• Title/Summary/Keyword: 비상전원장치

Search Result 50, Processing Time 0.032 seconds

A Study on the Development of Digital Power Supply for Ship′s Emergency Lighting System (선박 비상조명용 디지털 전원장치 개발)

  • Lee, Sung-Geun
    • Journal of Navigation and Port Research
    • /
    • v.28 no.8
    • /
    • pp.667-671
    • /
    • 2004
  • This paper describes an development of digital power supply for ship's emergency lighting system(SELS). Proposed system is composed of emergency power supply system(EPSS), half bridge(HB) inverter, fluorescent lamp(FL) starting circuit and microprocessor control system. Experimental works using proposed system confirm that speedy and stable power to be supplied when main power source cut-off, compared with conventional analog type, and control input power up to 35.0[%] by adjusting pulse frequency of the HB inverter.

A Study on Power Conversions of the Power Supply for Fire Safety Use (소방용 전원장치의 전력변환에 관한 연구)

  • Kwon, Seong-Pil;Lee, Jang-Won;Yook, Gil-Soo
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2011.11a
    • /
    • pp.462-465
    • /
    • 2011
  • 최근 우리나라에서는 대형 화재사고가 빈번히 발생함에 따라 그로 인한 재산 및 인명피해가 날로 증가하고 있는 실정이다. 따라서 건축물 내에서 화재가 발생할 경우 인명피해를 최소화하기 위하여 피난유도설비의 설치를 의무화하고 있다. 지금까지 일반적으로 가장 널리 사용되고 있는 피난유도설비로는 유도등이 있으며, 최근 들어 피난유도선의 설치도 다중이용업소를 중심으로 점차 확대되어가고 있는 추세이다. 피난유도설비는 평상시 이용되는 교류 상용전원에 의해서뿐만 아니라 비상시 이용되는 직류 비상전원에 의해서도 정상적으로 작동되어야 하기 때문에, 피난유도설비의 전원장치는 주어진 전원으로부터 주어지는 교류 또는 직류를 발광부에 맞게 일정한 전압과 주파수로 변환시켜주어야 한다. 실제로 LED(발광다이오드) 유도등은 상용전원으로부터 220V의 교류를 받아서 전원장치에서 정류변환을 통해 얻어지는 낮은 전압 24V의 직류를 이용하며, 대부분의 유도등 백라이트로 사용되고 있는 CCFL(냉음극형광램프)에는 상용전원으로부터 220V, 60Hz 교류를 인가받아 전원장치에서 정류 역변환을 통해 만들어진 100kHz의 고주파 교류가 공급된다. 더욱이 유도선의 전원장치에서는 상용전원 220V, 60Hz의 교류를 인가받아 정류 역변환 및 교류변환 과정을 차례로 거쳐 최종적으로 100V, 400Hz의 교류로 전환하여 TFEL(박막전계발광) 소자로 전송하게 된다. 한편, 상용전원이 차단된 상태에서도 전원장치는 마찬가지로 비상전원으로부터 24V의 직류를 공급받아 인버터를 통해 역변환 하여 100kHz의 고주파 교류를 만들어 주거나 추가적인 교류변환을 거쳐 100V, 400Hz의 교류로 변환시켜 내보낸다. 본 연구에서는 상대적으로 복잡한 전력변환 회로들을 포함하고 있는 유도선의 전원장치를 개선하여, 전원장치의 연결가능길이를 기존의 60m에서 최대 100m까지 연장시킴으로써, 터널이나 지하도와 같은 곳에서 특히 경쟁력을 갖게 될 것으로 기대된다.

