• Title/Summary/Keyword: 리튬브로마이드

Search Result 44, Processing Time 0.025 seconds

A Study on the Performance Characteristics of an Absorption Chiller for Variable Cooling Water Flow Rate at Partial Load Conditions (흡수식 냉온수기의 부분부하에 따른 냉각수 변유량시 성능특성에 관한 연구)

  • 박찬우;조현철;강용태
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.16 no.1
    • /
    • pp.26-33
    • /
    • 2004
  • In general, an absorption chiller or heat pump is operated under the constant cooling water flow rate condition even though the system works with a partial load. The objective of this paper is to study the effect of the cooling water flow rates and the temperature of cooling water on the system performance to find the energy saving methode for the partial load operation of the double effect $H_2O$/LiBr absorption chiller. It is found that the performance of the system is sensitive to the temperature of cooling water than the cooling water flow rate, so the decrease of the performance due to reducing the cooling water flow rate can be overcome with the reduction of the cooling water temperature by 1$^{\circ}C$. The flow rate of the cooling water flow rate ranges from 50% to 100% of the flow rate at normal conditions with a partial load. It is also found that the operation cost of the cooling water pump and the cooling tower can be reduced by 23%.

Falling Film Heat Transfer on a Horizontal Single Tube (수평단관 상의 유하액막 열전달)

  • 김동관;김무환
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.7
    • /
    • pp.642-648
    • /
    • 2000
  • Falling film heat transfer analyses with aqueous lithium bromide solution were peformed to investigate the transfer characteristics of the copper tubes. Finned(knurled) tube and a smooth tube were selected as test specimens. Averaged generation fluxes of water and the heat transfer performances(heat flux, heat transfer coefficient) were obtained. The results of this work were compared with the data reported previously. As the film flow rate of the solution increased, the generation fluxes of water decreased for both tubes. The reason is estimated by the fact that the heat transfer resistance with the film thickness increased as the film flow rate increased. The effect of the enlarged surface area at the knurled tube was supposed to be dominant at a small flow rate. The generation fluxes of water increased with the increasing degree of tube wall superheat. Nucleate boiling is supposed to occur at a wall superheat of 20 K for a smooth tube, and at 10 K for a knurled tube. The heat transfer performance of the falling film was superior to pool boiling at a low wall superheat below 10 K for both tubes tested. The knurled tube geometry showed good performance than the smooth tube, and the increased performance was mainly came from the effect of the increased heating surface area.

  • PDF

Experimental Correlation of Wettability for Micro-scale Hatched Tubes (미소해칭 전열관의 젖음률에 대한 실험적 상관식)

  • 김진경;박찬우;이경엽;강용태
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.15 no.1
    • /
    • pp.19-24
    • /
    • 2003
  • The objectives of this paper are to develop a new method of wettability mea-surement and to study the effect of surface roughness on the wettability in a $H_2O$/LiBr falling film absorber. Two absorber tubes with micro-scale roughness and a bare tube are tested in a falling film absorber installed in a test rig. Inlet solution temperature, concentration and mass flow rate are considered as key parameters. A new method is proposed to estimate the wettability of a tube by measuring a minimum mass flow rate to wet the tube completely. The wettability for the structured surfaces was higher than that for the bare tube. The wettability decreased linearly along the vertical location. The wettability increased with increasing the solution temperature and the solution mass flow rate. The experimental correlations of the wettability for the bare and the micro-hatched tubes were developed with error bands of$\pm20%\;and\;\pm10%$, respectively. This work can be used in the design of absorbers with micro-scale roughness.

