Analysis on Thermal Environment in the Rotunda of New National Museum of Korea (새 국립중앙박물관 로튠다에서의 열환경 분석)

  • 이승철;조영진;김두성;이재헌;김홍범
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.1
    • /
    • pp.32-39
    • /
    • 2003
  • Thermal comfort in the Rotunda which is high wide visiting space of the new national museum of Korea has been numerically investigated in this paper. To evaluate thor-mal comfort of the Rotunda, well-known indices, PMV and PPD were introduced. The results of present investigation show that thermal comfort is satisfied at the breathing zone of the visiting space. However a thermal stratification with $9^{\circ}C$ of temperature difference occurs along the height of the Rotunda which makes the thermal environment worse. For example, the PPD value reaches up to 50% in the 6th floor connection passage. Consequently, additional HVAC design factors should be considered in order to reduce the large thermal stratification.

Characteristics of thermal comfort for artificial environment experiment in summer (하계 인공환경실험에서의 온열쾌적특성)

  • 박종일;김경훈;홍희기;민병일;김창주
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.10 no.3
    • /
    • pp.368-377
    • /
    • 1998
  • The purpose of this study was to examine theory about indoor thermal comfort-environment as well as to determine thermal sensation and physiological responses for men in summer indoor environment, under various air temperature and relative humidity, with male university students. Subjective Evaluation, Heart Rate(Electrocardiogram), Electroencephalogram(EEG) were examined. We found that comfort of people was achieved at SE $T^{*}$ 24.7$^{\circ}C$, -0.82<PMV<0.93, subject's clothing(0.41c1o)and the difference of skin temperature was found at the calf area as air temperature changes. At low SE $T^{*}$, heart rate was decreased and at high SE $T^{*}$, heart rate was increased but there was no change EEG(keeping $\alpha$-wave).wave).

  • PDF

Effect of the Vertical Air Circulation on the Thermal "Environment in a Large Space (대공간 열환경 특성에 관한 수직순환기류의 영향)

  • 김경환;강석윤;최충현;조영진;이재헌;오명도
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.6
    • /
    • pp.581-588
    • /
    • 2000
  • This paper describes the effect of vertical air circulation on the thermal environment in an airport passenger terminal with induced flow by jet fans. In comparing the level of thermal comfort at the breathing line of 1.5 m in height, the results from the two models with or without the vertical air circulation, show that the average PPD is 8% in the former and 23% in the latter, respectively. It is thought that vertical air circulation lends to improved thermal comfort for human in respect of ventilation in a large space.

  • PDF

Characteristics of Thermal Environments and Evaluation of Thermal Comfort in Office Building in Summer (여름철 사무실내 온열환경 특성 및 쾌적성 평가)

  • Lee, C.H.;Bae, G.N.;Choi, H.C.;Lee, C.S.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.6 no.3
    • /
    • pp.206-217
    • /
    • 1994
  • In this study, indoor thermal parameters were measured to investigate the characteristics of thermal environments and 212 occupants were questioned to evaluate Korean thermal comfort in office building in summer. Thermal and comfort sensations were estimated using PMV(Predicted Mean Vote) and ET* (New Effective Temperature) which are most widely used nowadays. Comparing this experimental result with international standards and that of other research, Korean thermal responses were discussed. It was found that TSV(Thermal Sensation Vote) is more sensitive than PMV to the variation of temperature and that the measured percentage of dissatisfied is higher than PPD(Predicted Percentage of Dissatisfied) in real office building environments. By regression analysis, the following regression equation has been obtained: TSV=0.461ET*-11.808 and neutral temperature is $25.6^{\circ}C$ in this case. Thermal comfort range based on 80% satisfaction is also $24.0{\sim}26.8^{\circ}C$, which is about $1^{\circ}C$ higher than that of ANSI/ASHRAE Standard.

  • PDF

Evaluation on Thermal Environment Installed Ventilating Fans in the Rotunda at New National Museum of Korea (기류유인팬을 이용한 새 국립중앙박물관 로튠다에서의 열환경 평가)

  • 이승철
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.3
    • /
    • pp.303-309
    • /
    • 2004
  • In order to improve thermal comfort in the Rotunda, which is high and wide visiting space of the new national museum of Korea, eight ventilating fans were installed near the ceiling of Rotunda. It has been analyzed thermal comfort of Rotunda with/without ventilating fans by numerical simulation. To evaluate thermal comfort of the Rotunda, well-known indices, PMV and PPD were introduced. The results of present investigation show that temperature distribution of the case with fans is closer to target temperature than the case with-out fans at the breathing zone. In the case without fans, thermal stratification with 16$^{\circ}C$ of temperature difference occurs along the height of the Rotunda which makes the thermal environment worse and the PPD values reach up to 50% in the 6th floor connection passage. In the case with fans, however, the vertical temperature difference were reduced to 9$^{\circ}C$ and the PPD values were lower below 20%. Consequently, the ventilating fans adopted on this study are effectively used for improving the thermal comfort in large space structure with thermal stratification.

