• Title/Summary/Keyword: 열 감지기

Search Result 96, Processing Time 0.033 seconds

A Study on Fire Alarm Test of IoT Multi-Fire Detector combined Smoke/CO and Smoke/Temperature Sensors (연기/CO 및 연기/열 복합형 IoT 멀티 화재 감지기의 화재감지실험 연구)

  • Son, Geun­Sik;So, Soo­Hyun
    • Journal of the Society of Disaster Information
    • /
    • v.17 no.2
    • /
    • pp.236-244
    • /
    • 2021
  • Purpose: The purpose of this study is to develop IoT multi-fire detectors combined smoke/carbon monoxide/heat and wireless IoT communication and to confirm the detect performance by smoke generator fire test and cotton wicks fire test. Method: The IoT multi-fire detector combined smoke and CO and combined smoke and heat were experimented the detect performance by smoke generator test and fire test of cotton wicks. And the case of fire alarm was checked. Result: The IoT multi-fire detector combined smoke and CO rung the alarm at the fire test of cotton wicks, did not ring the alarm at the smoke generator test. In comparison, the IoT multi-fire detector combined smoke and heat did not ring the alarm both at the smoke generator test and the fire test of cotton wicks. Conclusion: The IoT multi-fire detector combined smoke and CO detected the only smoke including the carbon monoxide and the IoT multi-fire detector combined smoke and heat did not ring the alarm for lack of heat. As a result, when the developed IoT multi-fire detector was detected the signal more than the set point, the fire alarm was sounded through cotton wicks fire test and smoke generator.

원전 제이실 바닥 화재감지기 선정에 관한 연구

  • 구철수;임장현
    • Proceedings of the Korean Nuclear Society Conference
    • /
    • 1996.05d
    • /
    • pp.543-548
    • /
    • 1996
  • 국내 가압 경수형 원자력 발전소 주제이실의 바닥에 가장 적합한 화재 감지기 선정을 위하여 원전 심사, 검사시 적용한 국내·외 화재감지기 설계 및 설치에 관한 법규와 규제요건의 종합적인 검토를 수행하고 원전의 주제이실 바닥 환경을 최대로 모의한 시험장치를 이용하여 선형열감지기와 공기 표본 추출형 연기감지기의 동작 성능을 비교 시험하였다. 시험 결과 케이블 화재시 공기 표본 추출형 연기감지기가 감도 및 응답특성이 정온식 선형 감지기 보다 우수한 것으로 확인되었다.

  • PDF

A Study on the adaptability of Carbon monoxide Detector (일산화탄소감지기의 적응성에 관한 연구)

  • Seo, Byung-Keun;Yoon, Myong-O
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2010.10a
    • /
    • pp.190-194
    • /
    • 2010
  • 화재감지기는 화재시 발생되는 열, 연기, 불꽃, 독성가스등의 다양한 연소생성물을 감시한다. 기술의 발전으로 화재 감지방식과 기능이 다양해지고 있으며, 이에 따라 다양한 방식의 감지기들이 개발되고 있다. 최근 진보된 감지기들은 화재로 발생 이전에서 부터 감지, 비화재보에 대한 방지는 물론 감지기의 상태 오염 감도 등의 다양 정보를 제공함으로써 유사시 신속하고 정확한 대응이 가능하도록 발전되고 있다. 이러한 진보된 감지기는 막대한 피해가 예상되는 장소, 대피하는데 많은 시간이 소요되는 장소에 적용되어 인명 및 재산피해를 절감 시키고 있다. 일산화탄소감지기 또한 진보된 감지기로 화재 초기 가연물이 연소할 때 발생하는 일산화탄소를 감시한다. 일반화재의 경우 화재 초기에 가연물이 서서히 연소시 불완전 연소로 인한 다량의 일산화탄소가 발생되기 때문에 기존 열, 연기, 불꽃감지기에 비해 빠른 반응을 보여 화재를 조기에 감지함으로써 조기 대응으로 인한 피해를 줄일 수 있을 것이다. 본 연구에서는 실물화재시험 자료를 바탕으로 CO감지기의 조기 감시능력을 확인하였다. CO감지기는 화재초기 발생되는 일산화탄소를 감지하므로 대피시간이 많이 필요한 장소(병원 노인요양시설 학교 백화점 등), 침대 폼메트리스 훈소화재 발생장소(호텔침실 기숙사 숙박업소, 병실 등)등에 적응성이 우수할 것으로 분석된다. 최근 설계되는 초고층 건축물 및 주요 시설물 등에서 화재 시뮬레이션과 가상시나리오 유형 분석을 통해 성능위주의 설계가 적용되고 있다. 그만큼 정확하고 신속한 감지가 중요하다 할 수 있다. CO감지기야 말로 그 기대에 가장 부합될 것으로 분석된다.

