• 제목/요약/키워드: 조한구

검색결과 232건 처리시간 0.025초

송전선용 현수애자 양생공정에서 발생하는 접착부의 응력변화 (Stress Response of Cement Interface on Manufacturing Process of a Suspension Insulator)

  • 우병철;한세원;조한구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1448-1450
    • /
    • 2003
  • The suspension insulators are subjected to harsh environment in service for a long time. Long term reliability of the insulators is required for both mechanical and electrical performances. We studied an analysing method to find out a deformation of brittle porcelain with a thermal expansion of simulation analysis and experimental results show that cement volume growths affect severely to be mechanical failure ageing.

  • PDF

직류 전차 탑재형 피뢰기의 하우징 설계 및 성능평가 (Performance Evaluation and Housing Design for Direct Current Surge Arrester in Railway Rolling Stock)

  • 조한구;김석수;한세원;이운용
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.128-131
    • /
    • 2000
  • The main objective of this paper is to design and test a new type of polymer ZnO surge arrester for DC power system of railroad vehicles. The rated voltage is 1500V direct current. The main research works are focused on structure design by finite element method, rating voltage, temporary over voltage and studies of characteristics of polymeric surge arrester.

  • PDF

170kV급 단로기용 Composite Insulator 제조기술에 관한 연구 (A Study on the manufacturing Composite Insulator for 170kV D/S)

  • 진상용;;이동원;송원표;송희석;조한구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.34-36
    • /
    • 2002
  • The objective of this study is to develop the composite insulator for 170kA disconnecting switch. In this paper, we have investigated the test procedure about each component(FRP tube, flange, shed) through technical standard(IEC 61462) and obtained demand characteristics by mechanical & electrical property test.

  • PDF

전철 탑재 피뢰기용 MOV 소자 임펄스 특성 (Impulse Characteristics of MOV Elements for Railroad Vehicle Arrester)

  • 한세원;조한구;이형구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 D
    • /
    • pp.1529-1531
    • /
    • 1999
  • The main functions of AC railroad vehicles arresters is to protect the main transformer from lightening impulse or switching impulse surge, then the MOV(metal oxide varistor) elements rated of 10kA is applied. The residual voltage and surge energy absorption are important parameters in designing arrester, these must be carefully decided with considering protecting level of impulse environment of system. The purpose of this study is to discuss the residual voltages and the energy absorption capability by impulse currents on MOV elements for railroad vehicles, and to introduce design factors which act as optimal protecting condition against impulse currents.

  • PDF

폴리머 피뢰기의 고장전류에 대한 방압 설계기술에 관한 연구 (Study on the relief design for the fault current of polymer arrester)

  • 김인성;박효열;조한구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 D
    • /
    • pp.1717-1719
    • /
    • 1999
  • The chief advantage of polymer arrester. from design of pressure relief, anti-contamination, electrical failure was reduced by outdoor polymer housing. In the first for development of pressure relief design for polymer arrester, fault current and surge were studied through experiments of electrical. Designed the FRP inner tube and unit modules for pressure relief housing. Tested the performance of unit modules for pressure relief of polymer arrester, and the result was successful. The pressure relief of polymer arrester depend on design pattern of diamond shape and ellipse. Study on the pressure relief of FRP inner tube for outdoor polymer arrester. Designed and manufactured FRP inner tube of polymer arrester. Tested the fault current of polymer arrester per 10 kA, 10 cycle.

  • PDF

피뢰기 열화진단에 있어 전원 고조파의 영향과 보정에 관한 연구 (A Study on the Influence of Harmonics in Power System Voltage on Arrester Diagnostics and its Compensation)

  • 김일권;송재용;한주섭;길경석;류길수;조한구
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제54권11호
    • /
    • pp.493-497
    • /
    • 2005
  • This paper dealt with the influence of harmonic voltages on arrester diagnostics and its compensation method by using a designed Pspice arrester model. A pure sinusoidal voltage and its 3$^{rd}$ harmonic voltage were applied to the model, and the leakage current components were analyzed. The simulation results have shown that the peak value of resistive leakage current depends not only on the phase of the 3$^{rd}$ harmonic voltage but also on the magnitude of it. In this paper, an approximated 5$^{th}$ order polynomial formula by the Least-Square-Technique was derived, and correction factors which compensate the error caused by the 3$^{rd}$ harmonic voltage were calculated.

초고압 현수애자의 Pin 형상에 따른 응력해석 (The Temperature Distribution Analysis and Temperature Rise Test of Pole Mold Transformer)

  • 조한구;박기호;한세원;윤문수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.155-157
    • /
    • 2001
  • Various types suspension insulators made of toughness glass or porcelain are used in the power transmission. And, Insulators are continually subject to mechanical and electrical stresses which depend on the characteristics of the line. The main factor that influence the increase in reliability of insulators. In operation is the capacity of the design to withstand the certain load over a long time, the mechanical strength of the insulators. This paper describes the results of a study on the stress analysis of suspension insulator based on the finite element analysis using NASTRAN. And, the mechanical strength was evaluated through such as kinds of pin type.

  • PDF

154kV 지중 방식층용 ZnO소자 및 서지 보호장치 성능 (The Performance of ZnO Varistors and Surge Protector for 154kV Underground Cable)

  • 조한구;한동회;윤한수;이종혁;장태봉;이형구
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.248-250
    • /
    • 2001
  • The surge protector is crucial power apparatus to guarantee the safe operation of power transmission of underground cable which can effectively restrain the overvoltage and inductive lightning stroke in power system. This paper describes the results of a study on the performance of ZnO varistors and surge protector for 154 kV underground cable. And, the influence of water tight and insulating performance was evaluated through such as surge protector of the armored design.

  • PDF

Design Optimization and Performance of High Voltage Composite Bushing

  • 조한구;강형경
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2009년도 추계학술대회 논문집
    • /
    • pp.234-234
    • /
    • 2009
  • This paper illustrates the use of electric field computation to optimize the design of high voltage composite bushing. In the bushing, a high electric stress occurred between field shaper and central conductor by the closely space. Also coaxial cylindrical shield has a great height along the axis to control an electric field. Consequently, all the potentials are raised axially along the field shaper and electric stress is concentrated on a part of the surface of the FRP tube near the upper end of the field shaper. Maxwell 2D simulator based on the boundary element method was also introduced in order to verify the reliability of the polymer bushing. The optimized design uses internal elements for electric stress grading at critical parts of the bushing.

  • PDF

와인딩 장력이 composite 부싱용 FRP tube의 굽힘변형에 미치는 영향 (Effect of The Bending Strain of FRP Tube for Composite Bushing with Winding Tension)

  • 조한구;유대훈;강형경
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2009년도 하계학술대회 논문집
    • /
    • pp.380-381
    • /
    • 2009
  • This paper describes effect of the bending strain of FRP tube for composite bushing with winding tension. The composite bushing can be formed, by adding silicone rubber sheds to a tube of composite materials. The FRP tube is internal insulating part of a composite bushing and is designed to ensure the mechanical characteristics. Generally the properties of FRP tube can be influenced by the winding angle, wall thickness and winding tension. As winding tension is increased glass contents was increased in the range of 70.4~76.6%. In the bending test, winding tension is increased residual displacement was decreased in the range of 14.0~12.2 mm.

  • PDF