• Title/Summary/Keyword: 보일러

Search Result 2,432, Processing Time 0.03 seconds

The Impact of Side Reactions in Sulfur Recovery Unit Design (황 회수 공정 설계에서 부 반응의 영향)

  • Kim, Sung Ho;Jung, Won Seok;Lee, Hee Mun;Chang, Geun Soo
    • Plant Journal
    • /
    • v.13 no.3
    • /
    • pp.36-46
    • /
    • 2017
  • In the reaction furnace of modified Claus process, chemical equilibrium reactions and kinetic reactions occur simultaneously. The main kinetic components are hydrogen ($H_2$), carbon monoxide (CO), carbonyl sulphide (COS) and carbon disulphide ($CS_2$). The equilibrium calculations, empirical correlations and sulfur recovery technology providers' (licensors) data for kinetic components (COS and $CS_2$) in the reaction furnace were analyzed to evaluate the amount of kinetic components by applying them to five different projects in which GS Engineering & Construction participated. Kinetic components ($H_2$ and CO) are also calculated and the results are analyzed to evaluate the impact of temperature in the reaction furnace and the waste heat boiler. Total required $O_2$ deviations for combustion in the reaction furnace are additionally shown, with and without side reactions. A full understanding of side reactions in the modified Claus process can help to improve sulfur recovery efficiency and optimize equipment design.

  • PDF

Comparison of Combustion Characteristics With and Without Water Tube Simulating Heat Exchanger in Two Sections Porous Media Burner (2단 다공성 매체버너에서 열교환기를 모사한 수관 유무에 따른 연소 특성 비교)

  • Lee, Hui-Do;Kim, Jae-Hyeon;Lee, Kee-Man
    • Journal of the Korean Institute of Gas
    • /
    • v.23 no.5
    • /
    • pp.24-34
    • /
    • 2019
  • In this study, the experimental studies were conducted to analyzing characteristics of combustion and flame stabilizing according to with and without water tube in boiler. The burner has consisted of SiC foam where has the location of submerged flame between a ceramic board acting as flash-back arrestor. Porous burner is also insulated to minimize heat loss in the radial direction. In the condition of fixed equivalence ratio, the flame mode was divided into three stability zones by the flow rate. The main factor for blow-off and flash-back depends on mixture flow rate. Consequently, the case of burner with water-tube has higher NOx emissions than without case. This result explains that the presence of water-tube makes the heat loss resistant to ambient temperature with increasing of NOx. This tendency was proved by predicting the relationship between O2 emission and NO production rate, and by analysing temperature profiles.

Utilization of Circulating Fluidized Bed Combustion Ash and Related Specifications for Mine Backfills (순환유동층 석탄재의 활용 기술과 광산 채움재 관련 규격 동향)

  • Jang, Jeong Gook;Ji, Sangwoo;Ahn, Ji-Whan
    • Resources Recycling
    • /
    • v.26 no.2
    • /
    • pp.71-79
    • /
    • 2017
  • Circulating fluidized bed combustion (CFBC) ash is one of useful mineralogical resources having abundant content of free lime and anhydrite, and has a self-cementitious property. Recently, considerable interest has been gained regarding the utilization of CFBC ash, along with its use in mine backfill and reclamation. Prior to adopt the use of CFBC ash in the mine backfill technology, discussion on the technology and related specification is prerequisite in the future. This paper presents a review on studies in the emerging technology of CFBC ash utilization, and provides useful information with regard to the specifications for mine backfills utilizing CFBC ash.

A Study on the Regeneration of SCR Catalyst Deactivated by Unburned Carbon Deposition (탄소침적으로 피독된 탈질 촉매의 재생에 관한 연구)

  • Moon, Seung-Hyun;Lee, Seung-Jae;Ryu, In-Soo
    • Journal of Korean Society of Environmental Engineers
    • /
    • v.32 no.10
    • /
    • pp.928-935
    • /
    • 2010
  • A bag filter system was partially burnt down during a trial run of waste wood incineration boiler. This brought about unburned hydrocarbon which caused a rapid deactivation of low temperature SCR catalyst set up in two stage after the bag filter. The deactivated catalyst was investigated in order to trace the origin by several characterization methods such as XRD, EDX, BET, TGA, SEM. The deactivated catalyst was regenerated by different methods such as acid washing, water washing in ultrasonication, and calcination treatment under air condition. It is found the calcination treatment under air condition at $450^{\circ}C$ for 2 hours to be the best regeneration method. The catalytic activity was measured in the form of 2 cm ${\times}$ 2 cm ${\times}$ 10 cm (catalyst weight 10 g) honeycomb type. A deNOx efficiency of the regenerated catalyst showed 100% at $180^{\circ}C$ which is the same level of fresh one.

Performance Evaluation and Economic Estimation of Ground Source Heat Pump Cooling and Heating System (지열 냉난방 시스템의 성능 및 경제성 평가)

  • Lim Hyo Jae;Song Yoon Seok;Kong Hyoung Jin;Park Seong Koo
    • Journal of Energy Engineering
    • /
    • v.13 no.4
    • /
    • pp.296-300
    • /
    • 2004
  • Performance evaluation and economic estimation were conducted on the water to water GSHP (Ground Source Heat Pump) installed in existing building. Ground heat exchanger was a closed vertical loop type and sized to be 5 boreholes and 100m depth per borehole. Operation efficiency of the system shows that, COP increased from 3.0 to 4.2 with entering water temperature in heating operation, however, COP decreased from 5.0 to 3.7 in cooling operation. Economic estimation was analyzed by LCC (Life Cycle Cost) method and it showed that GSHP could save 68% of cost compare to the conventional oil source. Thus, despite of the large amount of initial cost, GSHP has a economic advantage to the other energy sources.

