engineering Research
    • /
    • v.28 no.4D
    • /
    • pp.459-467
    • /
    • 2008
  • Because of the insufficiency of ground space, the utilization of underground is getting more and more in these days. Moreover, underground space is being used not only buildings but multipurpose space for movement, storage and shopping. However, ground space has vital weakness for fire compared to ground space. Especially in case of underground shopping center, there are various stuffs to burn and poisonous gas can be exposed on this count when the space is burned. A large number of casualties can be also occurred from conflagration as underground space has closed structures that prevent rapid evacuation and access. Therefore, this research proposes the guidance methodology for evacuation from conflagration in large-sized underground facilities. In addition, suggested methodology uses high technology wireless sensor information from up-to-date ubiquitous sensor networks. Fire information collected by sensors is integrated with existing underground facilities information and this is sent to guidance systems by inducing process. In the end, this information is used for minimum time paths finding algorithm considering the passageway capacity and distance. Also, usefulness and inadequacies of proposed methodology is verified by a case study.

An analytical Study on the Smoke Behavior using BRI 2002 in Japan (일본의 BRI2002를 활용한 건물의 연기성상에 대한 해석적 연구)

  • Kim, Dong-Eun;Seo, Dong-Goo;Hong, Hae-Ri;Kwon, Young-Jin
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2010.10a
    • /
    • pp.287-290
    • /
    • 2010
  • 최근 건축물은 초고층화 대형화 지하심층화 등으로 변모하고, 더나아가 복합화가 진행되고 있다. 이러한 건축물은 화재 발생 시 기존의 건축물보다 큰 인재로서 다가오며, 특히 연기로 인한 피해가 주를 이루고 있다. 하지만 국내의 경우 연기의 피해에 따른 피난용량설정 및 계획 등에 관한 연구가 미흡한 실정이다. 따라서 본 연구는 기존 개발된 일본의 연기 거동 해석모델인 BRI2002의 메커니즘를 이용하여, 가상의 건축물에서의 Case Study를 통한 연기거동을 분석함으로서 향후 연기거동에 대한 연구의 방향성 및 기초적인 자료를 구축하는데 그 목적이 있다.

  • PDF

On the Pressurization for Smoke Control in Building Fires (건물화재에서의 가압방연 설계에 관한 연구)

  • Kim, Myeong-Bae
    • 연구논문집
    • /
    • s.29
    • /
    • pp.39-48
    • /
    • 1999
  • This paper deals with the lobby pressurization for smoke control in building fires. A computer program and related modeling technique are presented. The pressure difference between a lobby and a fire area is not able to be same among building floors because an injection fan can not be installed in each floor. The most remote area from the injection fan has therefore the smallest pressure difference if flow areas are not different through all floors. An adjacent floor from the injection fan has possibly too large pressure difference because the most remote lobby must also meet the required pressure difference over the fire area. Moreover this problem will lead to a larger capacity of the fan. It is showed that the fan capacity can be decreased by adjusting the flow area of air supply duct in each floor.

  • PDF

A study on the optimal ventilation and smoke exhaust systems in case of fire in subway stations installed with PSD (PSD가 설치된 지하철 역사 내 화재 시 최적 배연시스템 연구)

  • Kim, Hyo-Gyu;Yoo, Ji-Oh;Kim, Doo-Young
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.20 no.2
    • /
    • pp.527-539
    • /
    • 2018
  • The subway used by many passengers is required to maintain a safe and comfortable environment and PSD (Platform Screen Door) must be installed in the platform after reinforcing the standard in 2003. In the previous research, in case of subway fire to control it, it is necessary to design the optimal ventilation and smoke exhaust system according to equipment capacity of the smoke exhaust system. Therefore, in this study, based on the results of previous research, three-dimensional numerical analysis was performed for the CO gas and smoke flow by the subway ventilation system in case of platform fire. As a result of this study, it was found that in case of emergency, if only the upper-level smoke exhaust system is activated, the risk of evacuation is high due to CO gas (653.8 ppm) and smoke concentration ($768.4mg/m^3$). And when all the smoke exhaust systems are activated and only the fire side PSD is opened, CO gas (36.0 ppm) and smoke concentration ($26.2mg/m^3$) are detected and the propagation range of smoke flow was reduced. When all the smoke exhaust systems are activated and only the fire side PSD is closed, it was analyzed as the most effective ventilation mode in the evacuation environment due to the absence of smoke-recirculation.

