Thermal Performance of an Enthalpy Exchanger Made of Paper at Different Outdoor Temperatures and Humidities (외기 온·습도 변화에 따른 종이재질 전열교환 엘리먼트 성능에 관한 연구)

  • Kim, Nae-Hyun;Lee, Eul-Jong;Song, Kil-Sup;Oh, Wang-Kyu
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.34 no.7
    • /
    • pp.697-702
    • /
    • 2010
  • An enthalpy exchanger in which heat and moisture transfer occur between the indoor and outdoor air operates at various outdoor conditions. In this study, the effect of the outdoor-air temperature and humidity on the performance of an enthalpy exchanger was experimentally investigated. An apparatus was specially-made to accurately measure the incoming and outgoing dry- and wet-bulb air temperatures as well as the flow rates. Tests were conducted in constant-temperature and constant-humidity chambers at different outdoor temperatures and humidities. It is shown that the effectiveness of latent-heat exchange increases as the relative humidity increases; further, this effect exhibited minimal dependence on the absolute humidity. However, the effectiveness of sensible-heat exchange is independent of both temperature and humidity

Study on the Performance of Total Heat Exchanger with Rotating Porous Plates (다공형 전열판의 회전에 의한 열교환시스템의 성능에 관한 연구(Ⅱ) - 전열판의 회전수 변환에 대하여 -)

  • Lim, T.W.;Cho, D.H.
    • Journal of Power System Engineering
    • /
    • v.9 no.4
    • /
    • pp.18-23
    • /
    • 2005
  • The experimental investigation was carried out to evaluate the performance of air-to-air heat exchanger with rotating porous plates newly developed in this study. The rotating porous plates are mounted with an equal interval of 18 mm inside the heat exchanger where the hot and cold airs enter at opposite ends. When flowing in opposite directions by the separating plate installed in the center of the rotating porous plates, the airs give and receive the heat each other. The material of the porous plate is cooper and its thickness is 1.0 mm. Air flow rate is varied from 10 to 120 m3/h. From the experiment of air-to-air heat exchanger with the rotating porous plates, the heat exchange performance increased with the increase in RPM of the porous rotating discs at the conditions of the same air flow rate. The sensible heat exchange efficiency was maximum 60 to 70 percent, and enthalpy exchange efficiency 50 to 60 percent.

  • PDF

A Study on Operating Method by Energy Evaluation and Performance Evaluation of Heat Recovery Ventilator According to Outdoor Conditions (전열교환 환기시스템의 외기변화에 따른 성능평가 및 에너지평가를 통한 운전방안에 관한 연구)

  • Kim, Kwang-Hyun;Yee, Jurng-Jae
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.20 no.1
    • /
    • pp.57-64
    • /
    • 2008
  • Recently, regulation of ventilator installation and its details has been revised and the establishment of heat recovery ventilator in newly built apartments has been obligated. This study was done to offer the method of operation and design of heat recovery ventilator to save energy by measuring its efficiency and comparing with the results of experiment. This paper confirmed that it is desirable to operate heat recovery ventilator by using "by-pass mode" within $60{\sim}80%$ scope of the difference indoor absolute humidity in spring and autumn and outdoor absolute humidity and heat recovery ventilator of energy saving effect is better than constant air volume system.

Study on the Performance of Total Heat Exchanger with Rotating Porous Plates (다공형 전열판의 회전에 의한 열교환시스템의 성능에 관한 연구(Ⅰ) - 환기측과 외기측의 풍량 변화에 대하여 -)

  • Cho, D.H.;Lim, T.W.
    • Journal of Power System Engineering
    • /
    • v.9 no.4
    • /
    • pp.11-17
    • /
    • 2005
  • This paper reports an experimental study on the performance evaluation of air-to-air heat exchanger with rotary type newly developed in this study. Air flow rate is varied from 10 to 120 m3/h. The range of RPM of the porous rotating discs mounted inside the heat exchanger unit is 0 to 50. The temperature of the return air side is set by adjusting heat supply at heater. The material of the porous rotating discs is cooper and its thickness is 1.0 mm. The heat transfer rate increased with the increase in air flow rate. It was found that the heat transfer rate, as the temperature of the return air side was increased, was improved due to higher temperature difference. The heat exchange performance increased with the increase in the temperature of the return air side at the conditions of the same RPM. The sensible heat exchange efficiency was maximum 68 to 76 percent, and enthalpy exchange efficiency 64 to 74 percent.

  • PDF

An Experimental Study on the Long-Term Performance Variation of the Plate-Type Enthalpy Exchange Element Made of Paper (판형 종이 재질 전열교환 소자의 장기 성능 변화에 대한 실험적 연구)

  • Kim, Nae-Hyun
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.28 no.4
    • /
    • pp.165-170
    • /
    • 2016
  • Long-term performance of the enthalpy exchange element is a topic of current interest due to the concern of possible performance degradation over time. In this study, a 350 CMH enthalpy recovery ventilator equipped with an enthalpy exchange element was installed in an office room, and the performance has been traced over the past 5 years. The appearance, overall dimension, thermal performance, leakage ratio and anti-bacterial performance were checked annually. Results showed that the change in thermal performance (sensible, latent and enthalpy efficiency) was negligible with periodic cleaning with an air gun. However, the leakage ratio increased with time, measuring 7.3% after 5 years. Anti-bacterial test revealed that no bacteria were found during the test period. The largest change in the dimension occurred at the middle location of the element, although the change was less than 2% of the initial value.

증기발생기 전열관에서의 숏 피닝에 의한 잔류응력분포 모델 및 균열 해석

  • 신규인;박재학;김홍덕;정한섭
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2000.06a
    • /
    • pp.1-6
    • /
    • 2000
  • 가압 경수로의 증기발생기는 원자로(reactor vessel)와 가압기(pressurizer)에서 가열ㆍ가압된 1차 계통의 고온, 고압수가 터빈을 돌리는 2차 계통수와 열교환을 일으켜 고온ㆍ고압의 증기를 발생시키는 것으로, 전열관의 파손이 발생될 경우 1차 계통에서 2차 계통으로 방사능 물질이 누출되어 심각한 문제가 야기된다. 따라서 증기발생기의 전열관 손상이나 파손 문제는 원자력 발전소의 수명과 밀접한 관계가 있다. (중략)

  • PDF

A Study on the Dew Condensation According to the Operational Conditions of a Heat-Recovery Ventilator (전열교환 환기시스템의 운전 상태에 따른 결로 발생에 관한 연구)

  • Jeon, Byung-Heon;Kim, Jong-Won;Lee, Seung-Kap;Lee, Young-Ju;Ahn, Young-Chull
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.10
    • /
    • pp.529-533
    • /
    • 2013
  • Heat-recovery ventilators are being adopted in most newly built apartment houses for energy reduction and indoor environment improvement. In winter, however, the dew condensation resulting from the difference between the indoor and outdoor temperatures may reduce the ventilator's performance and threaten the health of indoor residents. This study analyzes the occurrence of dew condensation according to the ventilator's operational conditions and the changes of temperature and products. The experimental results show that condensations is formed at $26^{\circ}C$ and 60%R.H, which is an unfavorable climatic condition, and when the damper is not closed tightly. Therefore it is important to ensure damper performance to prevent back flow.