An Experimental Study on Flow and Heat / Mass Transfer Characteristics of $LiBr-H_2O$ Solution Flowing over a Cooled Horizontal Tube (수평 냉각관 외부를 흘러내리는 $LiBr-H_2O$ 수용액의 유동 및 열/물질 전달 특성에 관한 실험적 연구)

  • Seal, Sin-Su;Lee, Sang-Yang
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.24 no.8
    • /
    • pp.1085-1096
    • /
    • 2000
  • An experimental study was performed to examine the heat and mass transfer characteristics of $LiBr-H_2O$ solution flowing over a single horizontal tube with the water vapor absorption. Effects of the flow rate and the temperature of the solution at the top of the tube, the absorber pressure and the drainage pattern were considered. The absorption rate depends highly on the absorber pressure at the low flow rate condition while on the solution inlet temperature at the high flow rate condition. Also, when the flow rate is low, the absorption performance with the sheet flow drainage appeared to be higher than that with the dripping/jet drainage. However, at the high flow rate condition, the case became reversed. The liquid film became wavy with the higher absorption rate. The waves were more probable to form with the lower flow rate and temperature of the solution, and with the higher absorber pressure.

Experimental Study on Cavitation Instability of a Solution Pump Inducer in an Absorption Chiller-Heater (흡수식 냉온수기내 용액펌프 Inducer의 Cavitation 불안정성에 대한 실험적 연구)

  • Seo, Min;Lee, Kyung-Hoon;Kang, Shin-Hyung
    • Proceedings of the KSME Conference
    • /
    • 2008.11b
    • /
    • pp.2434-2439
    • /
    • 2008
  • This paper was studied on the cavitation instability of a Solution Pump Inducer in an absorption chiller-heater. Inlet pressure of LiBr and rotational speed at nominal mode are 2,800 Pa and 3,500 rpm respectively. Due to the marginal operation of available NPSH, the cavitation performance of the inducer is critical for the stable operation without the deterioration of head performance. In the study, cavitation performance and its mode of instability was investigated experimentally. Water was used as the working fluid and the test inducer was scaled up as 1.75 times for detail measurements and flow visualization. Inlet pressure was controlled by a vacuum pump. This research focused on types of cavitation instability and phenomena to investigate the possibility of harmful damage due to cavitation instability. Casing wall pressure and instantaneous inlet pressure was measured to observe the unsteady flow characteristics. Through the visualization and spectrum analysis of pressure, the occurrence region and intensity of asymmetric cavitation and cavitation surge are analyzed in the test inducer.

  • PDF

Heat and mass transfer characteristics in a vertical absorber (수직형 흡수기내 열 및 물질 전달 특성)

  • 서정훈;조금남;최기봉
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.11 no.6
    • /
    • pp.835-845
    • /
    • 1999
  • The objective of the present study was to investigate heat and mass transfer characteristics in a vertical falling film type absorber using LiBr-$H_2O$ solution with 6owt%. The experimental apparatus consisted of an absorber with inner diameter of 17.2 mm and length of 1150mm, a generator, an evaporator/condenser, a solution tank, a sampling trap etc. The parameters were solution temperature of 45 and $50^{\circ}C$, coolant temperature of 30 and $35^{\circ}C$, and film Reynolds numbers from 50 to 150. Pressure drop in the absorber increased as solution and coolant temperatures decreased. Pressure drop in the absorber increased up to the film Reynolds number of 90, and then decreased at the further increase of the Reynolds number above 90. The maximum absorption mass flux observed at the film Reynolds number of 90. Absorption mass flukes increased as coolant temperature decreased. Absorption mass fluxes and heat transfer coefficients under subcooled condition were larger than those under superheated condition. Heat transfer coefficients were affected by solution temperature more than coolant temperature. The maximum absorption effectiveness under the subcooled condition was 23% for coolant temperature of $30^{\circ}C$ and 31% for coolant temperature of $35^{\circ}C$ under the present experimental conditions.