Evaluation of Comfort Performance for Modernized Hanok: Targeting Hanok Residence at the Jamjeong-Haetsal Village in Hwasun, Jeonnam Province (신한옥의 쾌적성능 평가: 전남 화순 잠정햇살마을 한옥단지를 대상으로)

  • Choe, Seung-Ju;Lee, Mihyang;Kim, Jae-Hyang;Han, Seung-Hoon
    • Land and Housing Review
    • /
    • v.12 no.2
    • /
    • pp.99-108
    • /
    • 2021
  • With increasing interest in living in hanoks, there's a growing need for more quantitative data on the thermal comfort performance of modern hanoks. With that in mind, this research project studied a modern hanok located in Jamjeong-Haetsal Village in Hwasun, Jeollanam Province as a case study to evaluate the Predicted Mean Vote (PMV) of modernized hanoks. Based on environmental data collected at the hanok and computer simulation both Life-Cycle PMV (L.C.PMV) and Normal PMV (N.PMV) were calculated for the hanok. Study results showed that during the summer and winter seasons the PMV and heat index at major heat and major cold weather points significantly deviated from the comfort zone. The rate of change in PMV was also greater in the winter than in the summer. The study found that the modern hanok lacks proper thermal insulation for maintaining thermal comfort.

Thermal Comfort and the Physiological and Psychological Effects of Spending Time in Broad-Leaved Forests in Summers (여름철 활엽수림에서의 휴식이 온열환경 쾌적성 및 인체의 생리ᐧ심리적 반응에 미치는 영향)

  • Juhyeon Kim;Injoon Song;Choyun Kim;Dawou Joung;Yunjeong Yi;Bum-Jin Park;Chorong Song
    • Journal of Korean Society of Forest Science
    • /
    • v.112 no.4
    • /
    • pp.544-553
    • /
    • 2023
  • The purpose of this study was to reveal the thermal comfort and physiological and psychological effects of spending time in broad-leaved forests in suumer. Thirty-one university students (with an average age of 21.4 ± 2.1 years) participated in the study, and a within-subjects experimental design methodology was used. The participants moved to an experimental site (with a crown closure of 76.6%) or a control site (25.9%), sat on a chair to eliminate the impact of movement, and rested for 5 minutes with closed eyes. At this time, thermal comfort, heart rate variability, heart rate, and forehead temperature were continuously measured. After that, blood pressure and pulse rate were measured, and a subjective evaluation was conducted. As a result, spending time at an experimental site showed a statistically significant decrease in the predicted mean vote and the percentage of dissatisfied values, enhancement of parasympathetic nerve activity, decrease of forehead temperature, diastolic blood pressure, heart rate, pulse rate, and improvement of personal thermal sensation (thermal sensation vote and comfort sensation vote). In conclusion, it was found that a forest with high crown closure reduces thermal stress and induces physiological and psychological relaxation.

Temporal Changes in the Physiological and Psychological Relaxation Effects of a Forest Environment during the Summer (시간 변화에 따른 여름철 산림환경의 생리ᐧ심리적 안정 효과)

  • Injoon Song;Juhyeon Kim;Choyun Kim;Dawou Joung;Yunjeong Yi;Bum-Jin Park;Chorong Song
    • Journal of Korean Society of Forest Science
    • /
    • v.113 no.1
    • /
    • pp.107-117
    • /
    • 2024
  • This study investigated temporal changes in forest physical variables and their effects on thermal comfort and physiological and psychological responses. Environmental factors (air temperature, mean radiant temperature, wind speed, and relative humidity), the predicted mean vote (PMV), and the predicted percentage of dissatisfied (PPD) visitors were continuously measured between 9:00 AM and 6:00 PM. We assessed the physiological and psychological responses (heart rate variability, heart rate, oral temperature, blood pressure, pulse rate, thermal sensation vote, comfort sensation vote, and subjective feelings) of 30 male university students (average age: 21.7±1.9 years), who closed their eyes and relaxed for 5 minutes every hour. Examination of correlations between environmental factors and physiological responses showed that ① the mean radiant temperature, wind speed, and relative humidity significantly changed with time; ② PMV and PPD also showed significant changes over time, and the thermal sensation vote corresponded with PMV; however, the comfort sensation vote did not correspond with PPD; ③ Among the physiological responses, parasympathetic nerve activity, sympathetic nerve activity, heart rate, and diastolic blood pressure significantly varied with time, with parasympathetic nerve activity having the lowest value and sympathetic nerve activity the highest at the highest air temperature (2:00-4:00 PM); and ④ Air temperature, mean radiant temperature, and wind speed showed a negative correlation with parasympathetic nerve activity and a positive correlation with sympathetic nerve activity. These findings indicate that the relaxation effects of the forest environment depend on what time of day people are exposed to it, and the changes occurring in forest environmental factors over time modulate these effects.