• Title/Summary/Keyword: 증발압력

Search Result 271, Processing Time 0.024 seconds

Study on Evaporation Pressure Drop of Hydrocarbon Refrigerants (탄화수소계 냉매의 증발 압력강하 특성에 관한 실험적 연구)

  • Lee Kwang-Bae;Lee Ho-Saeng;Kim Jae-Dol;Yoon Jung-In
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.29 no.5
    • /
    • pp.533-539
    • /
    • 2005
  • Experimental results are presented for heat transfer and pressure gradients of HCs refrigerants R-290, R-600a, R-1270 and HCFC refrigerant R-22 during evaporating inside horizontal double pipe heat exchangers. Two tubes with a tube diameter of 12.70mm and 9.52mm are used for this investigation. Hydrocarbon refrigerants have higher pressure drop than R-22 in 12.7mm and 9.52mm. The results from the investigation can be used in the design of heat transfer exchangers using hydrocarbons as the refrigerant for the air-conditioning systems.

Definition and Improvement of the Sound which was generated by Bubbles at the Accumulator of the Evaporator (증발기 어큐뮤레이터에서의 버블 소음 규명 및 개선)

  • 박정희;장의영;박윤서
    • Proceedings of the Korean Society for Noise and Vibration Engineering Conference
    • /
    • 1996.04a
    • /
    • pp.148-154
    • /
    • 1996
  • 가정용 냉장고에 있어서 정음화를 위한 다각적인 노력이 냉장고의 주요 소음원이라고 할 수 있는 압축기, 냉기 순환용 팬, 압축기 냉각용 팬 및 냉매 순환용 파이프 방진구조 등의 개선을 통하여 국내외적으로 상당한 진척을 보이고 있다. 이러한 소음원들의 특징은 각각이 특정한 목적에 의하여 작동하는 하나의 구동부이거나 이러한 구동부와의 직접적인 연결에 의해 가진되는 경우로서 Airborne Noise나 Structureborne Noise를 발생시키고 있다. 본 논문에서는 이러한 압축기나 팬이 꺼진 상태에서 냉장고의 싸이클상에 열교환용 냉매가 봉입된 상태에서 압축기가 운전시 형성되었던 싸이클상의 고압 및 저압측의 압력 차이에 의하여 증발기의 Accumulator내에 형성된 Sleeve(이하, 삽입관 .PHI.1.5 Hole)에 의해서 발생되는 Bubble 소음에 대한 실험적 규명과 소음 측정을 통한 주파수 분석을 하였으며, 이러한 Bubble 소음 발생시 싸이클상의 온도 및 압력값을 측정하여 Strasberg에 의해 도출된 선형화된 식을 이용하여 Bubble 소음 발생시 주파수 분석을 통한 Bubble Size를 결정하였고, Bubble 소음 발생의 직접적인 원인으로 작용하는 Orifice를 제거하여 Bubble 소음의 개선 정도를 비교 검토하였다.

  • PDF

Developement of remote controlled treatment for the improvement of water quality (가압방식을 겸용한 소형 포터블 냉매회수 및 충전 전용기 개발)

  • Kang, Sung-Jun;Kim, Jin-Taek;Kim, Jung-Hoon
    • Proceedings of the KAIS Fall Conference
    • /
    • 2012.05b
    • /
    • pp.637-639
    • /
    • 2012
  • 본 논문에서는 대형 공조기기에서 냉매의 회수시간을 단축하기 위해 진공과 가압방식을 겸용하면서 작업 시 이동이 손쉽게 소형으로 회수 및 충전이 가능할 수 있는 냉매 회수 및 충전 전용기 개발을 하고자 한다. 냉매회수시스템의 작업과정은 냉매회수 장치와 냉동기의 증발기 하부에 충진용 밸브를 호스로 연결하고 진공펌프를 운전하여 저장 탱크 내에 부착된 압력계가 진공상태가 될 때까지 액냉매를 회수 한 후, 자체적으로 증발, 흡입, 액화시켜 탱크내의 온도와 압력을 낮추어 액화된 냉매를 저장탱크로 회수하는 장치로 구성되어 있다.

