전치 가이드 베인 설치에 따른 열회수 보일러 입구 온도 최적화 (NUMERICAL OPTIMIZATION OF TEMPERATURE DISTRIBUTION IN HRSG SYSTEM USING INLET GUIDE VANE)

  • 이수윤;안준;신승원
    • 한국전산유체공학회지
    • /
    • 제14권3호
    • /
    • pp.1-8
    • /
    • 2009
  • Diverging channel from gas engine exit to the inlet section of Heat Recovery Steam Generator (HRSG) has been re-designed for 1 MW system. To improve the uniformity in velocity and temperature distribution of existing design(Case A and B), two additional test geometries have been chosen for the numerical simulation. At first, gas burner exit section has been centered to the inlet section of the boiler(Case C) and uniformity in velocity and temperature distribution has been improved considerably. Secondly, the diverging channel length can be further reduced to compact geometry with new guide vane design (Case D and E). Proposed design shows overall improvement in uniformity in velocity and temperature distribution compared to existing one.

소각로 및 폐열회수 보일러 플랜트의 열설계 (Thermal Design of Incinerator and Waste Heat Recovery Boiler)

  • 김숭기;김성중;최상민
    • 기계저널
    • /
    • 제34권12호
    • /
    • pp.940-960
    • /
    • 1994
  • 열설계과정을 요약 정리하면서 미국, 독일, 일본 등의 기계학회(또는 기술자협회)에서 보일러 및 소각로 등의 설계과정을 표준화하기 위하여 많은 노력을 기울여 왔음을 볼 수 있었다. 설계에 적용되는 주요 공식, 물성, 열전달 계수 등과 같은 자료를 공업표준이나 학회 또는 기술자협회의 지침서 형태로 공유하는 것이 공학발전에 유익하다는 사례를 확인할 수 있었다. 이를 종합하면 우리의 나아갈 바를 생각하는 좋은 지표가 될 수 있을 것으로 보인다.

  • PDF

폐수열 히트펌프 재생에너지 시스템 설계 (Design of Heat Pump Renewable Energy System Using Wastewater with a Heat Source)

  • 추연규;김봉기;김성두
    • 한국정보통신학회:학술대회논문집
    • /
    • 한국해양정보통신학회 2011년도 춘계학술대회
    • /
    • pp.787-790
    • /
    • 2011
  • 본 연구에서는 페수열 회수 보일러에서 버려지는 페수열을 재생하여 에너지를 재활용하기 위하여 퍼지제어 알고리즘을 사용한 지능제어기를 설계하고자 한다. 폐수유입온도의 변화와 폐수유입량의 변화를 파라미터로 하여 컴프레서의 정속운전 대수와 토출온수온도의 특성곡선을 전문가의 지식으로부터 얻을 수 있다. 폐수열 회수 보일러에 유입되는 폐수부하에 따른 컴프레서의 정속운전 대수를 최소화 하기위해 폐수유입온도와 유입량의 변화를 측정하여 최적의 정속운전 대수 및 인버터 운전량을 실시간으로 결정하는 지능제어기를 설계하여 페수열 부하의 변동을 실시간으로 추정하여 최소의 컴프레서 운전대수 및 조작량을 제어함으로써 에너지 효율과 경제성을 극대화할 수 있다.

  • PDF

전치 가이드 베인 설치에 따른 열회수 보일러 입구 온도 최적화 (NUMERICAL OPTIMIZATION OF TEMPERATURE DISTRIBUTION IN HRSG SYSTEM USING INLET GUIDE VANE)

  • 이수윤;안준;신승원
    • 한국전산유체공학회:학술대회논문집
    • /
    • 한국전산유체공학회 2008년도 학술대회
    • /
    • pp.148-154
    • /
    • 2008
  • Diverging channel from gas burner exit to the inlet section of Heat Recovery Steam Generator (HRSG) has been re-designed for 1 MW system. To improve the uniformity in velocity and temperature distribution of existing design(Case A and B) of 300 kW HRSG system, two additional test geometries have been chosen for the numerical simulation. At first, gas burner exit section has been centered to the inlet section of boiler(Case C) and uniformity has been improved considerably. Secondly, the diverging channel length can be further reduced for compact geometry with new guide vane design (Case D and E). Proposed design shows overall improvement in uniformity in velocity and temperature distribution compared to existing one.

