• Title/Summary/Keyword: 이산화탄소의 열전달 계수

Search Result 32, Processing Time 0.024 seconds

Experimental Study on Characteristics of Evaporation Heat Transfer of CO2 in a Smooth Tube (평활관에서 이산화탄소의 증발열전달 특성에 관한 실험연구)

  • Lee, Sang-Jae;Choi, Jun-Young;Lee, Jae-Heon;Kwon, Young-Chul
    • Journal of Energy Engineering
    • /
    • v.16 no.4
    • /
    • pp.181-186
    • /
    • 2007
  • In order to investigate the heat transfer coefficient and pressure drop during evaporation of $CO_2$, basic experiment on the evaporation heat transfer characteristics in a horizontal smooth tube was performed. The experimental apparatus consisted of a test section, a DC power supply, a heater, a chiller, a mass flow meter, a pump and a measurement system. Experiment was conducted for various mass fluxes ($200{\sim}1200\;kg/m^2s$), heat fluxes ($10{\sim}80\;kW/m^2$) and saturation temperatures ($-5{\sim}5^{\circ}C$). With the increase of quality, the evaporation heat transfer coefficient decreased. With the increase of heat flux, the evaporation heat transfer coefficient increased. Significantly change of the heat transfer coefficient was observed at any heat flux and mass flux. With the increase of saturation temperature, the heat transfer coefficient increased. Pressure drop increased with the increase of mass flux and the decrease of saturation temperature.

Heat Transfer Characteristics of Carbon Dioxide in a Inclined Helical Coil Type Heat Exchanger with Inner Diameter Tube of 4.55 mm (내경 4.55 mm의 경사진 헬리컬 코일형 열교환기내 이산화탄소의 열전달 특성에 관한 연구)

  • Son, Chang-Hyo
    • Journal of the Korean Institute of Gas
    • /
    • v.11 no.3
    • /
    • pp.1-6
    • /
    • 2007
  • The heat transfer coefficient and pressure drop during gas cooling process of $CO_2$ (R-744) in inclined helical coil copper tubes were investigated experimentally. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and a inclined helical coil type gas cooler (test section). The test section consists of a smooth copper tube, which is specified as the inner diameter of 4.55 mm. The refrigerant mass fluxes were varied from 200 to $600kg/m^2s$ and the inlet pressures of gas cooler were done 7.5 to 10.0 (MPa). The heat transfer coefficients of $CO_2$ in the inclined helical coil tubes increase with the increase of mass flux and gas cooling pressure of $CO_2$. The pressure drop of $CO_2$ in the gas cooler shows relatively good coincidence with those predicted by Ito's correlation developed for single-phase in a helical coil tube. The local heat transfer coefficient of $CO_2$ is well coincident with the correlation by Pitla et al. However, at the region near pseudo-critical temperature, the experiments indicate higher values than the Pitla et al. correlation.

  • PDF

Heat Transfer Characteristics of Supercritical $CO_2$ in Helical Coil Gas Coolers on the Change of Coil Diameters (코일직경변화에 따른 헬리컬 코일형 가스냉각기내 초임계 이산화탄소의 냉각열전달 특성)

  • Son, Chang-Hyo
    • Journal of the Korean Institute of Gas
    • /
    • v.11 no.3
    • /
    • pp.44-48
    • /
    • 2007
  • The cooling heat transfer characteristics of supercritical $CO_2$ in a helical coil gas cooler on the change of coil diameters are experimentally investigated. The main components of the refrigerant loop are a receiver, a variable speed pump, a mass flow-meter, a pre-heater and a helical coil gas cooler (test section). The test sections are made of a copper tube which the inner diameter is 4.55 mm and the helical coil diameters are done of 26.75 mm and 41.35 mm. The mass fluxes of refrigerant are varied from 200 to 800 [$kg/m^2s$] and the inlet pressures of gas cooler are 7.5 to 10.0 (MPa). A gas cooler with helical coil diameter of 26.75 mm has larger heat transfer coefficient than that of 41.35 mm. Also, when compared with experimental data and published correlations avaliable, most of correlations are under-predicted, but Pitla published correlations avaliable, most of correlations are under-predicted, but Pitla et al.'s correlation shows a relatively good coincidence with the experimental data except the region of pseudo critical temperature.

