Inrush Current Control of Matching Transformer for Dynamic Voltage Restorer

동적전압보상기를 위한 정합 변압기의 돌입전류 제어

  • 서일동 (숭실대 전기공학과) ;
  • 전희종 (숭실대 전기공학부) ;
  • 손진근 (경원전문대학 전기제어시스템과)
  • Published : 2006.08.01

Abstract

This paper proposes an inrush current control technique of matching transformer for configuration of dynamic voltage restorer(DVR). The DVR system consist of PWM inverter to inject arbitrary voltage, LC low pass filter as harmonic eliminator and matching transformer for isolation. However, the matching transformer has an excess of inrush current by magnetic flux saturation in the core. Due to this inrush current, the rating of matching transformers is double for needed nominal rating for protection of DVR. Therefore, in this paper, the modeling method of magnetic flux saturation is used to analyze a magnitude of inrush current, and additional current controller is used for PWM inverter output regulation. Simulation and experimental results are provided to demonstrate the validity of the proposed control method.

본 논문에서는 동적전압보상기 (DVR)를 구성하기 위한 정합 변압기의 돌입전류 제어기법을 제안하였다. DVR 시스템은 배전계통에서 발생하는 순시적 전압강하를 보상하기 위한 직렬전압 주입장치로서, 임의의 전압을 생성하는 PWM 인버터와 전압 평활용 LC 수동필터 및 절연을 위한 정합 변압기 등으로 구성된다. 그러나 정합 변압기의 사용은 변압기내에서 자속 포화현상에 의하여 정격의 수배에 달하는 돌입전류가 발생하여 시스템의 절연파괴를 초래하고 이 때문에 변압기의 정격용량을 2 배 정도로 초과하여 사용하게 한다. 따라서 본 연구에서는 정합 변압기의 자속 포화현상에 따른 돌입전류의 크기를 분석할 수 있는 새로운 모델링 분석기법 및 돌입전류의 크기를 제한하는 자화전류 제어기법을 제안하였다. 모의실험 및 실험을 통하여 제안된 DVR 제어기법의 타당성을 입증하였다.

Keywords

References

  1. P. Wang, N. Jenkins, and M. H. J. Bollen, 'Experimental investigation of voltage sag mitigation by an advanced static var compensator,' IEEE Trans.l Power Delivery, vol. 13, pp. 1461-1467, Oct. 1998 https://doi.org/10.1109/61.714772
  2. M. F. Alves, T. N. Ribeiro, 'Voltage sag: an overview of IEC and IEEE standards and application criteria,' Proceedings of IEEE Conference on Transmission and Distribution, 1999, Vol. 2, pp. 585-589
  3. S. Nilsson, 'Special application considerations for custom power systems,' in Proc. IEEE PES Winter Meeting, New York, Jan/Feb. 31/04, 1999, pp. 1127-1130
  4. Ying-Yu, Shin-Liang Jung, 'Full Control of a PWM DC-AC Converter for AC Voltage Regulation,' IEEE Transactions on Aerospace and Electronic System, Vol. 34, No. 4, October 1998, pp. 1218-1226 https://doi.org/10.1109/7.722709
  5. R. Buxton, 'Protection from voltage dips with the dynamic voltage restorer,' in IEE Half Day Colloquium on Dynamic Voltage Restorer, London, U.K., 1998, Dig. No. 1998/189
  6. Trutt, F. C., Erdelyi, E. A., and Hopkins, R. E., 'Representation of the Magnetization Characteristic of DC Machines for Computer Use,' IEEE Trans. on Power Apparatus and Systems, Vol. 87, No. 3, 1968, pp.665-669 https://doi.org/10.1109/TPAS.1968.292178
  7. D. Mahinda Vilathgamuwa, H. M. Wijekoon, 'Control and Analysis of a New Dynamic Voltage Restorer Circuit Topology for Mitigating Long Duration Voltage Sags,' Industry Applications Conference, 2002. 37th IAS Annual Meeting. Conference Record of the , Volume 2, 13-18 Oct. 2002, pp. 1105-1112
  8. 손진근 외, '개선된 전압 Sag 및 위상 검출기법에 의한 동적전압보상시스템,' 전력전자학술대회 논문집, pp. 185-188. 2005. 7
  9. 손진근 외, 'THD를 고려한 DVR 시스템의 LC필터 설계,' 전력전자학술대회 논문집, pp. 490-493. 2005. 7
  10. 김희중 외, '전력품질 향상기기의 실증시험을 위한 2 MVA SSFG(Sag Swell Flicker Generator) 개발,' 전력전자학회 논문지, 1229-2214, 제10권 제6호, pp. 626-633. 2005