Experimental study on applicability of Air-Curtain system in train fire at subsea tunnel rescue station (해저터널 열차 화재 시 구난역 에어커튼 시스템의 성능에 관한 실험 연구)

  • Park, Byoung-Jik;Shin, Hyun-Jun;Yoo, Yong-Ho;Park, Jin-Ouk;Kim, Hwi-Seong;Kim, Yang-Kyun
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.20 no.1
    • /
    • pp.1-9
    • /
    • 2018
  • Visibility is very poor in tunnel fire because of confined space where the fire may easily lead to the mass casuality incident because of fast smoke spread. In this test, air curtain and the fan were installed at rescue station in a bid to make use of rescue station in safe way during the train fire in undersea tunnel and a full-scale fire test was conducted to identify the applicability of air curtain system. Air curtain system was installed at a real rescue station and the test was continued for 2 minutes till heptane which was used as fire source was completely burned out. When air curtain was working, difference in temperature between inside and outside the platform was $160^{\circ}C$ and carbon monoxide measured inside the platform was less than the case of no air curtain system by 160 ppm. Thus a full-scale fire test demonstrated that the air curtain system installed at rescue station in undersea tunnel was able to effectively block the heat and smoke generated from the fire.

The study on performance evaluation of heat resistance and smoke control system using air-curtain system in tunnel (터널용 에어커튼 시스템의 내열 및 제연 성능 평가 연구)

  • Park, Byoung-Jik;Shin, Hyun-Jun;Yoo, Yong-Ho;Park, Jin-Ouk;Kim, Yang-Kyun;Kim, Hwi-Seong
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.20 no.4
    • /
    • pp.743-755
    • /
    • 2018
  • Tunnel is a semi-closed structure similar to underground space where the smoke generated from fire fills the space fast while escaping from the space slow. Because of such characteristics, when the fire breaks out by traffic accident, the vehicles are jammed making it difficult for the people to evacuate from the scene as well as for the fire engine to gain access to the scene. For such reasons, tunnels are globally categorized into some disaster classes for differentiated facilities and operation approaches. In Korea, less than a 1 km-long tunnel accounts for 80.0% and such a short tunnel which is categorized into Class III is not required to have smoke control system. In this study, a full-scale fire test was conducted in a bid to apply air curtain system using heat-resistant sirocco fan to a less than 1 km-long tunnel. To that end, heat resistance test to verify the normal operation at $250^{\circ}C$ for 60 minutes was conducted. Consequently, despite of rapid rising-temperature and increasing-carbon dioxide inside the air curtain (direction of fire in tunnel), initial condition was found to have been sustained outside the air curtain (opposite direction of fire in tunnel).

Simulation study of smoke spread prevention using air curtain system in rescue station platform of undersea tunnel (해저터널 구난역 플랫폼 화재연기확산 방지를 위한 에어커튼 시스템 차연성능 시뮬레이션 연구)

  • Park, Sang-Heon;An, Jung-Ju;Han, Sang-Ju;Yoo, Yong-Ho
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.17 no.3
    • /
    • pp.257-266
    • /
    • 2015
  • This study introduce that we studied optimization and possibility of smoke spread prevention with air-curtain system in undersea tunnel named from Ho-Nam to Jeju line in domestic if a fire break out in train. To verify performance, air-curtain system is installed between rescue station platform and each door of passenger car to provide safety route to evacuator and we studied simulation model of various cases about 15 MW fire severity considering domestic specifications. As a result we verified the fact that CASE1(air jet with 15degree toward passenger car) and CASE 5 (air jet with 15degree toward passenger car and pressure air blast from cross passage) is best Smoke Spread Prevention and less inflow carbon monoxide. Through above results, we expect that air-curtain system is one of the facilities for fire safety and provide us safety platform route in undersea tunnel.