  • PDF

A study on the Characteristics of the High Efficiency absorption Chiller by Heat Recovering from Condenser (응축기 배열 회수에 의한 흡수식 냉동기의 고효율화에 관한 연구)

  • Park, Chan-Woo
    • Proceedings of the SAREK Conference
    • /
    • 2006.06a
    • /
    • pp.46-51
    • /
    • 2006
  • In order to utilize the refrigerants condensation heat of condenser on the absorption chiller system, the solution cooling condenser(SCC) were proposed, which weak solution of absorber outlet use as a cooling water. As the UA of the solution cooling condenser increased, increasement of COP is about maximum 0.09 in occasion of single effect and is about maximum 0.08 in occasion of double effect series flow. In the case of heat exchanger efficiency is about 0.85, it's increments are 0.08 and 0.072, each. And solution cooling condenser is a more effective device in the single effect absorption system more than double effect system for the principle of operation. In order to increases the heat of solution cooling condenser, if reduce the flow rate of cooling water or the value of UA, it makes COP increase a little, but it brought COP decrease because of increasing the pressure of system.

  • PDF

Comparison Between Two Solar Absorption Cooling System Using Single Effect and Single Effect/Double Lift Cycle (일중효용 사이클과 일중효용/2단승온 사이클을 이용한 태양열 흡수식 냉방시스템의 비교)

  • 정시영;이상수;조광운;백남춘
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.3
    • /
    • pp.267-276
    • /
    • 2000
  • A numerical study has been carried out to find out the optimal design condition of a solar absorption cooling system. The system was composed of solar collectors and an absorption chiller with LiBr/water The System performance with commercial single effect(SE) cycle and a new single effect/double lift(SE/DL) cycle utilizing low temperature hot water was calculated and compared. It was found that the required solar collector area grew exponentially as the overall heat loss coefficient of solar collectors increased. For instance, the required area for cooling capacity of 1 USRT was $17m^2$ if heat loss coefficient was 4 W/$m^2\;cdot\;K$. If heat loss coefficient was doubled($8\;W/m^2\;cdot\;$K), the required collector area was increased by 6 times($100m^2$) .It was also found that the SE-cycle as the heat loss coefficient of solar collectors increased. Generally, a SE/DL-cycle seems to be more advantageous than a SE-cycle if loss coefficient of solar collector is greater than 4 W/$m^2\;cdot\;K$.

  • PDF

A Numerical Study on Heat and Mass Transfer in a Falling Film of Vertical Plate Absorber Cooled by Air (공랭형 수직평판 흡수기 액막에서의 열 및 물질전달에 관한 수치적 연구)

  • 김선창;오명도;이재헌
    • Transactions of the Korean Society of Mechanical Engineers
    • /
    • v.19 no.4
    • /
    • pp.1071-1082
    • /
    • 1995
  • Numerical analyses have been performed to obtain the absorption heat and mass transfer coefficients and the absorption mass flux from a falling film of the LiBr aqueous solution which is cooled by cooling air. Heat flux at the wall is specified in terms of the heat transfer coefficient of cooling air and the cooling air temperature. Effects of operating conditions, such as the heat transfer coefficient, the cooling air temperature, the system pressure and the solution inlet concentration have been investigated in view of the local absorption mass flux and the total mass transfer rate. Effects of film thickness and film Reynolds number on the heat and mass transfer coefficients have been also estimated. Analyses for the constant wall temperature condition have been also carried out to examine the reliability of present numerical method by comparing with previous investigations.

Analysis of LiBr-H$_{2}$O Film Absorption on a Horizontal Tube (수평원관상의 LiBr-H$_{2}$O 액막흡수현상 해석)

  • Park, Il-Seok;Choe, Do-Hyeong
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.20 no.2
    • /
    • pp.670-679
    • /
    • 1996
  • A numerical study for vapor absorption into LiBr-H$_{2}$O solution film flowing over horizontal circular tubes has been carried out. The momentum, energy and diffusion equations, which are parabolized by the boundary- layer approximation, are solved simultaneously for various mass-flow rates and inlet conditions. The results for the velocity, temperature and concentration fields, as well as the heat and mass flux at the free surface are presented. The effects of inlet conditions, i.e., flow rate, temperature and concentration, on the absorption process are also examined and discussed.