• Title/Summary/Keyword: 무정전 전원 장치

Search Result 89, Processing Time 0.022 seconds

10KVA Series-Parallel compensated UPS (10KVA 급 직병렬 보상형 무정전 전원 장치)

  • Jeon, Seong-Jeub;Cho, Gyu-Hyeong
    • Proceedings of the KIEE Conference
    • /
    • 2000.07b
    • /
    • pp.1083-1086
    • /
    • 2000
  • In this paper a development of 10KVA series-parallel compensated UPS is shown, which has high input power factor and sinusoidal output voltage regulation capability. Compared to conventional cascaded UPS, the size can be reduced significantly with high quality input and output waveforms. The front converter and the main inverter can be considered decoupled, hence the front converter and the main inverter can be designed independent of each other. In this paper, analysis and experimental results for an 10 KVA prototype are presented.

  • PDF

Design of Odd Harmonic Repetitive Controller for Uninterruptible Power Supply (무정전 전원장치를 위한 홀수고조파 반복제어기의 설계)

  • Yoon, Chun-gi;Cho, Younghoon;Lim, Seung-beom
    • Proceedings of the KIPE Conference
    • /
    • 2015.11a
    • /
    • pp.147-148
    • /
    • 2015
  • This paper presents an odd harmonic repetitive controller for single-phase UPS inverters. The proposed repetitive controller achieves the low output voltage THD and reduces the steady-state error by eliminating odd harmonic distortions caused by nonlinear and unbalanced loads. The proposed control scheme is verified through experiment using a 5kW single-phase T-type inverter.

  • PDF

A Development of DC Uninterruptible Power Supply (직류 무정전 전원공급 장치 개발)

  • Han, Tae Hee;Lee, Ji Heon;Kim, Ji Hong;Kim, Hee Jung
    • Proceedings of the KIPE Conference
    • /
    • 2020.08a
    • /
    • pp.267-268
    • /
    • 2020
  • 최근 화석연료의 고갈과 환경에 대한 우려로 고효율 에너지 변환 연구가 진행되고 있으며, 최근 이러한 Trend에 맞춰서 국내외 적으로 전력을 효율적으로 사용하기 위해 DC 배전에 대한 연구가 활발하게 이루어지고 있다. 본 논문에서는 DC배전의 추세에 맞춰, 고품질과 고효율의 에너지를 DC 부하에 공급 할 수 있는 DC UPS에 대한 연구 개발을 수행하였다.

  • PDF

A Study on Synchronized AC Power Source Voltage Regulator of Voltage Fed Inverter using a Photovoltatic effect (PV효과를 이용한 전압형 인버어터 전원동기 전압 조정기에 관한 연구)

  • Hwang, Lak-Hoon
    • Journal of the Korean Institute of Telematics and Electronics S
    • /
    • v.35S no.8
    • /
    • pp.120-129
    • /
    • 1998
  • In this paper represented uninterruptible power sypply(UPS) equipment maintaining constant output voltage, using a pulse width modulation(PWM) voltage fed inverter, as power source disconnection, voltage variation and output current variation with load variation. This system is driven by being synchronized voltage fed inverter and AC source, and in the steady state of power source charge battery connected to DC side with solar cell using a Photovoltaic (PV) that it was so called constant voltage charge. In addition, better output waveform was generated because of PWM(pulse width Modulation) method, and it was Proved to test by experiment maintained constant output voltage regardless of AC source disconnection, load variation, and voltage variation of AC power source.

  • PDF

Characteristic of VSI Driven by Source Synchronous Type for the Utility Interactive using a Photovoltaic Generation for the LED Luminaire Emergency Exit Sign Operation (LED 비상 유도등 동작을 위한 태양광발전 계통연계 전원동기 방식의 전압형 인버터 구동 특성)

  • Hwang, Lark-Hoon;Na, Yong-Ju
    • Journal of Advanced Navigation Technology
    • /
    • v.22 no.5
    • /
    • pp.420-428
    • /
    • 2018
  • In this paper, represented uninterruptible power supply (UPS) equipment maintaining constant output voltage, the proposes a photovoltaic system constructed with a step up boosting chopper and single phase pulse width modulation (PWM) voltage source inverter. as power source disconnection, voltage variation and output current variation with load variation. This system is driven by being synchronized voltage fed inverter and AC source, and in the steady state of power source charge battery connected to DC side with solar cell using a Photovoltaic that it was so called constant voltage charge. It can be results of saving electric power, and through a normal operation of energy storage system (ESS), the system operated the LED a calling on signal changes at the airport in an efficient manner. In addition, better output waveform was generated because of PWM method, and it was proved to test by experiment maintained constant output voltage regardless of AC source disconnection, load variation, and voltage variation of AC power source.