  • PDF

순환 유동층 보일러와 초초임계 증기 사이클을 이용한 500 MWe급 순산소 화력발전소의 건식 재순환 흐름의 열 교환 및 경제성 분석 (Heat Integration and Economic Analysis of Dry Flue Gas Recirculation in a 500 MWe Oxy-coal Circulating Fluidized-bed (CFB) Power Plant with Ultra-supercritical Steam Cycle)

  • 김세미;임영일
    • Korean Chemical Engineering Research
    • /
    • 제59권1호
    • /
    • pp.60-67
    • /
    • 2021
  • 본 연구에서는 CO2 포집을 포함하는 500 MWe 급 전기를 생산하는 순산소 석탄화력발전소에 대한 공정흐름도를 제시하였고, 기술경제성 평가를 수행하였다. 이 석탄화력발전소는 순환 유동층 보일러(CFB), 초초 임계 증기 사이클 증기 터빈, 보일러에서 배출되는 배기가스내 수분과 오염물질을 제거하는 배기가스 정제 장치(FGC), 산소 분리 초저온 공정(ASU), 이산화탄소를 분리하는 극저온 공정(CPU)을 포함한다. 건식 배기가스 재순환(FGR)은 CFB연소기내 온도 제어와 고농도 CO2 배출을 위하여 사용되었다. 이 순산소 석탄화력발전소의 열효율을 증가시키기 위하여 FGR 흐름에 대한 열교환, ASU에서 배출되는 질소 흐름에 대한 열교환, 그리고 CPU 내 기체 압축기의 열 회수를 고려하였다. FGR열교환기의 온도차(ΔT)의 감소는 배기가스의 더 많은 폐열 회수를 의미하며, 전기 및 엑서지 효율을 증가시켰다. FGR열교환기의 ΔT가 10 ℃ 에서 FGR과 FGC 주변의 연간 비용이 최소가 되었다. 이때, 전기 효율은 39%, 총투자비는 1371 M$, 총생산비용은 90 M$, 그리고 투자수익률은 7%/y, 그리고 투자회수기간은 12년으로 예측되었다. 본 연구를 통하여 순산소 석탄화력발전소의 열효율 향상을 위한 열교환망이 제시되었고, FGR 열교환기의 최적 운전 조건이 도출되었다.

열병합 복합발전시스템용 폐열회수 보일러 열설계 소프트웨어 개발 연구 (Development of a Thermal Design Software for the Heat Recovery Steam Generator of Combined Cogeneration Systems)

  • 김태국;오시덕;권용호;서석호;김백영
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2001년도 춘계학술대회논문집D
    • /
    • pp.726-731
    • /
    • 2001
  • A thermal design software is developed for the heat recovery steam generator(HRSG) of combined cogeneration systems. The heat transfer is calculated by using the element method to account for the varying thermal properties across the heat transfer elements. The circulation balance is computed for the evaporator to accurately estimate the steam generation rate and to check the proper circulation of the boiler water through the tubes. The software developed can be used to simulate HRSG systems with various combinations of auxiliary burner, wall superheater, superheater, reheater, evaporator, and economizer. Systems with several different combinations of the system components are successfully tested. And it is concluded that the developed software can be used for the design of heat recovery steam generators with various combinations of heat transfer components.