Load Following Operation Improvement by Governor Control Logic Modification of Thermal Power Plant (System Frequency Drop Prevention) (기력발전소 터빈조속기 제어로직 개선에 의한 발전기 부하추종성 향상 (계통주파수저하방지))

  • Lee, Jong-Ha;Kim, Tae-Woong
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.11 no.4
    • /
    • pp.302-306
    • /
    • 2006
  • The improvement of load following operation of the thermal power plant is influenced to the electrical quality. Analysis of boiler, turbine, and governor system, and the study of control algorithm are necessarily preceded. The thermal power plant is operated by various control systems. In the case of faulty governor system, it takes long days to solve the problem and impossible to repair the mechanism without outage. A non-planned outage is taken into consideration because of economical power production. The paper introduces the followings; In case of system-frequency drop during long term, at 500MW thermal power plant, the generator output was drop. To clear this problem, the control logic is modified with analysis of trend and control algorithm. As a result system frequency drop is prevented during the long tenn and the electric grid operation is improved.

A Sensor Value Validation Technique for Supporting Stable Operations of Thermal Power Plants (화력발전소의 안정운전 지원을 위한 계측값 검증 기법에 관한 연구)

  • Lee, Seung-Chul;Kim, Seung-Jin;Han, Seung-Woo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.12
    • /
    • pp.201-209
    • /
    • 2009
  • In power plant operations, sensor values often exhibit erroneous values due to their failures or the intrusions of various noises. However, most of the power plant monitoring and fault diagnosis systems perform their tasks based on the assumptions that the collected sensor values are correct all the times. These assumptions, which are not valid, often lead to serious consequences such as power plant trips. In this paper, we propose a power plant sensor value validation technique that can utilize the relationships existing among the sensor values as the sensor redundancy. The proposed technique is applied to the flow meters installed along boiler feed water systems of a typical tubular type boiler thermal power plant and shows a good potential of future applications.

The study on the variable orifice spray of the steam power plant desuperheater (화력발전설비의 과열증기저감용 가변오리피스 분사 특성)

  • Kim, Jeong-Sik;Kim, Kwang-Hee;Lee, Jong-Sun
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.14 no.1
    • /
    • pp.63-68
    • /
    • 2013
  • The steam power plant is becoming more important to supply a stable power lately. Desuperheater of the steam power plant facility plays a role in maintaining the proper superheat to avoid damage turbine power due to the superheated steam produced in the boiler. In this study, when the steam flows $530^{\circ}C$, 36.7 kg/s, 1.36 MPa in the 460mm pipe, variable orifice nozzle developed in Korea was carried out the performance analysis in coolant injection conditions of $150^{\circ}C$, 4.28 MPa. Findings, steam pipe coolant temperature was maintained at $446^{\circ}C$ and sprayed droplet size was verified by $50{\mu}m$ or less.

Structural Integrity Evaluation of Large Main Steam Piping by Water Hammering (수격 현상에 근거한 대형 주증기관의 구조건전성 평가)

  • Jo, Jong-Hyun;Lee, Young-Shin;Kim, Yeon-Whan;Jin, Hai Lan
    • Transactions of the Korean Society of Mechanical Engineers A
    • /
    • v.36 no.9
    • /
    • pp.1103-1108
    • /
    • 2012
  • A main steam pipe system is a branch pipe that connects a boiler with a turbine. Water hammering analysis is very important for limiting the damage caused to pipe systems by operation conditions. Water hammering created by an unsteady flow in pipeline systems can cause excessive change in pressure, vibration, and noise. The main steam pipe structure should be designed to safely maintain the pressure pulsation and several vibrations under operation environments. This study evaluated the structural integrity of a main steam pipe during suspended and normal operation by using the ASME fatigue life methodology and finite element analysis. In the analysis, water hammering was used for transient analysis. The calculated alternating stress and fatigue stress were compared with the applicable limits of ASME fatigue life. All the evaluation results satisfied the requirements of the ASME fatigue life.

Detection and Evaluation Technique of Hydrogen Attack (수소손상 검출과 평가기술)

  • Won, Soon-Ho;Hyun, Yang-Ki;Lee, Jong-O;Cho, Kyung-Shik;Lee, Jae-Do
    • Journal of the Korean Society for Nondestructive Testing
    • /
    • v.22 no.1
    • /
    • pp.32-37
    • /
    • 2002
  • The presence of hydrogen in industrial plants is a source of damage. Hydrogen attack is one such form of degradation and often causing large tube ruptures that necessitate an immediate shutdown. Hydrogen attack may reduce the fracture toughness as well as the strength of steels. This reduction is caused partially by the presence of cavities and microcracks at the grain boundaries. In the past several techniques have been used with limited results. This paper describes the application of an ultrasonic velocity and attenuation in hydrogen damage. Ultrasonic tests showed a decrease in wave velocity and an increase in attenuation. Such results demonstrate the potential for ultrasonic nondestructive testing to quantify damage. Based on this study, reliable recommendation is suggested to detect hydrogen attack.