  • PDF

Effect of the lubrication oil on heat transfer and pressure drop characteristics of supercritical carbon dioxide in a microfin tube (마이크로핀관내 냉동기유가 초임계 이산화탄소의 열전달과 압력강하에 미치는 영향)

  • Ku, Hak-Keun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.13 no.4
    • /
    • pp.1440-1446
    • /
    • 2012
  • This paper presents an experimental study of heat transfer and pressure drop characteristics of supercritical carbon dioxide with PAG inside a horizontal microfin tube. Heat transfer coefficient and pressure drop gradients were measured at 10 MPa in pressure and 520 kg/$m^2s$ in mass flux with variation of PAG mass concentration from 0.06% to 2.26%. The tendencies of both heat transfer and frictional pressure drop characteristics show the same as those of pure $CO_2$ up to 0.3% in PAG mass concentration. In case of 2.26% in PAG mass concentration, measured heat transfer coefficients showed 50% lower than those of pure $CO_2$ near the pseudocritical temperature and measured frictional pressure drop gradients show 1.6 times higher in comparison with those of pure $CO_2$ at $60^{\circ}C$ in $CO_2$ bulk temperature.

The heat transfer characteristics of supercritical $CO_2$ in a horizontal tube (수평관내 $CO_2$의 초임계 영역내 열전달에 관한 연구)

  • Oh Hoo-Kyu;Lee Dong-Geon;Son Chang-Hyo
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.29 no.5
    • /
    • pp.526-532
    • /
    • 2005
  • The cooling heat transfer coefficient of $CO_2$(R-744) in a horizontal tube was investigated experimentally. The experiments were conducted without oil in a closed refrigerant loop which was driven by a magnetic gear pump. The main components of the refrigerant loop are a receiver, a variable-speed pump. a mass flow meter. a pre-heater and gas cooler(test section). The test section consists of a smooth, horizontal stainless steel tube of 7.75 mm inner diameter. The experiments were conducted at mass flux of 200 to $400\;kg/m^{2}s$ and the inlet cooling pressure of 7.5 MPa to 10.0 MPa. The variation of heat transfer coefficient tends to decrease as cooling pressure of $CO_2$ increases. The heat transfer coefficient with respect to mass flux increases as mass flux increases. The pressure drop of $CO_2$ in the gas cooler shows a relatively good agreement with that predicted by Blasius's correlation. The local heat transfer coefficient of $CO_2$ agrees well with the correlation by Bringer-Smith.

Evaporation Heat Transfer and Pressure Drop of Carbon Dioxide In a Horizontal Tube (수평관내 이산화탄소의 증발 열전달과 압력강하)

  • Son, Chang-Hyo
    • Transactions of the Korean hydrogen and new energy society
    • /
    • v.18 no.2
    • /
    • pp.189-196
    • /
    • 2007
  • The evaporation heat transfer coefficient and pressure drop of $CO_2$(R-744) in a horizontal tube was investigated experimentally. The main components of the experimental apparatus are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and an evaporator(test section). The test section consists of a horizontal stainless steel tube of 4.57 mm inner diameter. The experiments were conducted at mass flux of $200{\sim}1000\;kg/m^2s$ saturation temperature of $0{\sim}20^{\circ}C$, and heat flux of $10{\sim}40\;kW/m^2$. The test results showed that the heat transfer coefficient of $CO_2$ has a greater effect on nucleate boiling more than convective boiling. Mass flux of $CO_2$ does not affect nucleate boiling too much. In comparison with test data and existing correlations, All of the existing correlations for the heat transfer coefficient underestimated the experimental data. However lung et al.'s correlation showed a good agreement with the experimental data. The evaporation pressure drop of $CO_2$ increases with increasing mass flux and decreasing saturation temperature. When comparison between the experimental pressure drop and existing correlations. Existing correlations failed to predict the evaporation pressure drop of $CO_2$.

Cooling Heat Transfer Characteristics of Carbon Dioxide in a Horizontal and Helically Coiled Tube (수평관과 헬리컬 코일관내 이산화탄소의 냉각 열전달 특성)

  • Son, Chang-Hyo
    • Transactions of the Korean Society of Automotive Engineers
    • /
    • v.16 no.1
    • /
    • pp.121-126
    • /
    • 2008
  • The cooling heat transfer coefficient of $CO_2$ (R-744) in a horizontal and helically coiled tube was investigated experimentally. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater, evaporator and gas cooler (test section). The test section consists of a horizontal stainless steel tube and hellically coiled copper tube of 4.57 and 7.75 mm. The experiments were conducted at saturation temperature of 100 to $20^{\circ}C$, and mass flux of 200 to $500kg/m^2s$. The test results showed the variation of the heat transfer coefficient tended to decrease as cooling pressure of $CO_2$ increased. The heat transfer coefficient with respect to mass flux increased as mass flux increased. The experimental results were also compared with the existing correlations for the supercritical heat transfer coefficient, which generally underpredicted the measured data. However, the experimental data showed a relatively good agreement with the correlations of Pitla et al. except for the pseudo critical temperature.