  • PDF

Characteristics on Evaporating Pressure Drop of HCs Refrigerants inside a horizontal tube (수평관내 HC계 냉매의 증발 압력강하 특성)

  • Choi, Jun-Hyuk;Lee, Ho-Saeng;Kim, Jae-Dol;Yoon, Jung-In
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.63-64
    • /
    • 2006
  • Chracteristics on evaporating pressure drop of HCs refrigerants inside a horizontal tube were studied experimentally. Experimental results were presented for pressure drops of hydrocarbon refrigerants R-290, R-600a, R-1270 and HCFC refrigerant R-22 inside a horizontal double pipe heat exchanger. Three tubes with a tube diameter of 12.70mm, 9.52mm and 6.35mm were used for this study. Hydrocarbon refrigerants showed higher evaporating pressure drop than that of R-22 in all tubes. The highest pressure drop was founded in R-600a. The highest evaporating perssure drop of all refrigerants was shown in a tube diameter of 6.35mm with same mass flux. The results can be used as the basic data for the design of heat exchanger using hydrocarbon refrigerants as an alternatives.

  • PDF

A Study on the Characteristics of Plate Finned-Tubes Evaporator (평판핀이 부착된 증발기의 특성에 관한 연구)

  • 손병진;민묘식;김홍배
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.15 no.3
    • /
    • pp.982-991
    • /
    • 1991
  • 본 연구에서는 냉방기에서 널리 이용되고 있는 평판핀이 연속적으로 부착된 다관식 증발 열교환기에 대하여 (1) 냉매의 열역학적 물성치의 변화 (2) 냉매와 공기 측 열전달 계수의 변화 (3) 냉매측 관 마찰 손실등을 고려한 시뮬레이션 프로그램을 작성하고 그 결과를 실험을 통하여 보정 완성하였다. 계산결과로 부터 공조기기의 설계조건, 공조계통 해석을 위한 기초자료를 제시하였다.

Zeolite Based Pervaporation Membrane: A Review (제올라이트 기반 투과증발 분리막: 총설)

  • JooYeop, Lee;Rajkumar, Patel
    • Membrane Journal
    • /
    • v.32 no.6
    • /
    • pp.383-389
    • /
    • 2022
  • Membrane separation process is an important technique utilized for various applications. This separation process proceeds due to a driving force such as concentration gradient, pressure or electrical potential gradient etc. Pervaporation is one of the separation process based on solution-diffusion mechanism. The pressure of the permeate side is reduced by creating vacuum and separation is driven due to pressure difference. Purity of the fuel or chemical like ethanol or isopropyl alcohol are improved by dehydration process through porous zeolite membrane. These membranes have high thermal, chemical, mechanical stability. This review is classified mainly into two different sections: Ethanol and bio-oil dehydration by zeolite membrane.

Effect of Aspect Ratio of Flat Tube on R410A Evaporation Heat Transfer and Pressure Drop (납작관의 종횡비가 R-410A 증발열전달 및 압력손실에 미치는 영향)

  • Kim, Nae Hyun;Lee, Eul Jong;Byun, Ho Won
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.37 no.4
    • /
    • pp.395-404
    • /
    • 2013
  • In this study, R-410A evaporation heat transfer tests were conducted in flattened tubes made from 5-mm round tubes. The test range covered a saturation temperature of $15^{\circ}C$, heat flux of $5{\sim}15kW/m^2K$, and mass flux of $200-400kg/m^2s$. The results showed that both the condensation heat transfer coefficient and the pressure drop increased as the aspect ratio increased, with a pronounced increase for an aspect ratio of 4. A comparison of the flattened tube data with existing correlations revealed that the heat transfer coefficients were reasonably predicted by the Shah correlation, and the pressure drops were reasonably predicted by the Jung and Radermacher correlation.