A Study on the Construction of Test circuit and Unification of Experiment Method for High Voltage Gas-insulated Load Switch using High Power Testing System (특고압 가스 절연 부하 개폐기의 통합형 대전력 시험 방법 및 회로 구성에 관한 연구)

  • Jung, Heung-Soo;Kim, Min-Young;Kim, Juen-Suk
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.12
    • /
    • pp.36-46
    • /
    • 2008
  • This paper is to study on the Construction of Test circuit and Unification of Experiment Method for high voltage gas-insulated load switch using high power testing system The high power testing system is a equipment to verify electrical and mechanical performance on electrical product. The system consist of short-circuit generator, back-up breaker, making switch, impedance, high voltage transformer, low voltage transformer, measuring and protection system, etc. Using this system, we can test related to high power, for example, short-time current test, active load Current test, magnetizing Current test, capacitive current test, closed loop current test, etc. Standards of high voltage gas-insulated load switch that is in use domestic distribution line are ES 5925-0002, IEC 60265-1, IEC 62271-1 and IEEE C 37.74, etc. In this paper, we standardized on the test procedure, organization of test circuit and analysis of measured data prescribed many difference standards, and applied this test method to 600[MVA] high power testing system. So that we can test the load switch satisfied standards.

Distribution Remote Management System Design and Program Development Based on ADWHM(Advanced Digital Watt-Hour Meter) (차세대 디지털 적산전력계에 기반한 배전원격관리시스템 설계 및 프로그램 개발)

  • Ha Bok-Nam;Ko Yun-Seok
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.4
    • /
    • pp.185-192
    • /
    • 2005
  • This paper proposes a DRMS(Distribution Remote Management System) which can enhance highly the economics of automatic metering system and the power quality supplied to the electric customer improving the efficiency of the meter reading, voltage management and load management work by realizing the remote meter reading, the remote voltage management and the remote load management based on the ADWHM(Advanced Digital Watt Hour Meter). The DRMS is designed so that the voltage management and load management work in remote site can be processed by collecting the voltage pattern and current pattern as well as watt hour data from all ADWHMs one time every month regularly or from special ADWHMS several time irregularly, A new on-line voltage and load management strategy based on the ADWHM is designed by analyzing the existing voltage management and load management process. Also, DRMS is designed so that watt-hour data, voltage pattern data, load pattern data and power factor data can be collected selectively according to the selection of user to assist effectively the methodology. Remote management program and database of the DRMS are implemented based on Visual C++, MFC and database library of MS. Also, DRMS is designed so as to communicate with the ADWHM using RS232C-TCP/IP converter and ADSL. The effectiveness of the remote metering function is proven by collecting and analyzing the data after ADWHMs installed in any site. The developed strategy and program also is verified through the simulation of voltage management and load management.

Study on Development Method of MDMS for AMI Operation based on Common Information Model (CIM 기반 AMI용 미터데이터관리시스템(MDMS) 개발 방안 연구)

  • Jung, Nam-Joon;Jin, Young-Taek;Chae, Chang-Hun;Choi, Min-Hee
    • KIPS Transactions on Computer and Communication Systems
    • /
    • v.1 no.3
    • /
    • pp.171-180
    • /
    • 2012
  • In the development of MDMS(Meter Data Management System) based on CIM(Common Information Model), which is international standard in information model and data exchange on power system, the two focused issues are the effective management of data collected in a shorter time period and the way to integrate services supporting legacy system to use the AMI(AMI, Advanced Metering Infrastructure) data. In this paper, we propose MDMS implementation methods and functions in AMI environment which are differ from existing AMR system environments in that the methods support bi-directional service infrastructure. The proposed MDMS in this paper has two unique features, one is the secure of interoperability by utilizing the CIM and ESB, the other is the improvement of field application by implementing system module based on components. On an implementation of smart grid, the result of proposed methods is expected to contribute to the efficient development and operation of CIM-based power system.

