• Title/Summary/Keyword: 주상변압기

Search Result 99, Processing Time 0.022 seconds

Adjustment of Load Regression Coefficients and Demand-Factor for the Peak Load Estimation of Pole-Type Transformers (주상 변압기 최대부하 추정을 위한 부하상관계수 및 수용율 조정)

  • Yun, Sang-Yun;Kim, Jae-Chul;Park, Kyung-Ho;Moon, Jong-Fil;Lee, Jin;Park, Chang-Ho
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.2
    • /
    • pp.87-96
    • /
    • 2004
  • This paper summarizes the research results of the load management for pole transformers done in 1997-1998 and 2000-2002. The purpose of the research is to enhance the accuracy of peak load estimation in pole transformers. We concentrated our effort on the acquisition of massive actual load data for modifying the load regression coefficients, which related to the peak load estimation of lamp-use customers, and adjusting the demand-factor coefficients, which used for the peak load prediction of motor-use customers. To enhance the load regression equations, the 264 load data acquisition devices are equipped to the sample pole transformers. For the modification of demand factor coefficients, the peak load currents are measured in each customer and pole transformer for 13 KEPCO (Korea Electric Power Corporation) distribution branch offices. Case studies for 50 sample pole transformers show that the proposed coefficients could reduce estimating error of the peak load for pole transformers, compared with the conventional one.

Temperature Rise Test and Temperature Distribution Analysis of Pole Mount Mold Transformer with One-body Molding (일체형 주상용 몰드 변압기의 온도분포 및 특성 비교)

  • Cho, Han-Goo;Lee, Un-Yong;Kang, Tack-Sou;Choi, In-Hyuk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.19 no.12
    • /
    • pp.1154-1159
    • /
    • 2006
  • The mold transformers have been widely used in underground substations of large building and have some advantages when compared with oil-transformer. Those advantages are low fire risk, environmental compatibility, compact size and high reliability. The mold transformer is generally known to have cooling duct between low voltage and high voltage coil. To achieve better compact structure and low loss, mold transformers made by one body molding method has been developed. Nevertheless, such kinds of transformer need better cooling method because heat radiation between each winding is still of problem. The life of transformer is significantly dependent on the thermal behavior in windings. Many designers have calculated temperature distribution in transformers and hot spot point by finite element method(FEM) to analyze winding temperature rise. In this paper, the temperature distribution analysis of 100 kVA pole mold transformer for power distribution were investigated by FEM program and the thermal analysis results were compared with temperature rise test.

Reliability Upgrading Technologies of Distribution Transformers (주상 변압기 신뢰성 향상기술)

  • Song, I.K.;Lee, B.S.;Jung, J.W.;Kim, D.M.;Kim, J.Y.;Lee, J.B.;Kwon, T.H.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07a
    • /
    • pp.212-215
    • /
    • 2003
  • In this paper, a model pole transformer was designed to improve the reliability of pole transformers and its short circuit withstand strength was tested. The failure causes of the pole transformers which had been operated in the field were analyzed and several patterns of the causes were determined. A novel countermeasure was devised to prevent the failures of the pole transformers in advance. A model pole transformer was designed and made in accordance with the given specifications to strengthen the short circuit withstand capability and its characteristic was tested. As a result, the advanced performance of the model pole transformer was confirmed and novel techniques in manufacturing process was suggested. It is considered that all the methods employed in the developing process will be helpful to design and manufacture the pole transformers thus the reliability of pole transformers in distribution lines will be improved.

  • PDF

The Design and Performance Test of Mold Transformer for Outdoor Pole (50 kVA 주상용 몰드변압기의 설계 및 특성평가)

  • Cho, Han-Goo;Lee, Un-Yong;HwangBo, Kuk
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.05c
    • /
    • pp.132-137
    • /
    • 2002
  • The mold transformers have been widely used in underground substations in large building and have some advantages in comparison to oil-transformer, that is low fire risk, excellent environmental compatibility, compact size and high reliability. In addition, the application of mold transformer for outdoor is possible due to development of epoxy resin. The mold transformer generally has cooling duct between low voltage coil and high voltage coil. A mold transformer made by one body molding method has been developed for small size and low loss. The life of transformer is significantly dependent on the thermal behavior in windings. To analyse winding temperature rise, many transformer designer have calculated temperature distribution and hot spot point by finite element method(FEM). Recently, numerical analyses of transformer are studied for optimum design, that is electric field analysis, magnetic field, potential vibration, thermal distribution and thermal stress. In this paper, the temperature distribution of 50 kVA pole mold transformer for power distribution are investigated by FEM program and the temperature rise test of designed mold transformer carried out and test result is analyzed compare to simulation data. In this result, the designed mold transformer is satisfied to limit value of temperature and the other property is good such as voltage ratio, winding resistance, no-load loss, load loss, impedance voltage and percent regulation.

  • PDF

The Energized Aging Property of Pole Mount Mold transformer by Back-to-back Method (반환부하법에 의한 옥외 주상용 몰드변압기의 과전열화 특정)

  • Hwang, Bo-Guk;Cho, Han-Goo;Lee, Un-Yong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.484-487
    • /
    • 2002
  • The mold transformers have been widely used in underground substations in large building and have some advantages in comparison to oil-transformer, that is low fire risk, excellent environmental compatibility, compact size and high reliability. In addition, the application of mold transformer for outdoor is possible due to development of epoxy resin. The mold transformer generally has cooling duct between low voltage coil and high voltage coil. A mold transformer made by one body molding method has been developed for small size and low loss. In this paper, the proto type mold transformer of 50kVA class is investigated by routine, type, special test. The outdoor energized aging test is investigated by back-to-back method to verify the long time performance of pole mold transformer. The aging process of transformer is analyzed by various diagnosis method such as DC voltage-current test, $tan{\delta}$, Meggar measurement, winding temperature and etc.

