한전 765kV 계통의 개폐과전압 해석 (Switching Overvoltage Analysis of KEPCO 765kV Transimission System)

  • 김정부;심응보;정재기;이용한
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1994년도 하계학술대회 논문집 C
    • /
    • pp.1622-1624
    • /
    • 1994
  • Among the power system overvoltages, switching overvoltages are analysed in this paper, using EMTP(Electro-Magenetic Transient Program ) and TNA(Transient Network Analyzer ). From this analysis, the switching overvoltages are used to determine the BSL(Basic Switching Withstand Level) and the clearance of the transmission tower. Up to now the switching overvoltages were analysed by EMTP, but in order to determine the more exact value of BSL, not only digital but also analog method is required.

  • PDF

낙뢰정보 실신간 통계분석시스템 개발 (Development of Real Time Analysis System about Lightning Information)

  • 곽주식;우정욱;심응보;김기운;김용수;이성진;이건웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.169-171
    • /
    • 2003
  • Because the overhead transmission lines are exposed to the outdoor weather, the faults of the transmission tines are due to natural conditions, and among these faults, the outage rate by lightning is about 50%. The lightning causes the damage of power system equipments, the shut down of electricity and the electro-magnetic interference. Therefore, the pertinent insulation design is important, not only to decrease the damage of the facility itself but also to increase the reliability of electric power system. For these reasons, we have to obtain and accumulate the lightning current parameters for the basic lightning research. This paper describes the development of real time analysis system about lightning information.

  • PDF

실시간 낙뢰화면 표시프로그램 개발 (Development of Heal Time Lightning Information System)

  • 곽주식;우정욱;심응보;김기운;김용수;이성진;이건웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.175-177
    • /
    • 2003
  • Because the overhead transmission lines arc exposed to the outdoor weather, the faults of the transmission lines are due to natural conditions, and among these faults, the outage rate by lightning is about 50%. The lightning causes the damage of power system equipments, the shut down of electricity and the electro-magnetic interference. Therefore, the pertinent insulation design is important, not only to decrease the damage of the facility itself but also to increase the reliability of electric power system. For these reasons, we have to obtain and accumulate the lightning current parameters for the basic lightning research. This paper describes the development of real time analysis system about lightning information.

  • PDF

LPATS에 의한 7년간의 한반도 뇌격특성분석 (Analysis of the lightning characteristics by LPATS Data during 7 year)

  • 우정욱;심응보;곽주식;권동진;문재덕;한상옥
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.509-511
    • /
    • 2003
  • Because the overhead transmission lines are exposed to the outdoor weather, the faults of the transmission lines are due to natural conditions, and among these faults, the outage rate by lightning is about 50%. The lightning causes the damage of power system equipments, the shut down of electricity and the electro-magnetic interference. Therefore, the pertinent insulation design is important, not only to decrease the damage of the facility itself but also to increase the reliability of electric power system. For these reasons, we have to obtain and accumulate the lightning current parameters for the basic lightning research. This paper describes the statistical distribution of lightning current parameters and the IKL map.

  • PDF

제어기 형태에 따른 HVDC 안정도 분석 (HVDC Stability Analysis According to Controller Types)

  • 김찬기;심응보;정길조;권동진;윤용범
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제49권10호
    • /
    • pp.665-674
    • /
    • 2000
  • This paper deals the HVDC system stability according to controller types. In this paper, in order to evaluate the stability, some important properties of the HVDC. such as $d{\tau}/d{\alpha}\;,\;dV/d{\alpha}$ and dP/dI stability in different control modes, are analysed. Furthermore, Maximum available power according to controller types are calculated. This paper shows a generated formulation of control sensitivity for control modes, aids in the design of the controller and the operating mode determination. Finally, a simulation is performed by Math/CAD, and a simulation results are verified.

  • PDF

4회선 인입철구 구조를 가진 154 kV 변전소의 뇌과전압 해석 (Lightning Surge Analysis in 154 kV S/S due to Flashover on the 4 Circuits Tower)

  • 우정욱;심응보;곽주식;최병준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.1888-1890
    • /
    • 2000
  • This paper describes the analysis results for the protection of lightning surge at 154 kV substation. We found that the surge arrester is needed at the inlet structure. The maximum overvoltage is about 1,500 kV at the circuit breaker without the surge arrester at the inlet structure. This value can be lower than 600 kV by installing the surge arrestor at the inlet structure. In addition to the incoming surge from transmission line, the shield wire should be considered to prevent the shielding failure by the direct lightning stroke.

  • PDF

비동기 전력계통 연계를 위한 Back-To-Back 직류설비의 운전특성 해석 (Analysis of Back-to-Back HVDC system featured for Asynchronous Connection)

  • 곽주식;우정욱;고봉언;김찬기;심응보
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 B
    • /
    • pp.1289-1291
    • /
    • 2000
  • The operation of Back-To-Back HVDC system for asynchronous connection is described. It can exchange electric power up to 300 MW between separately operated two rower systems, making the interaction on each system minimum. The analysis is done under three different AC transmission lines interconnected to BTB HVDC.

  • PDF

HVDC 전력변환기의 Commutation 동작분석 (Analysis of HVDC Converter Commutation Process)

  • 곽주식;우정욱;고봉언;김찬기;심응보
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 B
    • /
    • pp.1286-1288
    • /
    • 2000
  • Commutation failure can be considered as the severest abnormal operation of thyristor HVDC converter. During the failure, power conversion from DC to AC is stopped until the AC voltage get recovered. The process of thyristor converter is subscribed at normal and abnormal state, respectively. The detection and the protection for Cheju HVDC are explained by computer simulation results.

  • PDF

154 kV STATCON Bank용 콘덴서 셀 절연파괴 원인분석 (Analysis of a breakdown in 154 kV STATCON Bank condenser cell)

  • 주형준;권동진;강연욱;심응보;이상일;이흥호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.388-391
    • /
    • 2003
  • 154 kV 변전소에 설치 운전 중인 SC Bank 콘덴서 셀의 절연파괴 고장이 빈번하게 발생되어 전력계통의 운용 및 변전소 운전에 지장을 주는 사례가 많이 발생하였다. 따라서 이의 고장원인 진단을 통하여 대책수립을 하고자 EMTP(Electro-Magnetic Transient Program)를 이용하여 SC Bank의 정상상태시 과전압, 과전류에 의한 소손현상을 검토하고, 계통조건에 따른 공진점변화와 고조파에 따른 이상전압 및 콘덴서 셀 전압의 상승 현상을 검토 분석하고, 고조파 성분에 따른 과전압 및 과전류를 분석하여 대책을 제시한 사례연구의 결과이다.

  • PDF

송전선로 주변 통신선의 유도장해 원인 분석 (The Inductive Interference of Communication Line Near by Transmission Line)

  • 강연욱;곽주식;권동진;심응보;배주호;김재준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.400-402
    • /
    • 2003
  • The inductive interference can be happened on some of the communication line that is located near by paralleled transmission line. The causes of inductive interference are magnetic coupling, capacitive coupling and residual voltage at neutral point of transmission line. In this paper, after grounding the one side of communication line, we have measured the voltage to ground at the other side of it. And we also have measured the voltage to ground at the end of it without grounding. As a result, we proved that the cause of inductive interference is the difference of ground voltages.

  • PDF