  • PDF

P형 화재감지시스템과 퍼지논리를 적용한 화재감지시스템의 동작특성 비교분석

  • 홍성호;심두현;김상철
    • Proceedings of the Korean Institute of Industrial Safety Conference
    • /
    • 2003.05a
    • /
    • pp.173-178
    • /
    • 2003
  • 화재감지시스템은 화재로부터 발생하는 열과 연기 등을 감지하여 화재발생을 조기에 관계자에게 경보하여 주는 시스템이다. 현재 이러한 화재감지시스템은 일정 규모 이상의 건축물에 필수적으로 설치되어 있으며 이 시스템으로 많은 인명과 재산이 보호되고 있다. 그러나 현재 설비되고 있는 화재감지시스템은 화재 시에 발생되는 열, 연기 등에 대하여 감지기회로에서의 미리 지정한 고정값과의 비교를 통하여 정해진 기준을 넘을 경우 화재로 판정한다. 그러나 고정값을 기준으로 신호를 발신하게 되어있는 화재감지기의 동작은 상황에 따라 불확실한 경우가 발생한다.(중략)

  • PDF

Basic Study for performance Improvement of Fire Detectors System at Domestic Apartment Buildings (국내 공동주택 화재감지시스템의 성능개선을 위한 기초연구)

  • Son, Bong-Sae
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.15 no.1
    • /
    • pp.533-538
    • /
    • 2014
  • This study examines the performance of and searches for improvements to the existing automatic fire detection systems installed at domestic apartment buildings as a basic study for development of intelligent fire detection systems specifically for apartments. Thus, this study aims to find out the problems in performance and maintenance of the existing fire detectors installed at apartment buildings which is the prerequisite process for development of intelligent fire detection system for that specific application. It is also found impossible to check whether or not the detectors installed at each apartment are in an operational state at normal times. This study finds that it is desirable to replace the slow-sensing heat detectors by a smoke and single smoke detectors which can detect a fire at its early stage in an effort to improve the problems of fire detectors installed at apartment buildings presently. Because we need to the independence fire detection system of apartment building.

재해 예방용 이상열 감지시스템(CAN 열향)

  • Park, Yun-Seok
    • 방재와보험
    • /
    • s.115
    • /
    • pp.28-33
    • /
    • 2006
  • 공장이나 일반 건물에서 과전류 및 기열에 의해 절연물이 응용되고 유독 가스를 배출하여 화재의 초기 단계로 발전하는 경우가 많다. 이같은 사고를 예방하기 위한 향 검지기와 향 캡슐을 조합한 이상열 감지 시스템 'CAN 열향'의 원리 및 현장 적용 예를 알아본다.

  • PDF

A Experimental Study on the Response Characteristics for Fire Detector by Combustibles (가연물에 따른 화재감지기 응답특성에 관한 실험연구)