  • PDF

패러럴 슬라이드 게이트밸브의 열구조해석 및 ASME B&PVC 기반 피로수명 평가 (Thermal-structural Analysis and Fatigue Life Evaluation of a Parallel Slide Gate Valve in Accordance with ASME B&PVC)

  • 김태호;최재승;한정삼
    • 대한기계학회논문집A
    • /
    • 제41권2호
    • /
    • pp.157-164
    • /
    • 2017
  • 패러럴 슬라이드 게이트밸브는 복합발전플랜트 배열회수보일러와 증기터빈 사이에 위치하여 증기유동의 흐름을 제어하는 밸브로서 운전기간 동안 기동, 부하변동 및 정지 등의 운전이 반복적으로 이루어진다. 따라서, 각 기동운전 중에 밸브 두께 방향의 온도 차이로 인하여 발생하는 큰 압축 열응력으로 인한 피로손상 및 구조건전성에 대한 평가가 필요하다. 본 논문에서는 배열회수보일러의 주중기 밸브로 설치되는 16인치 패러럴 슬라이드 게이트밸브의 피로수명 평가를 위한 열구조해석 및 ASME B&PVC VIII-2에서 제시된 탄성응력해석 및 등가응력에 기반한 피로수명 평가를 수행하였다.

"ESCO 전문 시공사 (주)동서기연이 건축의 패러다임을 바꾸겠습니다"

  • 에너지절약전문기업협회
    • ESCO지
    • /
    • 통권58호
    • /
    • pp.34-37
    • /
    • 2009
  • '안전시공, 완벽시공, 고객만족'의 슬로건으로 ESCO를 말하는 기업이 있다. 대구에 위치한 (주)동서 기연은 소형열병합발전시스템, 바이오매스(우드칩, 바이오탄)보일러, 열회수환기장치, 태양열, 지열, 시스템냉난방기, 통합자동제어시스템, 진공청소시스템 등 기술력을 보유하고 전문 시공 업체로 전문성을 인정받았다. '더 싼 가격으로 더 큰 효율'을 위한 에너지 신기술로 에너지 분야에서 지속적으로 성정하고 있는 동서기연을 소개한다.

  • PDF

ATES 열펌프 시스템의 경제성 평가 (Economic Evaluation of ATES Heat Pump System)

  • 김남태;최종민
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2011년도 춘계학술대회 초록집
    • /
    • pp.199-199
    • /
    • 2011
  • ATES(Aquifer Thermal Energy Storage) 열펌프 시스템은 기존의 다양한 열원 적용 시스템 대비 효율이 우수한 것으로 알려져 유럽과 미국에서 건물 냉난방 시스템으로 적용되고 있다. 특히, ATES 시스템은 기존의 냉난방 시스템 대비 경제성이 우수한 것으로 알려져 있으나 국내에서는 이에 대한 연구 결과는 전무한 실정이다. 본 연구에서는 ATES 열펌프 시스템의 실증 성능 결과를 분석하였으며, LNG 보일러와 에어컨을 사용하는 기존의 냉난방 시스템을 비교시스템으로 ATES 열펌프 시스템의 경제성 평가를 수행하였다. ATES 시스템의 연간 실증 성능 실험결과 ATES 시스템은 외기온도와 무관하게 연중 안정적인 성능을 나타내었다. 경제성 평가시에 생애주기법(Life Cycle Cost)을 적용하여 ATES 열펌프 시스템의 설치 및 운전에 필요한 총 소요비용을 산정하고, 이 결과를 바탕으로 투자회수기간법을 통해 ATES 시스템의 투자회수 기간을 산정하였다. 생애주기법 적용 시에 현재가치법을 사용하였으며, 현재가치법은 수명주기에 발생하는 모든 투자비용과 절감액을 일정한 시점을 기준으로 등가환산하는 방법을 의미한다. 현재가치법에 사용되는 현재가치는 초기비용과 현재가치계수의 곱으로 나타나는데, 여기에서 현재가치계수는 임의의 이자율로 일정기간 동안 정기적인 할부금액이 적립될 때의 현재금액을 구하기 위해 사용하는 계수를 의미한다. 전기와 LNG는 각각 2009년 7월의 (주)한국전력공사와 (주)한국가스공사의 고시요금을 적용하였다. 본 시스템은 실증 설비용량인 20RT를 대상 건물로 가정하였고, 초기투자비는 크게 공사비와 냉난방 설비 구입비로 구성되어 있으며, 기본적인 물가지표는 (사)한국물가정보(KPI)의 고시 데이터를 참조하였다. 각 시스템의 초기투자비는 ATES 시스템이 비교대상 기존 냉난방 시스템 대비 5.7배 높게 나타났다. 일일 8시간 사용기준으로 계절별 전력요금을 고려한 연간운전 비용은 ATES 시스템이 기존 시스템 대비 냉난방 시에 각각 77%와 16%를 나타내어 운전비용이 연간 절감되었고, 난방 운전 시 절감 비율이 냉방시보다 크게 나타났다. 두 시스템에 대한 생애주기비용을 산정하기 위하여 에어컨과 보일러의 기존시스템과 ATES 시스템의 가용연수를 모두 20년으로 설정하였고, 유지보수 비용은 초기투자비용의 2%로 설정하고, 할인율은 은행 예금이자를 기준으로 5%로 설정하였다. 전기와 LNG의 요금 상승률은 (사)한국물가정보를 바탕으로 각각 2%와 8%로 가정하였다. 이러한 조건에서 생애주기법을 이용한 경제성평가는 ATES 시스템의 경우 생애운전비용이 초기투자비용보다 작게 나타났으며, 기존 냉난방 시스템은 생애운전비용이 초기투자비용에 비하여 높게 나타났다. 본 연구 대상 ATES 열펌프 시스템의 실증 성능 데이터와 기존 문헌으로부터 얻은 냉난방 시스템의 성능 결과를 이용하여 생애주기 비용을 적용한 결과 ATES 시스템의 기존 시스템 대비 투자회수 기간은 6.62년으로 나타났다. 특히, 본 연구에서는 ATES 시스템이 국내 최초로 적용됨에 따라 스크린 등의 부품을 다소 고가의 제품으로 시스템에 적용하였으므로 ATES 시스템의 신뢰성과 안정성이 확보되면 초기 투자비 감소가 가능할 것으로 예상되며, 기존 시스템 대비 투자회수 기간은 더욱 감소될 수 있을 것으로 예상된다.