Thermophysical Properties of CO2 and CO2-Hydrate Mixture and In-Tube Heat Transfer Characteristics (CO2-Hydrate와 CO2 가스 혼합물의 전달물성과 관내측 열전달계수 및 압력강하 예측)

  • Yun, Rin
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.25 no.5
    • /
    • pp.233-239
    • /
    • 2013
  • The Thermophysical properties of thermal conductivity, viscosity, and heat capacity for $CO_2$ slurry ($CO_2$ gas and $CO_2$-hydrate mixture) having a high gas phase volume fraction were predicted using the conventional mixture models and the TRAPP model under hydrate formation conditions. Based on the calculated thermophysical properties, the heat transfer coefficient and pressure drop of the $CO_2$ slurry in the tube were predicted. The thermal conductivity of $CO_2$ slurry ranged from 0.02 to 0.2 W/m-K, and the mixture viscosity was larger than that of pure $CO_2$ by 1.9~2.7 times. The heat capacity of $CO_2$ slurry ranged from 63 to 68% of that for pure $CO_2$. The predicted heat transfer coefficient of $CO_2$ slurry was 6 times higher than that of pure $CO_2$. In the separate model, the estimated pressure drop increased with an increase of $CO_2$-hydrate mole fraction, and was 60% of that of pure $CO_2$.

Evaporative Heat Transfer Characteristics of Carbon Dioxide in a Horizontal Tube (수평관내 이산화탄소의 증발 열전달 특성)

  • Son Chang-Hyo;Lee Dong-Gun;Kim Young-Lyoul;Oh Hoo-Kyu
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.12
    • /
    • pp.1134-1139
    • /
    • 2004
  • The evaporative heat transfer coefficient of $CO_2$ (R-744) in a horizontal tube was investigated experimentally. The experiments were conducted without oil in a closed refrigerant loop which was driven by a magnetic gear pump. The main components of the refrigerant loop are a receiver, a variable-speed pump, a mass flow meter, a pre-heater and evaporator (test section). The test section consists of a smooth, horizontal stainless steel tube of inner diameter of 7.75 mm. The experiments were conducted at mass flux of 200 to 500 kg/m$^2$s, saturation temperature of -5 to 5$^{\circ}C$, and heat flux of 10 to 40kW/m$^2$. The test results showed the heat transfer of $CO_2$ has a greater effect on nucleate boiling more than convective boiling. Mass flux of $CO_2$ does not affect nucleate boiling too much, and the effect of mass flux on evaporative heat transfer of $CO_2$ is much smaller than that of refrigerant R-22 and R-134a. In comparison with test results and existing correlations, correlations failed to predict the evaporative heat transfer coefficient of $CO_2$, therefore, it is necessary to develope reliable and accurate predictions determining the evaporative heat transfer coefficient of $CO_2$ in a horizontal tube.

Heat Transfer and Pressure Drop of $CO_2$ Gas Cooler in a Helically Coiled Tube (헬리컬코일형 $CO_2$ 가스쿨러의 열전달과 압력강하)

  • Kyoung, Nam-Soo;Yu, Tae-Guen;Son, Chan-Hyo;Oh, Hoo-Kyu
    • Proceedings of the Korean Society of Marine Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.246-247
    • /
    • 2005
  • The paper presents the heat transfer characteristics during cooling process of carbon dioxide($CO_2$) in a helically coiled tube. The main components of the apparatus consist of a receiver, a variable speed pump, a mass flowmeter, a pre-heater, a gas cooler(test section) and an isothermal tank. The test section with the inner diameter 4.55 [mm] is a tube in tube type heat exchanger with refrigerant flowing in the inner tube and water flowing in the annulus. The main results were summarized as follows : The heat transfer coefficient increases with respect to the decrease of the gas cooler pressure in a supercritical region and the increase of the refrigerant mass flux. The pressure drop decreases in increases of the gas cooler pressure and increases with respect to increases the refrigerant mass flux.

  • PDF