• Title/Summary/Keyword: 열교환기 핀

Search Result 171, Processing Time 0.02 seconds

An Analysis for Predicting the Thermal Performance of Fin-Tube Heat Exchanger under Frosting Condition (착상시 핀-관 열교환기의 열적 성능 예측을 위한 해석)

  • Lee, T.H.;Lee, K.S.;Kim, W.S.
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.8 no.2
    • /
    • pp.299-306
    • /
    • 1996
  • This work presents an analytical model, so called modified LMTD method, to predict the thermal performance of finned-tube heat exchanger under frosting conditions. In this model, the total heat transfer coefficient and effective thermal conductivity of the frost layer were defined as a function of frost surface temperature. The surface temperature of the frost layer formed on the heat exchanger was calculated through the analysis of the heat and mass transfer process in the air and frost layer. To examine the validity of this analytical model, the computed results from the present model, such as heat transfer rate, frost mass and thickness of frost, were compared with the ones of the expermental work and LMED method.

  • PDF

A Study on the Thermal Contact Resistance Evaluation for Fin-Tube Heat Exchangers (핀-관 열교환기에서의 접촉열저항 평가에 관한 연구)

  • Jeong, J.;Kim, C.N.;Youn, B.;Gil, S.H.;Yang, J.S.
    • Proceedings of the KSME Conference
    • /
    • 2000.11b
    • /
    • pp.291-296
    • /
    • 2000
  • Usually the contact between fin collar and tube surface for fin-tube heat exchanger is secured by mechanical expansion of the tubes. The objective of the present study is to develop a method of measuring the thermal contact resistance between fin collar and tube surface for fin-tube heat exchanger. Also an experimental work has been performed to evaluate the thermal contact resistance, and a rigorous numerical analysis has been employed to calculate the contact resistance from the measured data. The experiments have been conducted fur the fin-tube heat exchangers with the tube of outer diameters 7 and 9.52 mm.

  • PDF

Performance Characteristics on Environment Change of A/C applied Fin-tube and PF Heat Exchangers (환경변화에 따른 핀-관, PF 열교환기 적용 공조기 성능 특성 실험 연구)

  • Park, K.M.;Um, U.S.;Kwon, Y.C.;Lee, S.J.
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1267-1271
    • /
    • 2009
  • In the present study, performance characteristics on environment change of A/C applied fin-tube and PF heat exchangers were experimentally investigated. Capacity and COP changing an outlet air velocity, an indoor/outdoor temperature and a relative humidity were obtained. Air-enthalpy calorimeter was used. As the air velocity, indoor temperature and relative humidity increase, capacity and COP increase. PF A/C has smaller refrigerant weight than the fin-tube A/C. The performance of PF-2 A/C with the squarer fin was more excellent than that of PF-1 A/C with the triangler fin.

  • PDF

Flow Analysis of Heat Exchanger with Delta Winglet Vortex Generators on CFD (와류 생성기가 설치된 핀 튜브 열교환기의 열 유동해석)

  • Hwang, Seong-Won;Jeong, Ji-Hwan
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1166-1171
    • /
    • 2009
  • Fin-tube heat exchangers are widely used in refrigeration systems. To improve the performance of fin-tube heat exchangers, the shape of plain fin was developed in slit fin and louver fin. These pins have higher heat transfer performance as well as larger pressure drop. Recent studies of a delta winglet vortex generators(DWVG) show less heat transfer capacity than louver fin. However, the DWVG have very small pressure drop. This paper compares the performance for the plain fin and DWVG fin in terms of flow characteristics and heat transfer based on CFD analyses. The DWVG generate vortex and delayed flow separation and leads to a reduction of a wake region behind a tube. The results show that the DWVG produce improved heat transfer and reduced pressure drop compared to a plain fin. This result is opposite to the Reynolds analogy.

  • PDF

Flow Visualization Study around the Distributor of Plate-fin Heat Exchangers (판형-핀 열교환기 분배면의 유동 가시화 연구)

  • Jeong, Tae-Sik;Park, Seung-Ha;Kim, Chang-Su;Kim, Hyoung-Bum
    • Journal of the Korean Society of Visualization
    • /
    • v.10 no.3
    • /
    • pp.37-41
    • /
    • 2012
  • Plate-fin heat exchanger is a kind of compact heat exchangers with a good performance in heat transfer. It is widely used in various engineering fields such as aerospace, chemical and biomedical industries. Quantitative and qualitative flow visualization study were performed using the water model of commercial plate-fin heat exchanger with header angles of $30^{\circ}$. The Reynolds number was 100. Conventional digital particle image velocimetry was used to measure the instantaneous velocity fields of the header region and the flow visualization using dye injection and hydrogen bubble method were applied to capture the qualitative flow characteristics. The results showed the existence of separation flow region at the junction area and the bottom wall of the exit region.

