• 제목/요약/키워드: 슬릿휜

검색결과 9건 처리시간 0.012초

휜-관 열교환기에 있어서 각종 휜 형상의 성능 특성에 관한 실험적 연구 (Experimental study of performance characteristics of various fin types for fin-tube heat exchanger)

  • 윤백;김영생;박환영;박현연
    • 설비공학논문집
    • /
    • 제11권4호
    • /
    • pp.484-491
    • /
    • 1999
  • Air side heat transfer and pressure drop for ø9.52 fin-tube heat exchanger with various types of slit and louver fins were measured, and compared with wave-slit fin. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively. Actual heat exchanger was tested using water, and the tests were performed for 2 row heat exchangers with 3 different fin spacings, 1.3, 1.5 and 1.7mm. The overall performance of the enhanced fins was evaluated by comparing heat transfer coefficient with respect to fan power.

  • PDF

웨이브 및 웨이브-슬릿 열전달촉진 휜-관 열교환기의 공기측 압력강하 및 열전달 특성에 관한 실험 (Experimental study of air side pressure drop and heat transfer characteristics of wave and wave-slit fin-tube heat exchangers)

  • 윤백;길용현;박현연;유국철;김영생
    • 설비공학논문집
    • /
    • 제10권5호
    • /
    • pp.589-599
    • /
    • 1998
  • Air side heat transfer and pressure drop for fin-tube heat exchanger with wave and wave-slit fins were measured for various fin spacings and number of tube rows. Outer diameter of the tube including fin collar is 10.07mm, and experiments were done with dry surface condition. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively, and wave depth of the wave fin is 2mm. Experiments were conducted for 1, 2 and 3 rows and 3 different fin spacings, 1.3, 1.5 and 1.7mm. An attempt was made to demonstrate advantage of the enhanced fins over the plane fin by introducing the concept of fan power, Effect of the number of tube rows on heat transfer was discussed in connection with general mechanisms of heat transfer enhancement for fin-tube heat exchanger. Also the effect of hydrophilic coating was investigated. Lastly, correlations for Colburn j-factor and friction factor were developed.

  • PDF

슬릿휜-관 열교환기의 설계조건에서 공기측 압력강하 산출 (Evaluation of Air-side Friction Characteristics on Design Conditions of Slit Fin and Tube Heat Exchanger)

  • 조성철;김창덕;김창업;권정태;임효재
    • 에너지공학
    • /
    • 제16권3호
    • /
    • pp.149-154
    • /
    • 2007
  • 본 연구에서는 슬릿 휜-관 열교환기의 공기측 압력강하 특성을 실험적으로 고찰하였다. 물을 작동유체로 사용한 기존의 실험은 공기측 압력강하에 대해 일관된 방법을 제시하지 못하고 있다. 따라서 본 연구에서는 R22를 적용하여 휜-관 열교환기의 전표면과 습표면에 공기측의 압력강하 특성을 나타내는 표준 방법을 제시하고자 하였다. 기존의 실험 상관식과 본 연구에서 제시한 실험 데이터를 증발기와 응축기의 설계조건에서 레이놀즈수와 f-factor의 관계식으로 나타내었다. 본 실험은 공기의 속도가 $0.38{\sim}1.6\;m/s$ 일 때 냉매의 질량 유속 범위를 $150{\sim}250\;kg/m^2s$하여 수행하였다.

R410A 냉매를 사용한 열펌프용 열교환기의 형상에 따른 성능특성 연구 (A Study on Performance Characteristics of Heat Exchanger for Heat Pump with R410A Refrigerant)

  • 정규하;박윤철;오상경
    • 설비공학논문집
    • /
    • 제16권4호
    • /
    • pp.340-348
    • /
    • 2004
  • The air and refrigerant side heat transfer performances are key parameters to improve heat transfer efficiency of the heat exchanger including the fan performance. Design of the fins, treatment of the tube inside, tube diameter and tube array effect heat transfer performance of the heat exchanger. The heat exchanger is used as a condenser at cooling mode and used as an evaporator at heating mode in the heat pump system. The heat pump system uses R410A as the refrigerant. The heat exchangers are consisted with 7 mm diameter tubes with slit-type fins. The study was conducted with variation of arrangement of the refrigerant path and air flow rate and refrigerant pressure drop and heat transfer rate were measured with a code tester. The capacity of the 3 path heat exchanger is more efficient than 2 or 4 path heat exchangers in heating or cooling modes.

열전달 촉진 핀-관 열교환기의 공기측 압력강화 및 열전달 특성에 관한 실험 (Experimental Study of Air Side Pressure Drop and Heat Transfer Characteristics of Enhanced Fin-Tube Heat Exchangers)

  • 윤백;길용현;박현연;김영생
    • 대한기계학회논문집B
    • /
    • 제22권11호
    • /
    • pp.1555-1563
    • /
    • 1998
  • Heat transfer and pressure drop for ${\phi}10.07$ dry surface fin-tube heat exchanger with wave and wave-slit fins were measured for different fin spacings and number of tube rows. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively, and wave depth of wave fin is 1.5mm. The experiments were performed for 4 different fin spacings, 1.3, 1.5, 1.7 and 2.0mm, and the number of tube rows were 1,2 and 3 rows. The present results were compared with the previous results for the wave depth of 2mm. Also hydrophilic coated and bare fins were tested. Correlations for Colburn j-factor and friction factor were developed.