  • PDF

The Temperature Distribution Analysis of Mold transformer (100kVA 주상용 몰드 변압기의 온도분포 해석)

  • Cho, Han-Goo;Lee, Un-Yong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05b
    • /
    • pp.125-129
    • /
    • 2004
  • The mold transformers have been widely used in underground substations in large building and have some advantages in comparison to oil-transformer, that is low fire risk, excellent environmental compatibility, compact size and high reliability. In addition, the application of mold transformer for outdoor is possible due to development of epoxy resin. The mold transformer generally has cooling duct between low voltage coil and high voltage coil. A mold transformer made by one body molding method has been developed for small size and low loss, but it needs some cooling method because heat radiation between each winding is difficult. The life of transformer is significantly dependent on the thermal behavior in windings. Many transformer designers have calculated temperature distribution and hot spot point by FEM(finite element method) to analyze winding temperature rise. In this paper, the temperature distribution and thermal stress analysis of 100kVA pole cast resin transformer for power distribution are investigated by FEM program.

  • PDF

The On-Line Measuring of Dissipation Factor on pole Transformer (주상 변압기의 절연유 유전정접 활선 측정 기법)

  • Lee, Su-Kil;Kim, Jae-Chul;Yoon, Yong-Han;Lee, Bo-Hoo;Kim, Oun-Seok
    • Proceedings of the KIEE Conference
    • /
    • 1996.07b
    • /
    • pp.853-855
    • /
    • 1996
  • This paper describes the dissipation factor measuring techniques of insulating oil on the operating transformer by using digital signal processing. After applying voltage to the electrodes which is installed In a transformer, acquiring source voltage and current of electrodes and using cross-correlation techniques. we can check the dissipation factor of insulating oil. To Improve measuring accuracy and the speed of process, we use hardware such as TMS320C31 DSP board and analog filter and software such as cross-correlation techniques, rectangular window, and digital filtering techniques. We simulated the measuring accuracy and the degree of the noise effect of this new measuring techniques by using computer simulation, and compared the simplified measuring devices with schering bridge on degraded insulating oil. The result showed that this measuring technique can be used as diagnostic method on the pole transformers.

  • PDF

The Study of the Design Tests for Current Capability according to ANSI (ANSI 규격에 의한 주상 변압기의 동압력 내력시험에 관한 연구)

  • Kim, Sun-Koo;Kim, Won-Man;La, Dae-Ryeol;Roh, Chang-Il;Lee, Dong-Jun;Jung, Heung-Soo
    • Proceedings of the KIEE Conference
    • /
    • 2003.07b
    • /
    • pp.909-911
    • /
    • 2003
  • The almost pole transformers are constructed with tank, cover, clamp etc., that contains the insulation oil, core, coil, terminals, bus and the other accessories. If some fault current will be flown by some trouble or accident, interior pressure of the transformer shall be very quickly rise, and mechanical components or insulation oil from the transformer enclosure shall be propelled or dropped from the tank. For the prevention of the above accident, recently the pole transformers should be done 'the Design Tests for Fault Current Capability' according to ANSI C57.12.20(1997) There are two tests method in this standard, Test Number I with a high current arcing fault, without internal fusible elements, shall be conducted on rack enclosure with its minimum designed air space. Test Number II with an internal fusible element, shall be conducted on each enclosure diameter utilizing the internal fusible elements. KEPCO recently request to be done the 'Design Tests for Fault Current Capability' for pole transformers according to KEPCO's standard ES141-$533{\sim}545$, PS141-$482{\sim}518$ and RS141-$611{\sim}628$ that is same with Test Number I of ANSI C57.12.20.

  • PDF

The Thermal Analysis of Pole Mount Mold Transformer with One-body Molding by Duct Condition (일체형 주상용 몰드변압기의 덕트에 따른 열해석 특성 연구)

  • Cho, Han-Goo;Lee, Un-Yong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07b
    • /
    • pp.1135-1138
    • /
    • 2003
  • The transformer is major equipment in power receiving and substation facilities. Necessary conditions required for the transformer are compactness, lightness, high reliability, economic advantages, and easy maintenance. The pole-mount transformer installed in distribution system is acting direct role in supply of electric power and it is electric power device should drive for long term. Most of modem transformer are oil-filled transformer and accident is happening considerable. The mold transformers have been widely used in underground substations in large building and have some advantages in comparison to oil-transformer, that is low fire risk, excellent environmental compatibility, compact size and high reliability. In addition, the application of mold transformer for outdoor is possible due to development of epoxy resin. The mold transformer generally has cooling duct between low voltage coil and high voltage coil. A mold transformer made by one body molding method has been developed for small size and low loss. One body molding transformer needs some cooling method because heat radiation between each winding is difficult. In this paper, The thermal analysis of pole mount mold transformer with one body molding by duct condition is investigated and the test result of temperature rise is compared with simulation data.

  • PDF