  • Choi, Moon-Soo;Hong, Sung-Ho;Lee, Sang-Ho;Park, Sang-Tae;Yoo, Song-Hyun
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2011.11a
    • /
    • pp.514-517
    • /
    • 2011
  • 화재감지 및 경보시스템의 설계 목표는 화재발생 초기 단계에서 화재징후를 발견, 피난의 개시를 신속하게 통수하는 것이다. 화재감지기는 다양한 건물 및 환경에 설치되기 때문에 주위 온도 및 가연물의 종류 등 환경적 측면을 심층적으로 고려하지 않으면 적절하게 감지하지 못하는 경우가 발생할 수 있다. 즉, 가연물 종류 등을 고려한 설계에 따라 설치된 화재감지기는 화재시 설계치 대로 조기에 화재를 감지하여 화재 예방 및 화재로 인한 피해를 최소화할 수 있는 것이다. 본 논문은 화재시 조기에 화재를 감지기하여 건축물내 인명피난을 목적으로 설치되는 화재감지기의 응답특성을 분석한 연구이다. 화재감지기의 응답특성을 분석하기 위하여 다양한 가연물을 발생시키고 화재감지기 종류별로 설치한 다음 각 화재감지기의 응답특성을 분석하였다. 그 결과 정온식 열감지기는 열방출률이 적은 화재를 조기에 감지하는 것에 적합하지 않은 것으로 나타났다. 광전식 연기감지기는 회색 계통의 목재류 화재성상에서 응답특성이 떨어졌고, 동일한 공간에서 화원의 수평거리와 동작시간이 비례한다고 볼 수 없었다.

  • PDF

Febrication of Cu-Mn-Co-Ni-$O_4$ Thin Film Type Infrared Detector of Membrane Structure (메브레인 구조를 갖는 Cu-Mn-Co-Ni 산화물계 박막형 적외선 감지기 제조)

  • 박정희;신종배;전민석;한경섭;최덕균
    • Proceedings of the Materials Research Society of Korea Conference
    • /
    • 2003.11a
    • /
    • pp.74-74
    • /
    • 2003
  • 적외선 감지기는 냉장고, 에어컨, 자동차용 전자부품 등의 온도측정 및 제어, 과잉 전류의 억제를 위한 소자로 널리 사용되며, 또한 최근에는 온도보상형 수정발진기(TCXO) 또는 RF모듈, 액정 판넬의 온도보상회로 등 정보통신기기의 신뢰성 향상을 위해 그 수요가 날로 증가하고 있다. 현재 상용되는 적외선 감지기의 대부분은 벌크형 또는 후막형으로 제조되고 있으나, 최근 반도체공정 기술의 발달로 인하여 보다 향상된 특성이 요구됨에 따라 박막형 등 새로운 형태의 적외선 감지기 대해 활발한 연구가 이루어지고 있다. 본 연구에서는 열 질량과 전도에 의한 열손실을 최소화하여 소자의 감도 및 응답 특성을 향상시키기 위하여 SiO$_2$Si$_3$N$_4$/SiO$_2$ (ONO)다중층 위에 소자 감지부를 형성하고 bulk-micromachining기술을 이용하여 멤브레인 구조를 갖는 박막형 적외선 감지기를 제작하였다.

  • PDF

공동주택용 원격점검형 화재감지기에 관한 연구

  • Gang, Won-Seon;Jeong, Jong-Jin;Son, Bong-Se
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2013.04a
    • /
    • pp.154-155
    • /
    • 2013
  • 2007년 1월 1일부터 2012년 5월 31일까지의 주택화재에 대한 소방방재청의 통계자료를 보면 공동주택에서 발생하는 화재는 매년 약 10,000여건 이상이 발생하는 것으로 나타났다. 이는 전체 화재발생의 약 30%정도를 차지하고 있으므로 조기에 인명을 대피시키기 위한 경보설비의 필요성은 더욱 높아지고 있는 상황이다. 화재감지기는 보통 거실/방 등의 천정에 위치하는데, 해당 화재감지기가 제대로 작동하는지를 점검하기 위해서는 점검기구를 이용하여 열 또는 연기를 각 감지기에 직접 가하는 방법으로 개별적인 점검을 하고 있다. 그러나 공동주택과 같이 사생활침해가 우려되는 건물의 침실 등에 설치된 화재감지기를 점검하는 경우 점검자가 해당 세대에 직접 들어가 점검을 수행해야 하기 때문에 현실적으로 100% 점검이 불가능한 상황이다. 따라서 본 논문은 이와 같은 문제점을 해결하기 위한 방안을 제시한 것으로서, 화재감지기가 정상작동 여부를 수신기에서 원격으로 점검할 수 있도록 하기위한 것이다.