• Title/Summary/Keyword: 열원시스템

Search Result 341, Processing Time 0.026 seconds

A Study on the Characteristics of Heat Source Temperature for Two-Well Geothermal System Using Numerical Simulation (수치 시뮬레이션을 이용한 복수정(Two-Well) 개방형 지열 시스템의 열원수 온도 변화 검토)

  • Cho, JeongHeum;Nam, YuJin
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.27 no.4
    • /
    • pp.207-212
    • /
    • 2015
  • The use of groundwater and ground_heat is one of the ways to use natural and renewable energy, and it has been considered as a technology to reduce greenhouse gas emissions and increase energy-saving. There are a few researches on the optimum design for the open-loop geothermal system. In this study, to develop the optimal design method numerical simulation of the open-loop geothermal system with two-wells was performed by a groundwater and heat transfer model. In this paper, a study was performed to analyze the system performance according to well distance and pumping flow rate. In the result, average heat exchange rate and heat source temperature were calculated and it was found that they were dependent on the pumping rate.

A Study on the Application of the Optimal Control System for Heat Source and HVAC System (열원 및 공조설비의 최적제어시스템 현장 적용성에 관한 연구)

  • Baek, Seung-Jae;Kim, Jin;Ahn, Byung-Cheon;Song, Jae-Yeob
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1014-1019
    • /
    • 2009
  • The optimal control system for heat source and HVAC system has been developed for minimizing energy consumption while maintaining the comfort of indoor thermal environment in terms of the environmental variables such as time varying indoor load and outdoor temperatures. The optimal set-points of control parameters are supply air temperature and chilled or hot water temperatures. The optimal control study has been implemented for biosafety laboratory by using TRNSYS simulation program in order to investigate energy performance for heat source and HVAC system.

  • PDF

A Study on the Operating Performance of Solar Assisted Hot Water System for Apartment Houses (공동주택용 태양열원 급탕시스템의 운전성능 연구)

  • 이윤규;황인주
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.11
    • /
    • pp.928-936
    • /
    • 2003
  • In the present study, feasibility investigation on the solar assisted hot water supply system for apartment houses was carried out by the review of service facility and heat load pattern. Also analysis and experiment of the small sized system model were performed. This hybrid system are consists of solar collector, heat storage tank, controller, and gas boiler using LPG as a secondary heat source. The analytical results showed a good agreement with experimental data. We found that this hybrid system could reduce the energy cost by 30% for hot water compared to typical boiler system in the apartment houses. Also we showed that this model could be used for the energy and economic analysis of the hybrid system.

Feasibility Study on Leveling Method of Electric Power Load by Applying Thermal Storage Air Conditioning System (축열식 열원시스템 적용에 의한 전력부하 평준화의 경제성 검토)

  • Lee, Chulgoo
    • Journal of the Korean Society for Geothermal and Hydrothermal Energy
    • /
    • v.15 no.1
    • /
    • pp.9-17
    • /
    • 2019
  • Reducing global warming potential has become important, and as one of those methods for reducing it, economic evaluation by applying ice thermal storage air conditioning system was performed. The floor area and height of the subject building was assumed $5,000m^2$ and 20 m. Absorption chillerheater system and air source heat pump system was used for comparing to the subject system, and payback period method was used to perform economic evaluation. Although the running cost of ice thermal storage system is reduced compared to two systems, the ratio is not significant compared to the increase of initial construction expenses, and payback period was calculated to be about 7.7 and 79.3 years. However, the heat storage system should be approached from the viewpoint of long term rather than the economic standard in the present standard.

A Study of Determining Initial Ignoring Time of Line Source Model used in Estimating the Effective Soil Formation Thermal Conductivities (지중유효열전도율 해석에 사용되는 선형열원 모델의 초기제외시간 결정에 관한 연구)

  • Lee, Se-Kyoun;Woo, Joung-Son;Kim, Dae-Ki
    • Journal of Energy Engineering
    • /
    • v.17 no.3
    • /
    • pp.167-174
    • /
    • 2008
  • Line source model is commonly used in analyzing the data obtained from thermal response test to estimate the effective soil formation thermal conductivity. In the application of line source model some part of initial data must be ignored in order to achieve more accurate result. The period of time for this initial data is called initial ignoring time(IIT) in this paper. However there has been no definite rule in determining this initial ignoring time. Therefore line source model requires experienced analyzer to select the useful data, which is somewhat subjective. One method often suggested is the calculation of IIT with non dimensional time $\tau=5$. However, this is a very theoretical result derived from a system of perfect line source model, which is somewhat different from the real system. A new method to determine IIT is presented in this study. This method requires error estimation first and IIT can be decided from the results of error estimation. This method is applied in the analysis of field test data and shows better result than the one obtained from the method using non dimensional time mentioned above as shown in Table 2.

Empirical evaluation of the heating performance by a heat pump system with surplus heat from a greenhouse (온실 태양잉여열을 이용한 히트펌프시스템의 난방 성능평가에 관한 실증 연구)

  • Jeon, Byung-Yong;Park, Youn-Cheol;Ko, Gwang-Soo
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.41 no.1
    • /
    • pp.99-104
    • /
    • 2017
  • This study evaluated the heating performance of a hybrid heat pump system. The system was installed in a $100-m^2$ greenhouse to utilize surplus solar energy. A hybrid heat pump system was installed at Jocheon-ri, Jeju Island, for an empirical evaluation of the performance. The system consists of a heat storage tank and plate heat exchangers for several heat exchanges between the greenhouse and heat pump or storage tank. The system uses R410a as the working fluid and is controlled automatically by a defined set temperature of the greenhouse. This system incorporates two kinds of heat sources: outdoor air and a storage tank that collects heat from the topside of the greenhouse. The results showed that the heating capacity was 19.9 kW in the outdoor air source mode and 21.4 kW with direct heating from hot water in the thermal storage tank. These results are very similar to those of a previous study.