증발기의 설계조건에서 공기측 열전달계수 및 압력강하 산출 (Evaluation of Air-side Heat Transfer and Friction Characteristics on Design Conditions of Evaporator)

  • 김창덕;이진호
    • 설비공학논문집
    • /
    • 제15권12호
    • /
    • pp.1007-1017
    • /
    • 2003
  • An experimental study on the air-side pressure drop and heat transfer coefficient of slit fin-tube heat exchanger has been carried out. The data reduction methodology for air-side heat transfer coefficients in the literature is not based on a consistent approach. This paper focuses on new method of data reduction to obtain the air-side performance of fin-tube heat exchanger using R22 and recommends standard procedures for dry and wet surface heat transfer estimation in fin-tube heat exchanger having refrigerant on the tube-side. Results are presented as plots of friction f-factor and Colburn j -factor against Reynolds number based on the fin collar outside diameter and compared with previous studies. The data covers a range of refrigerant mass fluxes of 150∼250 kg/$m^2$s with air flows at velocity ranges from 0.3 m/s to 0.8 m/s.

응축기의 설계조건에서 R22와 R134a의 압력강하 예측 및 실험 (Prediction and Experiment of Pressure Drop of R22 and R134a on Design Conditions of Condenser)

  • 강신형;변주석;김창덕
    • 에너지공학
    • /
    • 제15권4호
    • /
    • pp.243-249
    • /
    • 2006
  • 본 실험적 연구는 슬릿휜-관열교환기의 냉매측 압력강하에 대하여 수행하였다. 응축기의 설계조건에서 미세휜관내 냉매 R22와 R134a의 압력강하에 대한 실험데이터와 앞서 제안한 상관관계식과 상호 비교하였다. 실험은 냉매 R22와 Rl34a의 응축기 입구온도 $60^{\circ}C$, 질량유속 $150{\sim}250\;kg/m^{2}s$ 범위에서 수행하였다. 공기의 유입조건은 건구온도 $35^{\circ}C$, 상대습도 40%이며, 공기유속의 범위는 $0.68{\sim}1.43\;m/s$이다. 실험결과 응축기의 과냉도 $5^{\circ}C$ 조건에서 R134a의 압력강하는 R22보다 $22{\sim}22.6%$ 높게 나타났으며, 냉매의 질량유속 $200{\sim}250\;kg/m^{2}s$의 범위에서 실험으로부터 측정한 R22와 Rl34a의 압력강하는 예측결과와 ${\pm}20%$내에 일치하였다.

대체냉매 R407C 및 R410A를 이용한 슬릿휜-관 열교환기의 응축특성에 관한 연구 (An Experimental Study on Condensation Characteristics of Slit Fin-tube Heat Exchanger Using Alternative Refrigerants, R407C and R410A)

  • 전창덕;장경근;강신형;이진호
    • 설비공학논문집
    • /
    • 제14권9호
    • /
    • pp.706-716
    • /
    • 2002
  • R410A and R407C are considered to be alternative refrigerants to R22 for the air-conditioners. Experimental investigation is made to study the condensation heat transfer characteristics of slit fin-tube heat exchanger using alternative refrigerants R410A and R407C. R407C, a non-azeotropic refrigerant mixture, exhibited a quite different condensation phenomenon from those of R22 and R410A and its condensation heat transfer coefficient was much lower than that of R22 and R410A. Between the R22 and R410A, the condensation heat transfer coefficient of R410A, near-azeotropic refrigerant mixture, was a little higher than that of R22. R410A also showed the lowest condensation pressure drop across the test section. For all refrigerants, the condensation heat transfer coefficient and pressure drop increase as the mass flux increases.

대체냉매를 사용하는 공조기용 열교환기의 특성에 관한 연구 (A Study on the Characteristics of Heat Exchanger in Air-Conditioning System using Alternative Retrigerants)

  • 김남신;이은호;유재석;김기현;최윤호;김권진;김만회;황석렬
    • 에너지공학
    • /
    • 제9권3호
    • /
    • pp.192-201
    • /
    • 2000
  • 증발기와 응축기로 폐회로 냉동 시스템을 구성하여 기존 사용 냉매인 R22와 대체냉매로써 부각되고 있는 R407C, R410A를 사용하여 여러 가지 관 직경과 휜 형상을 가지는 열교환기에 대한 열전달량, 질량유량, 열교환기를 지나가는 냉매의 온도분포 그리고 공기측 압력강하를 측정하였다. 모든 열교환기에서 냉매의 질량유량이 증가함에 따라 열전달량은 증가하였다. R22와 R407C의 경우에 증발기측에서는 거의 같은 열전달량을 나타냈고 응축기측에서는 R407C가 전체적으로 열전달량이 높게 나타났다. 그리고 열교환기의 전달량은 유로의 형상보다는 냉매의 질량유량과 전열면적에 더 많은 영향을 받는다. 공기측 압력 강하는 열수가 많은 열교환기의 경우가 작게 나타났으며 슬릿휜을 가지는 열교환기의 압력강하가 가장 크고 웨이비휜을 가지는 열교환기가 가장 작게 나타났다.

  • PDF