  • PDF

The Utilization of Energy Storage System(ESS) as Emergency Power Source for Nuclear Power Plant (원자력 발전소 비상전원으로써 ESS의 활용)

  • Lee, Woo-Rim;Chang, Choong-koo
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.641-642
    • /
    • 2015
  • 에너지저장장치(Energy Storage System, ESS)는 생산된 전력을 전력계통에 저장했다가 전력이 가장 필요한 시기에 꺼내어 사용함으로써 에너지효율을 높이는 능동적인 기술이다. ESS는 풍력발전, 태양광발전 등 신재생에너지와 같은 분산전원 도입, 피크부하에 대응하기 위한 부하평준화, 전력품질개선 등 그 역할과 기능이 확대되고 있다. 본 논문에서는 후쿠시마 사고 이후 강조된 비상전원과 관련하여 원자력발전소 부지 내 비상전원으로써의 ESS 활용과 그 가능성에 대해서 기술하였다.

  • PDF

A Study on the Safety Security of Emergency Power for Fire Fighting (소방용 비상전원 안전성 확보에 관한 연구)

  • Lee, Won-Kang;Choi, Chung-Seog
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2012.04a
    • /
    • pp.133-136
    • /
    • 2012
  • 본 논문에서는 소방용 비상전원 안전성 확보에 관한 것으로서, 과부하 조건 회피를 위한 인터록 시스템 및 기타 방법의 한계점을 분석하여 최근 제도적으로 도입된 소방전원보존형 발전기의 필요성과 타당성을 확인하고 나아갈 방향을 제시하는데 있다. 소방부하 및 비상부하 겸용의 자가발전설비에서 어느 한쪽의 용량으로만 택일하여 설치할 경우 정전 및 화재 발생 시 발전기 용량 초과로 비상전원 공급 중단과 소화설비의 미작동의 위험이 초래된다. 소방시설에 비상전원의 안전한 공급을 목적으로 하는 소방전원보존형 발전기는 과부하에 도달되면 소방전원보존용 컨트롤러에서 신호를 발신하여 소방부하는 남겨두고 비상부하의 일부 또는 전부를 차단하고, 소방부하에 비상전원이 연속적으로 공급하고 그 작동 상태가 표시되는 표시장치를 특징을 가진 시스템이다. 소방 안전을 확보하는 제도는 안전을 위한 행정적인 절차와 기준을 지킴으로써 기술적인 안전성이 보장되도록 하는 방식으로 운용되고 있다. 이에는 확인 절차가 필수적으로 요구되는 것이다. 임의의 구두 진술로나 이와 다름없는 임의적인 서류로만 인정할 수는 없는 것이며, 그럴 경우 제도에 의한 소방 안전 확보의 보장성이 무너지기 때문이다.

  • PDF

A Study on the Implementation and Modeling of 20kW Scale ESS Load Test Device for Emergency Generator (소방용 비상발전기의 현장부하시험을 위한 20 kW급 ESS 부하시험장치 모델링과 구현에 관한 연구)

  • Choi, Seung-Kyou;Lee, Hu-Dong;Choi, Sung-Sik;Ferreira, Marito;Rho, Dae-Seok
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.20 no.9
    • /
    • pp.541-550
    • /
    • 2019
  • An emergency generator is key equipment for fire-fighting to supply power to fire-fighting facilities, which protect property and people in cases of fire accidents. A rated load test for emergency generators must be carried out by connecting an emergency load to the generator in accordance with related regulations. However, a no-load test has been performed for emergency generators in general since serious problems can occur when the main power is cut off, including the damage of customer devices and shut down of critical loads. Therefore, this paper proposes a load test method for an emergency generator using energy storage system (ESS) without the interruption of main power. The emergency power system was also modeled based on PSCAD/EMTDC software, and a 200-kW scale ESS load test device was implemented. The simulation and test results show that the load test method is useful and practical for an emergency power supply system.