Inrush Current Control of Matching Transformer for Dynamic Voltage Restorer (동적전압보상기를 위한 정합 변압기의 돌입전류 제어)

  • Seo, Il-Dong;Jeon, Hee-Jong;Shon, Jin-Geun
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.11 no.4
    • /
    • pp.340-348
    • /
    • 2006
  • This paper proposes an inrush current control technique of matching transformer for configuration of dynamic voltage restorer(DVR). The DVR system consist of PWM inverter to inject arbitrary voltage, LC low pass filter as harmonic eliminator and matching transformer for isolation. However, the matching transformer has an excess of inrush current by magnetic flux saturation in the core. Due to this inrush current, the rating of matching transformers is double for needed nominal rating for protection of DVR. Therefore, in this paper, the modeling method of magnetic flux saturation is used to analyze a magnitude of inrush current, and additional current controller is used for PWM inverter output regulation. Simulation and experimental results are provided to demonstrate the validity of the proposed control method.

Development of electric safety control system for incapable operation of ELB and MCB using the low voltage distribution line (저압 배전선로의 누전 및 배선용 차단기의 오동작 방지를 위한 전기안전 제어장치 개발)

  • Kwak, Dong-Kurl;Shin, Mi-Young;Jung, Do-Young;Kim, Hyo-Jin;Baek, Seong-Hyun;Choi, Byung-Seub
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.371-372
    • /
    • 2007
  • The major causes of electrical fire are classified to short circuit fault, overload fault, electric leakage and electric contact failure. The occurrence factor of the fire is electric arc or spark accompanied with electrical faults. Residual Current Protective Device (RCD), that is Earth Leakage Circuit Breaker(ELB) and Molded_case Circuit Breaker (MCB), of high sensitivity type used at low voltage wiring cuts off earth leakage and overload, but the RCD can't cut off electric arc or spark to be a major factor of electrical fire. As the RCDs which are applied low voltage distribution panel are prescribed to rated breaking time about 30[ms] (KS C 4613), the RCDs can't perceive to the periodic electric arc or spark of more short wavelength level. To be improved on such problem, this research development is proposed to a auxiliary control apparatus for RCD trip on electric arc or spark due to electrical fire. Some experimental results of the proposed apparatus is confirmed to the validity of the analytical results.

  • PDF

Analysis on Electromagnetic Loss Characteristics of Bus bar and Enclosure according to the Specifications of Enclosures for a 24kV Switchgear (24kV급 배전반의 외함재질과 두께에 따른 Bus bar와 외함의 전자기 손실특성 분석)

  • Heo, Jeong Il;Hong, Jonggi;Kang, Hyoungku
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.62 no.4
    • /
    • pp.181-185
    • /
    • 2013
  • This paper deals with the electromagnetic loss characteristics of enclosures for a 24kV high voltage switchgear by using a finite element method (FEM). A study on the electromagnetic characteristics of enclosures for a high voltage switchgear should be conducted to minimize the size and the temperature rising of a switchgear. Generally, the enclosures made by stainless steel are used to minimize the eddy current loss caused by the transporting current in Bus bars due to its non-magnetic characteristics although the price of stainless steel is expensive compared with other metal for enclosures. Therefore, a switchgear made by stainless steel enclosures could be fabricated as a small size and are applied to a switchgear in urban substations. On the contrary, the switchgear enclosures made by steel could be fabricated with relatively cheap manufacturing price. However, the temperature easily rises due to the transporting current in Bus bars because steel is a ferromagnetic material. Therefore, the size of a switchgear made by steel enclosures is relatively massive and installed in rural substations. In this paper, the electromagnetic losses in the enclosures of a switchgear according to various enclosure thicknesses are calculated and compared with each other. Especially, we proposed a hybrid type enclosures for a switchgear made by stainless steel (top and bottom enclosure) and steel (left and right enclosure). It is concluded that the cost electromagnetic performance of applying the hybrid type enclosure is favorable to develop a high voltage switchgear.