A Single-Phase Buck AC-AC Power Converter for Custom Power Applications (수용가 전원 응용을 위한 단상 Buck AC-AC 전력 변환기)

  • 강정식;최남섭
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2001.05a
    • /
    • pp.427-430
    • /
    • 2001
  • Computers and automated manufacturing processes in industry are very susceptible to voltage sags and surges. The need for greater power reliability makes the end-users to use the uninterruptible power supply and other electronic power conditioning means to maintain the stable voltage. In this paper, a single-phase buck ac-ac converter for Custom Power Applications is presented. The presented converter uses IGBT's as switching module and maintains the stable voltage through PWM technology in spite of the input voltage sags and load rejections. In this paper, the operation characteristics of the power converter at steady state are illustrated using PSPICE simulations.

  • PDF

Improvement of Output Waveforms in UPS Using the Discrete Control Technique (이산제어기법을 이용한 UPS의 출력파형 개선)

  • 김대곤;박해암;오금곤;조금배;백형래;김영동
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.11 no.6
    • /
    • pp.57-63
    • /
    • 1997
  • Uninterruptible power supply(UPS) system should provide a good quality and stable power supply no matter what the condition of the raw mains. And when the mains fails, it must provide uninterrupted power to the load for a specified time. In this paper. discrete control system is introduced to improve output waveforms of UPS. This technique can be obtained output voltage by discrete data of synchronous control and voltage control to various loac. And then, the compact and light UPS can be realized by remove of the analog circuit and simulation and ezperinentation were performed with this control algofihtm. The experiment result show the effectiveness of proposed UPS system uwing the discrete control techjique.

  • PDF

Design element analysis for IGBT Gate driver (IGBT 게이트 드라이버 설계요소 분석)

  • Jeong, Jinyong;Cha, Hanju
    • Proceedings of the KIPE Conference
    • /
    • 2013.07a
    • /
    • pp.455-456
    • /
    • 2013
  • 모터 가변속 구동장치나 계통연계 전력변환 장치, 무정전 전원장치(UPS)등 스위칭 주파수가 수 ~ 20kHz 정도의 중용량 장치에 IGBT가 주로 사용된다. 최근에는 소용량 가전제품부터 대용량의 전철의 모터 구동장치 등 다양한 전기기기에 IGBT가 사용되고 있다. IGBT의 성능은 게이트 드라이브 회로에 의해 결정되며, 스위칭 특성, 파형 컨트롤과도 밀접한 관련이 있다. 본 논문에서는 IGBT의 안정적인 스위칭 동작에 영향을 끼치는 요인과 Turn-on 시퀀스를 분석하였고 IGBT의 물리적 특성을 고려하여 불안정한 게이트-에미터 전압을 안정화시킬 수 있는 게이트 드라이버의 설계 요소에 대하여 고찰하였다.

  • PDF

Improved DC-DC Bidirectional Converter (개선된 DC-DC 양방향 컨버터)

  • Kim, Seong-Hwan;Hur, Jae-Jung;Jeong, Bum-Dong;Yoon, Kyoung-Kuk
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.41 no.1
    • /
    • pp.76-82
    • /
    • 2017
  • Since the introduction of electronically controlled engines and electric propulsion ships, the need for an uninterruptible power supply for emergency power supply devices that use batteries has gained importance. The bidirectional converter in such emergency power supply devices is a crucial component. This paper proposes, a topology for an improved DC-DC bidirectional converter that is characterized by a high voltage conversion ratio and low voltage stress of switches. To confirm the performance of the converter, a computer simulation was executed with PSIM software. The conversion ratio of the proposed converter was found to be four times higher than the conventional boost converter in step-up mode and one-fourth that of the conventional buck converter in step-down mode, and the voltage stress of the switches was one-fourth of the high-side voltage. Moreover, the proposed converter was confirmed to be able to distribute equal currents between two interleaved modules without using any extra current-sharing control method because of the charge balance of its blocking capacitors.

Design of the Fuel Cell Powered Line-Interactive UPS System (연료전지 시스템을 이용한 Line-Interactive 방식의 무정전 전원 공급 장치의 설계)

  • Choi, Woo-Jin;Jeon, Hee-Jong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.18 no.6
    • /
    • pp.205-212
    • /
    • 2004
  • In this paper the design of a 1-[KVA] fuel cell powered line-interactive UPS system employing modular (fuel cell & DC/DC converter) blocks is proposed. The proposed system employs the two fuel cell modules along with suitable DC/DC converters and these modules share the DC-Link of the DC/AC inverter. A supercapacitor module is also employed to compensate for the instantaneous power fluctuations and to overcome the slow dynamics of the fuel processor. The energy stored in the supercapacitor can also be utilized to handle the overload conditions for a short time period. Due to the absence of batteries, the system satisfies the demand for an environmentally friendly and dean source of the energy. A complete design example illustrating the amount of hydrogen storage required for 1hr power outage, and sizing of supercacpacitor for transient load demand is presented for a 1-[KVA] UPS.