• Title/Summary/Keyword: 석고보드 벽체

Search Result 16, Processing Time 0.029 seconds

A Comparison of Fire Resistance for Wall According to Increase the Thickness of Gypsum Boards (석고보드 두께증가에 따른 벽체 내화성능 비교)

  • Choi, Dong-ho;Chol, Soo-Kyung
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2019.05a
    • /
    • pp.95-96
    • /
    • 2019
  • In this study, fire resistance test according to KS F 2257-8: 2015 was carried out to compare fire resistance for wall consisted of gypsum boards with two types of drywall with gypsum boards which is based to lightweight studs. As a result, it was found that the fire resistance of the wall constructed with 12.5 mm of general gypsum board was 16 minutes higher than that of the wall constructed 9.5 mm in accordance with integrity and was 9 minutes higher than that of the wall(9.5 mm) depending on insulation. If the wall with the gypsum board 12.5 mm is constructed, it can be confirmed that the fire resistance is improved by about 43%.

  • PDF

Study on the Conduction Heat Transfer Characteristics According to the Heating Temperature of Lightweight Panel Wall material (경량칸막이 벽체재료의 수열온도에 따른 전도 열전달 특성 연구)

  • Park, Sang-Min;Lee, Ho-Sung;Choi, Su-Gil;Kim, Si-Kuk
    • Fire Science and Engineering
    • /
    • v.32 no.1
    • /
    • pp.46-56
    • /
    • 2018
  • The paper relates to a study on the conduction heat transfer characteristics according to the heating temperature of lightweight panel wall material. Plywoods, marbles, heat resistant glasses, as well as general gypsum board and fire-proof gypsum board, which have been widely used for lightweight panel wall material, were selected as experiment samples, and heating temperatures were set as $100^{\circ}C$, $200^{\circ}C$, $300^{\circ}C$, $400^{\circ}C$, $500^{\circ}C$ and $600^{\circ}C$. Next, each of the heating temperatures were introduced on the bottom part of the wall material for 30 minutes, and analyses were made on the heat transfer characteristics to the backside part on the top part through conduction. As results of the experiment, the maximum backside temperatures were measured up to $190^{\circ}C$ for a general gypsum board, $198^{\circ}C$ for a fire-proof gypsum board, $189^{\circ}C$ for a plywood, $321^{\circ}C$ for a marble, and $418^{\circ}C$ for a heat resistant glass as heating temperatures were introduced maximum of $600^{\circ}C$. In addition, the maximum change rate of conduction heat transfer were measured up to 85 W for a general gypsum board, 95 W for a fire-proof gypsum board, 67 W for a plywood, 1686 W for a marble, and 3196 W for a heat resistant glass as the maximum heating temperatures were introduced up to $600^{\circ}C$. Also, carbonization characteristics of the wallpapers were measured to visually check the danger of conduction heat transfer, and the results showed that smokes were first generated on the attached wallpapers for the heating temperature $600^{\circ}C$, which were 1021 s for a general gypsum board, 978 s for a fire-proof gypsum board, 1395 s for a plywood, 167 s for a marble, and 20 s for a heat resistant glass, and that the first generation of carbonization were 1115 s for a general gypsum board, 1089 s for a fire-proof gypsum board, 1489 s for a plywood, 192 s for a marble, and 36 s for a heat resistant glass.

Connection Tests for Cold-Formed Steel Wall Panels (냉간성형강 벽체패널의 연결부실험)

  • Lee, Young-Ki
    • KSCE Journal of Civil and Environmental Engineering Research
    • /
    • v.34 no.3
    • /
    • pp.739-746
    • /
    • 2014
  • The objective of this test series was to determine shear load per unit length which causes a unit slip in the fastener joint. The shear load is one of major factors which reflect partial composite action for cold-formed steel wall stud panels. Test method used were based on the methods presented in the 1962 AISI Specification. According to the comparison with experimental strength, it is seen that the shear loads used in nominal axial strength predictions made acceptable results.

Variation Characteristics of Stiffness and Impact Resistance under Conastruction Height of Gypsum Board Wall (석고보드 벽체의 시공높이에 따른 수평하중저항성 및 내충격성 변동 특성)

  • Song, Jung Hyeon;Kim, Ki Jun;An, Hong Jin;Shin, Yun Ho;Ji, Suk Won;Choi, Soo Kyung
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2014.11a
    • /
    • pp.184-185
    • /
    • 2014
  • The purpose of this study is to experimentally evaluate the variation characteristics of stiffness and impact resistance under the construction height of gypsum board wall at the actual construction site. The method suggested in previous study was applied on the test method of horizontal load resistance and impact resistance. As a result of horizontal load resistance test, when the wall height is 2,400 mm, the maximum displacement is 13.6 mm and residual deformation is 0.5 mm, and when the wall height is 3,000 mm, the maximum displacement is 31.3 mm and the residual displacement is 6.8 mm. As a result of impact resistance test, the residual deformation of each specimen at 20 cm of fall height were 1.02 mm and 0.08 mm, respectively, the residual deformation at 40 cm of fall height were 1.58 mm and 0.35 mm, respectively, and the residual deformation at 60 cm of fall height were 2.23 mm and 2.48 mm, respectively.