Cause and Countermeasure of Inundation Damage in Underground Space (우리나라 지하공간 내수침수피해 원인 및 대책)

  • Cho, Jae-Woong;Choi, Woo-Jung
    • Proceedings of the Korea Water Resources Association Conference
    • /
    • 2011.05a
    • /
    • pp.420-420
    • /
    • 2011
  • 도시지역의 내수침수피해는 거의 매년 발생하고 있으며, 반지하와 같은 거주공간이 매우 취약한 상태이다. 특히 최근에는 지하철, 지하상가 등이 대규모 개발되고 복합네트워크화 되어 지하공간의 침수대책과 대피방안 마련이 시급한 상황이다. 일본의 경우 2000년 토카이 호우피해 후 통합유출해석 모형을 개발하였으며, 1999년 및 2003년 후쿠오카 침수피해 발생 후 특정도시하천침수피해대책법을 제정, 1999 후쿠오카, 2004년 하마마츠, 2008년 카누마 피해 후 일본 방재연구소에서는 실시간 1차원 지표범람모형과 모니터링을 통한 실시간 내수침수지도를 개발하였다. 특히 지하공간에 대해서는 "지하공간에 유입하는 범람수가 계단상 보행자게에 주는 위험성에 관한 연구" 등 실험을 바탕으로 각종 지하공간 침수대책 매뉴얼 및 지하시설의 침수시 피난확보계획 지침, 지하공간 침수대책 가이드라인 등 인명피해를 줄이고자하는 노력이 계속되어 오고 있다. 우리나라는 2006년 경기도 고양시 3호선 정발산역이 침수되었으며, 2010년 서울시 지하철 2호선 사당역 및 4호선이 침수되는 등의 지하철 침수피해와 2010년 서울시 광화문 지하상가, 인천시 부평구 우림라이온스 벨리, 우남플라자, 계양구 농협하나로마트, 서원아파트 등의 지하상가와 지하다층의 침수피해가 발생하였다. 특히 2006년 3호선 정발산역 침수는 17시간이나 지하철이 불통되었고 이로 인하여 심각한 교통 체증이 유발 되었다. 본 연구에서는 2010년 집중호우로 인한 서울, 인천지역의 지하공간 침수피해를 중심으로 최근 10년간 지하공간 침수피해사례로부터 대표적인 침수피해 원인 및 특성을 정리하였으며, 그 결과 지하공간 침수의 주요원인은 지상공간의 침수류가 지하공간으로 유입하고, 지하공간의 배수설비 용량부족, 지하공간으로의 유입을 방지하기위한 방지턱, 차수판, 침수시 비상전원 공급, 침수시 지하공간 대피 매뉴얼의 부재 등 다양한 원인이 있는 것으로 나타났다. 특히, 소방방재청에서 고시한 '지하공간 침수방지를 위한 수방기준'에 지하공간 침수 방지를 위한 각종 시설의 설치 및 대피 경로지정 등에 대한 기준이 마련되어 있으나, 지하공간 중 유동인구가 가장 많은 지하철역에서 조차 침수에 대한 행동매뉴얼이나 대피에 대한 가이드라인이 마련되지 않은 것으로 나타났다. 따라서, 지하공간 침수를 방지하기 위하여 센서를 이용한 자동 차수판과 경보기 설치, 지하공간의 사람들이 안전한 대피로를 찾을 수 있도록 지상공간 및 지하공간 출입구를 모니터링 할 수 있는 CCTV의 설치, Dry Area를 두어 비상대피 할 수 있는 공간의 마련 등 시설적인 부분에 대하여 '지하공간 침수방지를 위한 수방기준'을 더욱 강화할 필요가 있으며, 지상공간의 침수 상황을 고려한 지하공간의 대피매뉴얼 또는 가이드라인 등의 수립이 필요하다. 또한 이와 더불어 재산 및 인명피해를 더욱 효율적으로 줄일 수 있도록 실시간 예 경보를 위한 침수해석 모형의 개발이 시급하다.