The Frost and Defrost Performances of Fin-and-Tube Exchangers with Different Surface Characteristics (표면특성이 다른 두 핀-관 열교환기의 착상 및 제상 성능)

  • 신종민;최봉준
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.6
    • /
    • pp.525-531
    • /
    • 2002
  • The effects of different surface hydrophilicity on frosting and defrosting characteristic were experimentally investigated. Mass of frost and water hold-up was measured. Results showed that no significant difference in the frost mass was found between the two different surfaces while the water hold-up of heat exchanger court be reduced by the enhancement of surface hydrophilicity. Also, the defrosting efficiency m hydrophilic surface was improved by 76%. It was expected that hydrophilic heat exchanger could provide the improvements in both thermal-hydraulic performances and system reliability during frost/defrost operating in refrigeration systems.

The Frost and Defrost Performances of Fin-and-Tube Heat Exchangers with Different Surface Treatment Characteristics (서로 다른 표면특성을 갖는 핀-관 열교환기의 착상과 제상 성능평가)

  • 최봉준;황준현;신종민
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.10
    • /
    • pp.781-785
    • /
    • 2002
  • The effects of different surfaces on dry and wet frosting test were experimentally investigated. The results of experiment were compared by the performance evaluation coefficient (PEC). Results showed that the air-side pressure drop of lacquer coated evaporator increased by 5% as compared to the plasma treated one. It was also found that the Plasma coated evaporator is lower than lacquer coated one in the PEC ratio.

A study on the behavior of frost formation according to surface characteristics in the fin-tube heat exchanger (핀-관 열교환기의 표면특성에 따른 착상 거동에 관한 연구)

  • 류수길;이관수
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.3
    • /
    • pp.377-383
    • /
    • 1999
  • In this study, the behavior of frost formation according to surface characteristics in the fin-tube heat exchanger has been examined experimentally. The results show that the thickness of the frost which is attached to the hydrophilic heat exchanger becomes thin and the air pressure drop is smaller than that of bare aluminium heat exchanger However, the frost mass of hydrophilic heat exchanger is more than the bare one. Hence, high density frost is attached to hydrophilic heat exchanger. The sensible and latent heat flux of hydrophilic heat exchanger is bigger than that of bare one, but the increasing amount is very small and the improvement of thermal performance is also very small. The variation of fin-pitch of heat exchanger shows little influence on frost formation and hydrophilic heat exchanger loses its surface characteristics rapidly with increasing relative humidity.

  • PDF

Empirical Correlations of Frost Properties on the Fin of a Heat Exchanger (열교환기 핀에서의 서리층 물성치에 대한 실험 상관식)

  • Kim, Kyoung-Min;Lee, Kwan-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.11
    • /
    • pp.629-635
    • /
    • 2009
  • In this study, fin surface temperature and frost properties, i.e., frost thickness and frost surface temperature on a heat exchanger, were experimentally analyzed with different fin thicknesses, fin sizes and thermal conductivities of fin. As a result, it is found that fin thickness and thermal conductivity of fin should be considered in order to design an efficient heat exchanger fin. Correlations of dimensionless average frost properties were proposed as functions of dimensionless air temperature, dimensionless fin base temperature, dimensionless fin thickness, absolute air humidity, Reynolds number and Fourier number. The correlations predicted well the average frost thickness with a maximum error of 10.5% and frost surface temperature with a maximum difference of $0.89^{\circ}C$, respectively.

Performance Comparison of 7mm Fin-Tube Heat Exchangers for Various Design Conditions (설계 조건에 따른 7mm 직경 핀-관 열교환기의 성능비교)

  • Chang, Keun-Sun;Kim, Hyuk;Hong, Seok-Ryul;Kim, Young-Jae
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.633-638
    • /
    • 2006
  • This study presents the air side heat transfer and friction characteristics of fin-tube heat exchangers with various fin types. A total of 8 samples of heat exchangers are tested. Fin patterns tested are slit, louver and plate fins. Each fin type has three cases of number of tube rows(N=1, 2, 3) and two different fin pitches. The results are plotted in terms of Colburn j-factor and friction factor f with respect to Reynolds number in the range of 200 to 510.

  • PDF