  • PDF

복합발전플랜트 배열회수보일러 분배기의 응력 및 피로 평가 (Stress and Fatigue Evaluation of Distributor for Heat Recovery Steam Generator in Combined Cycle Power Plant)

  • 이부윤
    • 한국산학기술학회논문지
    • /
    • 제19권8호
    • /
    • pp.44-54
    • /
    • 2018
  • 복합발전플랜트 배열회수보일러 고압증발기의 기기인 분배기에 대하여 설계조건과 과도운전조건을 고려하여 응력 및 피로에 관한 안전성을 평가하였다. 먼저, 배열회수보일러 튜브군 모델의 해석결과로부터 분배기의 상부에 연결되는 수직 강수관, 하부에 연결되는 수직 급수배관, 열교환기의 입구헤더로 향하는 수평방향의 방사형 배관들에 대하여 노즐하중을 도출하였다. 이와 같이 구한 노즐하중은 분배기의 상세모델에 대한 설계조건과 과도운전조건의 해석 시에 노즐 단면에 가해지는 하중으로 사용하였다. 분배기의 상세한 해석모델을 만들고 설계조건의 내압과 노즐하중에 대한 정적구조해석을 수행하였다. 설계조건에서 최대응력은 수평방향 배관의 노즐 보어에서 발생하였다. 최대응력 위치의 국부 1차 막응력이 쉘과 노즐에서 허용기준보다 작으므로 ASME Code의 허용기준을 만족하는 것으로 나타났다. 배열회수보일러에 주어진 8가지 과도운전조건을 고려하여, 분배기의 상세모델에 대하여 열해석을 수행하고, 과도운전 시의 내압, 노즐하중, 열하중에 대한 과도구조해석을 수행하였다. 과도운전조건에서 최대응력은 분배기 상부의 수직 강수관 노즐 부위에서 발생하였다. ASME Code에 의거하여 수직 강수관 노즐 부위의 피로수명을 평가하였다. 결과적으로 계산된 누적피로사용계수가 허용기준보다 작으므로 기대수명 동안에 피로파손에 관하여 안전한 것으로 나타났다.