A Study on Fire Alarm Test of IoT Multi-Fire Detector combined Smoke/CO and Smoke/Temperature Sensors  

Son, Geun­Sik (FILK)
So, Soo­Hyun (Department of fire safety, Kyungil University)
Publication Information
Journal of the Society of Disaster Information / v.17, no.2, 2021 , pp. 236-244 More about this Journal
Abstract
Purpose: The purpose of this study is to develop IoT multi-fire detectors combined smoke/carbon monoxide/heat and wireless IoT communication and to confirm the detect performance by smoke generator fire test and cotton wicks fire test. Method: The IoT multi-fire detector combined smoke and CO and combined smoke and heat were experimented the detect performance by smoke generator test and fire test of cotton wicks. And the case of fire alarm was checked. Result: The IoT multi-fire detector combined smoke and CO rung the alarm at the fire test of cotton wicks, did not ring the alarm at the smoke generator test. In comparison, the IoT multi-fire detector combined smoke and heat did not ring the alarm both at the smoke generator test and the fire test of cotton wicks. Conclusion: The IoT multi-fire detector combined smoke and CO detected the only smoke including the carbon monoxide and the IoT multi-fire detector combined smoke and heat did not ring the alarm for lack of heat. As a result, when the developed IoT multi-fire detector was detected the signal more than the set point, the fire alarm was sounded through cotton wicks fire test and smoke generator.
Keywords
IoT Multi-fire Detector; Smoke Generator Test; Cotton Wicks Fire Test; Unwanted Alarm Discrimination;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Choi, K.C. (2015). Technical recommendation to reduce false fire alarm of automatic fire detection system. Dongwon University, KFI, KR.
2 Park, I.D., Kim, C. (2016). "A study on railway vehicles fire detection using HMI touch screen." Journal of the Korean Institute of IIIuminating and Electrical Installation Engineers, Vol. 30, No. 1, pp. 38-43.   DOI
3 Ryu, H. (2014). "Analysis on activation characteristic of heat detectors in a compartment fire." Journal of The Korean Society of Disaster Information, Vol. 10, No. 4, pp. 599-609.
4 Ryu, H.C. (2014). "Analysis for detector response time by installation location of heat detector." Journal of the Korean Society of Hazard Mitigation, Vol. 14, No. 5, pp. 267-274.   DOI
5 Cha, J.H. (2016). "A study on improving the standard related to fire alarm malfunction in security system." Asia-pacific Journal of Multimedia Services Convergent with Art, Humanities, and Sociology, Vol. 6, No. 12, pp. 675-682.   DOI
6 Kim, S.K., Yuk, H.D., Yang, S.H., Jee, S.W., Lee, C.H. (2009). "A study on the problem of tester for the field inspection of the photoelectric smoke detector." Korean Institute of Fire Science & Engineering, Vol. 23, No. 4, pp. 137-144.
7 Nahid, C., Dewan, R.M., AZM, E.C. (2019). "Computer vision and smoke sensor based fire detection system." 1st International Conference on Advances in Science, Engineering and Robotics Technology 2019, Bangladesh, Dhaka, pp.1-5.
8 Ryu, H., Kim, D. (2015). "Study on the operation characteristics of heat detectors through fire and wind tunnel experiment." Journal of The Korean Society of Disaster Information, Vol. 11, No. 2, pp. 203-209.   DOI
9 Seo, B.K., Nam, S.G. (2016). "Study of the improvement of false fire alarms in analog photoelectric type smoke detectors." Korean Institute of Fire Science & Engineering, Vol. 30, No. 5, pp. 108-115.   DOI