Optimal Location of Mail Distribution Center using Steiner Tree (Steiner Tree 이론을 이용한 우편물 교환센터인 최적 워치선정)

  • Yang, Seong-Deog;Lyu, Woong-Gyu;Lee, Sang-Joong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.9
    • /
    • pp.82-87
    • /
    • 2008
  • Faster, safer and cheaper mailing of the postal matter is essential for surviving in the competitive market of home-delivery service. In the past, the domestic delivery business has been nu by only a few number of companies. But more and more number of companies including medium size ones are participating in the business, and the competition is getting severe. This paper proposes a method to select the optimal location of mail distribution centers that minimally connect the local mail centers of some major cities in Korea using the Steiner Tree theory, which is about connecting a finite number of points with a minimal length of paths and has been used in the distribution system optimization and optimal routing of the transmission lines of the electric power system. By using Steiner Tree theory in finding the best location of the postal delivery hub, we may expect the reduction of transportation cost and the increase of profit, resulting in acquiring the superior position in the competitive delivery business. It is expected that we may use the Steiner Tree theory in finding the best location of the electric power substation for the nott higher EHV(extreme high voltage) transmission network.

A Study on the Outages Due to Voltage Expanding in Closing High Voltage Capacitor (고압 커패시터 투입시 전압확대에 따른 사고 사례 연구)

  • Cho, Nam-Hoon;Jung, Jum-Soo;Park, Yong-Woo;Ha, Bok-Nam;Lee, Hyung-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.9
    • /
    • pp.94-102
    • /
    • 2008
  • Capacitor switching is essential for the economic operation and proper voltage control of KOREA electric utility distribution system. Voltage transients produced by capacitor switching (around 2.0 per unit at substation and 2.5 or less per unit at customer site, and lasting less then 1[ms]) do not have the magnitude or duration to interfere with the operation of computers, but they do disrupt the operation of adjustable speed drivers. The result of our research, ASD manufacturers should learn from the computer industry and design products that will operate satisfactory In the electrical envelopment in which they will be placed. In this case history, the inductors on the input to ADSs in order to prevent nuisance tripping from capacitor switching(and other causes within the apartment) proved to be an effective, low-cost solution.

Design of the Robust Active Power Filter under the Unbalanced and Distorted Source Voltages in Three-phase Four-wire Systems (전원전압의 불평형 및 왜곡에 강인한 3상 4선식 전력용 능동 필터의 설계)

  • Min Joon-Ki;Kim HyoSung;Choi Jaeho;Kim Kyung-Hwan
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.9 no.5
    • /
    • pp.420-429
    • /
    • 2004
  • This paper proposes a novel current control strategy on active power filters using PQR instantaneous power theory which can compensate the line current harmonics and the neutral line current under the unbalanced and/or distorted source conditions in three-phase four-wire systems. The characteristics of the inverter ac filters are analyzed and a novel digital controller are proposed to overcome the inherent time delay problem in digital controllers with designed control gain in this paper. The proposed current control method is based on a sinusoidal PWM for fully-digital implementation compared with a conventional hysteresis PWM. PSiM simulation results verify the good performance of the proposed current control strategy on shunt type APFs.

Islanding Detection Method for Grid-connected PV System using Automatic Phase-shift (자동 위상 이동을 이용한 계통 연계형 태양광 발전 시스템의 고립운전 검출기법)

  • Yun, Jung-Hyeok;Choi, Jong-Woo;So, Jung-Hun;Yu, Gwon-Jong;Kim, Heung-Geun
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.12 no.2
    • /
    • pp.107-114
    • /
    • 2007
  • Islanding of PV systems occurs when the utility grid is removed but the PV systems continue to operate and provide power to local loads. Islanding is one of the serious problems in an electric power system connected with dispersed power sources. This can present safety hazards and the possibility of damage to other electric equipments. In the passive method, the voltage and frequency of PCC are measured and it determines islanding phenomena if their values excess the allowed limits. If the real and reactive power of RLC load and those of the PV system are closely matched, islanding phenomena can't be detected by the passive methods. Several active methods were proposed to detect islanding operation in the region where the passive method can not detect it. The most effective method is SFS method which was suggested by Sandia National Laboratory. In this paper, a new islanding detection method using automatic phase-shift is proposed and its validity is verified through the simulation and experimental results.