The Study on the Bi-directional Ejection Air Curtain System for Blocking Smoke Diffusion in case of Tunnel Fire (터널 화재시 연기확산 차단을 위한 양방향 토출 에어커튼 시스템에 대한 연구)

  • Yang, Sang-Ho;Choi, Young-Seok;Kim, Jung-Yup;Kim, Nam-Goo;Kim, Kyung-Yup
    • The KSFM Journal of Fluid Machinery
    • /
    • v.17 no.5
    • /
    • pp.43-53
    • /
    • 2014
  • This paper presents a the study on air curtain system of top and bottom bi-directional jet air discharge for blocking the spread of smoke in case of tunnel fire. The five kinds different air curtains of A, B, C, D, and E of models for various performance tested after manufactured. A results of the various performance test obtained the best efficiency from E model air curtain. And optimize the injection angle of the air curtain nozzle through the three-dimensional computational fluid dynamics (CFD) analysis and analyzed the effects of external pressure of tunnel. and also single factor design have been applied. At present, our attention is focused on the velocity distribution(flow width and flow position) of 1.5m on the ground in tunnel. Also, analyzed the influence of draft in the tunnel. Detailed effects of discharge angle of air curtain and velocity at nozzle exit are discussed.

Scaled model tests for improvement and applicability of the transverse smoke control system on tunnels (횡류식 제·배연 시스템의 개선 및 적용성 분석을 위한 모형실험 연구)

  • Kim, Hyo-Gyu;Baek, Doo-San;Kim, Jae-Hyun;Lee, Seong-Won;Yoo, Ji-Oh
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.22 no.5
    • /
    • pp.563-574
    • /
    • 2020
  • Currently, road tunnels and railroad tunnels are building smoke control systems to emit toxic gases and smoke from fires. Among the various smoke control systems, the transverse smoke control system has the disadvantage that air supply or exhaust is performed on only half of the cross-section, rather than air supply or exhaust on the entire cross-section of the tunnel as air is supplied or exhausted by partitioning the wind path. Therefore, this study analyzed the effect of exhaustion through numerical analysis and scaled model tests on the zoning smoke control system, which improved the limitations of the transverse smoke control system. As a result of the scaled model test, the transverse ventilation system exhibited a 25.6% smoke control rate based on the state where no smoke was controled, and zoning smoke control system showed a smoke control rate of 40.8%. In addition, as a result of numerical analysis, it was found that transverse ventilation system did not control fire smoke spreading from the tunnel and continued to spread. On the other hand, zoning smoke control system was found to be smoke controled within a certain section due to the air curtain effect and the flue gas effect.

An Automatic Operating System for Manless Multipurpose in Greenhouse (시설원예의 생력화를 위한 다목적 자동작업장치 개발)

  • 민병로;김웅;이범선;이대원
    • Journal of Bio-Environment Control
    • /
    • v.13 no.3
    • /
    • pp.143-148
    • /
    • 2004
  • The automatic operating system was designed and built to work manless multipurpose in greenhouse. The system proved to be a reliable system for performing multipurpose functions. Its development involved the integration of moving part, height control part, watering part, ventilation part and inhalation part. The moving part was able to be moved it on the rail installed in greenhouse, the height control part controled it up and down by height of the crops, the watering part sprinkled a agricultural medicines on the crops and the ventilation and the inhalation part ventilated and inhaled different thing and vermin which were attached on crops. Based on the results of this study the following conclusions were made: The moving velocity was changed 0.047 - 0.027 m/s by the dial transfer. The velocity within 50 cm from center of the entrance was 0.2 m/s. The watering volume of spray increased as the pressure of spray was high. The difference of spray pressure between 10 kg/$\textrm{cm}^2$ and 15 kg/$\textrm{cm}^2$ was 60 ml, but that of spray pressure between 15 kg/$\textrm{cm}^2$ and 20 kg/$\textrm{cm}^2$ was 20 ml. The average speed of a current of inhalation was 3.64 m/s and the inhalation flux of inhalation was measured 0.044 ㎥/s by using glues seed and styrofoam.