A Study on Improvement of Operation Characteristics and Inspection Method of Standby Power Supply such as Emergency Induction Light using Li-ion Capacitor (리튬이온커패시터를 활용한 비상유도등 예비전원장치의 동작 특성 및 점검방법 개선에 관한 연구)

  • Jung, Jun-Chea
    • Journal of the Society of Disaster Information
    • /
    • v.16 no.2
    • /
    • pp.392-401
    • /
    • 2020
  • Purpose: This study analyzes the operating characteristics of a lithium ion capacitor that can be used as a standby power supply in an emergency, and determines whether the standby power supply is abnormal even by measuring the voltage using a linear proportionality characteristic during charging and discharging. The aim is to provide an experimental basis that can be done. Method: As a method for this study, first, analyze the operation principle and characteristics of the existing backup power supply and lithium ion capacitor, and then measure the voltage of the lithium ion capacitor according to the configuration and system block diagram of the induction lamp used in the experiment. We proceed with the test of the measured value of discharge power for each voltage band to check the amount of power held by the battery and the operation test experiment using induction lamps. Results: Just by checking the charging voltage using the linear proportional characteristics of lithium ion capacitors, it provides a basis for accurately inferring the effective operating time of induction lamp lamps. Conclusion: In the event of a disaster, the lithium ion capacitor is used as a spare power supply for emergency induction lamps to prevent complete discharge of emergency induction lamps, to prevent the problem of performing normal operation of the standby power supply, and to use only a simple voltage measurement to reserve power. It was intended to suggest many uses for evacuation equipment application in the future by making it possible to check whether the device is abnormal.

Battery charge system with Characteristics of Fast Discharge and slow charge (대용량 방전 특성과 완속 충전 기능을 갖는 배터리 충 방전 시스템)

  • Lee, Dong hyun;Kim, Hag-Wone;Cho, Kwan-Yuhl;Lee, Young-Gyu
    • Proceedings of the KIPE Conference
    • /
    • 2014.07a
    • /
    • pp.233-234
    • /
    • 2014
  • 본 논문에서는 비상 전원 공급 장치(emergency power supply 이하 EPS)를 위한 양방향 컨버터에 대하여 다룬다. 비상 전원 공급 장치용 양방향 컨버터는 대용량의 방전을 위한 Full Bridge(이하 PSFB)와 완속 충전을 위한Two-Transistor Forward converter로 구성된 비상전원 장치용 배터리 충방전 시스템을 제안한다.

  • PDF

Design of Ballast for a turning on a lamp in both common use and emergency (상용/비상 겸용 형광등 안정기 개발)

  • Jun, Kwang-Ho;Song, Soo-Min
    • Proceedings of the KIEE Conference
    • /
    • 2004.05b
    • /
    • pp.217-219
    • /
    • 2004
  • 종래의 비상 조명 장치로는 배터리 충전 회로를 이용하는 방법이 있으며 이는 정상적으로 전원이 공급되지 않는 한 배터리가 완전히 방전될 때까지 배터리와 비상 점등 회로가 연결되어 배터리의 과방전을 초래하고, 더 나아가 배터리의 특성상 과충전이나 과방전상태에 도달하여 배터리가 손상되어 사용할 수 없는 경우가 발생하기도 한다. 본 연구는 상기와 같은 종래 기술의 제반 단점과 문제점을 해결하기 위한 것으로, 상용시뿐만 아니라 기타 비상시에도 형광등에 전원이 공급되도록 하는 안정기를 개발하는 것을 목적으로 한다.

  • PDF

Hybrid System Design for Emergency Power Supply of Ground Robots (지상 로봇의 비상 전원 공급을 위한 하이브리드 시스템 설계)

  • Jo, Yeong-Min;Choi, Ju-Yeop;Choy, Ick;Cho, Sang-Yoon;Lee, Dong-Ha
    • Proceedings of the KIPE Conference
    • /
    • 2014.11a
    • /
    • pp.54-55
    • /
    • 2014
  • 일반적으로 지상 로봇의 주 전원으로 사용되는 대용량 배터리가 예상치 못한 시점에 방전되거나 고장으로 인해 전원 공급이 되지 않을 경우 지상 로봇의 위치 확인이 필요하게 된다. 이에 따라 본 논문에서는 이 통신용 비상 전원 공급을 위한 태양광 및 연료전지 전원 공급 장치와 이 장치를 보완하여 사용할 수 있는 배터리 충 방전 하이브리드 시스템을 설계하고, 이를 시뮬레이션과 실험을 통해 타당성을 검증 및 분석하도록 한다.

  • PDF