  • PDF

Partial Composite Action of Gypsum-Sheathed Cold-Formed Steel Wall Stud Panels (석고보드와 결합된 강재 샛기둥 패널의 부분 합성거동)

  • Lee, Young Ki
    • Journal of Korean Society of Steel Construction
    • /
    • v.13 no.4
    • /
    • pp.373-380
    • /
    • 2001
  • The problem addressed in this study is how to analytically treat the partial composite action for wall panels. An equation, derived for wood-joist floor systems, which determines deflections for beams with partial composite action is introduced. The equation is applied to the calculation of the mid-span deflection for gypsum-sheathed, cold-formed steel was stud panels. The objective of this study is to properly reflect the influence of the following factors in the calculation of mid-span deflection for the panel: connection slip, local buckling, perforations in the stud web, and effects from joints in the sheathing. Predicted deflections based on an upper bound for connection rigidity were closest to experimental deflections.

  • PDF

A Study on the Fire Resistance Performance of Wood Framed Lightweight Wall which Including a Middle Lintel (중인방을 포함한 목골조 경량벽체의 내화성능에 관한 연구)

  • Yeo, In-Hwan;Cho, Bum-Yean;Min, Byung-Yeol;Yoon, Myung-O
    • Fire Science and Engineering
    • /
    • v.25 no.3
    • /
    • pp.91-98
    • /
    • 2011
  • This study is about fire resistance performance of wood framed lightweight wall including a middle lintel as a traditional wall form in Korea. The target wall is non-loadbearing system which constructed with $38{\times}89$ mm ($2"{\times}4"$) wood frame and fireproof gypsum board covering, including a middle lintel made of $150{\times}150$ mm section glue-laminated timber. As a test results, all specimens have showed fire resistant performance over 90 minutes and tests were maintained until flame occuring on Specimen-l, 2, 3 at 91 min, 97 min and 98 min respectively. Fire resistance of the heat side gypsum board was 45 minutes and charring rate of middle lintel was equivalant with that of usual timber. The wood stud inside wall system showed relatively quick combution characteristic when exposed to high temperature with no temperature rising delaying time caused by moisture evaporation because of the dehydration preceded during the early period of fire side gypsum board resist to heat.

A Study on the Flexural Strength Capacity of Wall Stud Assembly (경량형강 스터드 벽체의 휨강도에 관한 연구)

  • Kwon, Young Bong;Chung, Hyun Seok;Kim, Gap Deuk
    • Journal of Korean Society of Steel Construction
    • /
    • v.15 no.2
    • /
    • pp.109-116
    • /
    • 2003
  • An investigation on the structural behavior of cold-formed steel lipped C-section stud for interior walls or partitions was carried out. This experimental research was carried out to study the ultimate and service load capacity of stud assemblies that are subjected to lateral loads. Each test specimen consisted of three or four lipped C-section studs and two C-section tracks that restrained both ends. The major factors considered in this experiment were the perforation on the web, the connection of the bridge channel and the special clip. The effect of the plaster board and the ply wood, which were attached to the tension flange on the flexural strength, was also investigated. Thereafter, the test strength capacities were compared with the nominal strength, based on the AISI Specifications (1996).

An Optimization Algorithm of Gypsum Board Loss for Wall Finishing in Modular Construction System (모듈러건축 벽체마감 석고보드 손실 최적화 알고리즘 개발)

  • Lee, Dong-Min;Chin, Sangyoon
    • Korean Journal of Construction Engineering and Management
    • /
    • v.15 no.1
    • /
    • pp.101-110
    • /
    • 2014
  • The ministry of Land, Infrastructure and Transport announced that they launched the pilot project to offer Happy House built with modular construction as part of the major projects of incumbent government in 2013. The market size of modular construction is getting increasingly enlarged together with strong will of government. The major challenges that current modular construction encounters can be summed up as lack of standardization of material on the stage of design and fabrication. The portion of material costs in modular construction marks 16 to 17% higher than the existing other construction method, and account for 60 % of total construction cost, which is why material management is the most important factor. However, the imperfect standardization and specification on design causes high loss of materials on fabrication, which makes the construction wastes and total construction cost increasing in accordance with the increase of material costs. This study has been conducted to verify major modules by developing optimization algorithm on gypsum board material among wall finishing materials. It is expected that this paper contributes not only to eco-friendly construction by minimizing the waste factors of materials through these efforts, but also to removing high cost issues which had been recognized as a setback of current modular construction.

Evaluations of Shear performance and Compressive strength of Light-weight hybrid panel (경량합성벽체의 전단성능 및 압축내력 평가)

  • Lee, Dong Hyuck;Lee, Sang Sup;Bae, Kyu Woong;Moon, Tae Sup
    • Journal of Korean Society of Steel Construction
    • /
    • v.17 no.1 s.74
    • /
    • pp.33-43
    • /
    • 2005
  • This paper presents the test results and evaluations for the energy dissipation capacity and compressive performance of light-weight hybrid panels. A total of 26 full-scale specimens of light-weight hybrid panels were tested. The parameters include the presence of light-weight foamed mortar, the specific gravity of light-weight foamed mortar (0.6, 0.8, 1.0, 1.2), the finishing materials (light-weight foamed mortar, OSB [Oriented Strand Board], gypsum board), the shape of bracing (x, ~), and the size of panels (1P-900 mm 2,400 mm, 2P-1,800 mm 2,400 mm). The results of the cyclic tests are somewhat different from those of monotonic tests, due to the different specific gravity of light-weight foamed mortar. It was found from the compressive tests that the ultimate strength and initial stiffness are increased by means of light-weight foamed mortar (2~2.5 times in ultimate strength and 2~3 times in initial stiffness).