  • PDF

Development of an Integrated Inundation Analysis Model for Urban Flood Inundation Analysis (도시지역의 침수해석을 위한 통합침수해석모형의 개발)

  • Kim, Dong-Il;Son, Ah-Long;Son, In-Ho;Han, Kun-Yeun
    • Proceedings of the Korea Water Resources Association Conference
    • /
    • 2011.05a
    • /
    • pp.135-135
    • /
    • 2011
  • 지구온난화와 이상기후에 따라 최근 우리나라를 둘러싼 기후패턴의 변화가 가속화되고 있으며 한반도는 장마기간이 소강상태를 보이는 반면, 장마 후 국지성 집중호우가 증가하고 태풍이 내습하는 현상이 빈번해짐으로써 홍수에 대한 위험과 피해규모도 증가하고 있다. 특히 도시지역에서는 강우규모가 배수시스템의 용량을 초과하거나, 하천수위 상승으로 관로 내에 역류가 발생하는 등 우수 배제 기능을 제대로 수행하지 못할 경우 발생하는 지표침수로 인해 심각한 인명 및 재산피해가 발생하고 있다. 실제로 현재 홍수해석 및 홍수위험지도 작성시 내수시스템을 반영하지 않아 침수면적 및 범위의 오차가 존재하며 홍수위험지도 작성시 내수범람과 외수범람을 따로 고려하는 문제점이 있다. 따라서 도시 침수 해석시 내수시스템을 반영한 정확한 침수심 및 침수면적계산뿐만 아니라 이상기후에 대비한 복합적 요인으로 인한 침수해석이 필요하다. 따라서 본 연구에서는 하천해석을 위해 1차원 하천 해석 모형인 FLDWAV모형을 적용하고 가상의 제방 파제 시나리오를 통하여 외수범람 영향을 구하였으며, 배수시스템의 SWMM모형과 제내지에서 내수와 외수범람의 영향을 고려한 DEM기반의 2차원 범람해석을 연계한 Dual-Drainage모형에 대하여 외수범람 영향에 따른 흐름의 양상, 침수심, 침수위 등을 분석하였다. 개발한 모형에 대한 적용성을 검토하기 위하여 대구 신암5동 유역을 선정하였고 대상유역의 수치지도를 활용하여 정형 격자 20m 크기로 지형자료를 구성하였으며, 건물의 영향도 고려하기 위해 DEM에 건물자료를 합성하였다. 침수해석 결과 내수시스템의 영향을 고려하지 않을 때가 고려하였을 때 보다 Node(맨홀)에서의 재유입의 영향으로 인하여 최대 침수심이 더 높게 나왔으며 침수면적도 넓게 나타나는 것을 확인하였고, 기존의 홍수위험지도 작성시 외수침수와 내수침수를 구분하여 해석하였던 것을 본 연구에서 통합하여 외수범람의 영향을 고려한 통합침수해석을 실시하여 내수에서 발생할 수 있는 유출량과 내수시스템의 월류량 등에 대한 고려가 없는 외수침수만 해석시 보다 최대침수심이 더 높게 나타났으며 침수면적 또한 넓게 나타남을 알 수 있었다. 본 연구를 통해서 도시홍수, 돌발홍수 등의 발생시 정확한 도시 침수 해석이 가능하며 도시침수구역에 대한 적절한 예 경보 및 피난대책 수립에 활용될 수 있을 것으로 사료된다. 또한 국내의 홍수위험지도나 도시 침수해석과 연계하여 선행시간을 확보한 정확도 높은 홍수정보시스템 구축에 크게 기여할 것으로 판단된다.

  • PDF