• Title/Summary/Keyword: 대공간 화재

Search Result 21, Processing Time 0.034 seconds

Optimization for Ventilation Capacity of Large Enclosure Considering Fire Load (화재하중을 고려한 대공간 제배연 용량 최적화 연구)

  • Ahn, Chan-Sol;Kim, A-Ram
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2011.11a
    • /
    • pp.478-481
    • /
    • 2011
  • This study is intended to evaluate and optimize the characteristics of smoke spreading and the appropriateness of evacuation time extended by operation of smoke control system during fire within the underground space of the building structured in compliance with the smoke control system performance criteria from the local fire safety standard, which has been currently applied to the buildings in Korea. Using the heat release per unit weight of the combustibles, a numerical analysis both in case of smoke control system in operation and the system not in operation was carried out at the several different shopping malls. From the viewpoint of securing the evacuation time, the results were compared in an attempt to assess the appropriateness of the fire safety criteria.

  • PDF

A Study on Smoke Filling in a Large Space (대공간에서의 연기축적에 관한 연구)

  • 김진곤;윤명오;한용식;김명배;김충익;유홍선;김상욱
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1998.11a
    • /
    • pp.53-60
    • /
    • 1998
  • In this study, smoke filling behaviors in a large space were investigated. For experimental study, thermocouples were used to measure the temperature of the hot gases layer and also to determine the smoke layer depth. Height markers were also hung from the roof so that observers could visibly assess the smoke layer depth. Ethanol was used as fuel. The smoke filling times were predicted with zone model and field model and numerical results were compared with experimental data. Good results were obtained.

  • PDF

Influence of the Fire on Emergency Evacuation Support System (대공간용 비상피난지원 시스템에 화재가 미치는 영향 분석)

  • Kim, JiTae;Sung, Kun Hyuk;Park, Won Hee;Lee, Duck Hee;Woo, Jun You;Ro, Kyoung-Chul
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.19 no.5
    • /
    • pp.626-631
    • /
    • 2018
  • An emergency evacuation support system is used to maintain evacuation routes by pressurizing a space inside screens. In cases of fire, it is important to understand the thermal distributions in the tunnel for preventing system failure. In this study, we numerically investigated the effect of fire on an emergency evacuation support system in a large fabric store with some fire scenarios with different combustibles. The critical temperature for system failures was assumed to be $200^{\circ}C$. As a result, the highest temperature was predicted in the ceiling part due to the effect of a ceiling jet, and the fire safety of the screen was secured at distances of 20 to 30 m according to the heat release rate. To prevent the inflow of smoke into the system, it is necessary to maintain more than 5 Pa if positive pressure inside the smoke screen. The results of this study could be useful for designing an emergency evacuation support system.

A Study on the Smoke control Design parameter of Large Volume space by Fire Dynamic Simulation (화재 시뮬레이션(FDS)을 이용한 대형공간의 제연 설계인자에 관한 연구)

  • Choi, Sang-Gon
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.19 no.11
    • /
    • pp.237-243
    • /
    • 2018
  • Performance-oriented design has been introduced in fire protection design, and various efforts have been made to minimize the damage caused by fire in the design stage. We conducted a study to provide information for reasonable design factors using a Fire Dynamic Simulation code provided by the NIST on boundary width and amount of supply. This paper shows that using a living-room air-supply system in a large space and dividing the space by a ventilation boundary are the two factors that are considered to have the greatest influence on the design of the living room ventilation. The results show that for performance-based design, the width of the ventilation boundary is designed to be the maximum limit in the initial design. It is judged that reasonable air volume determination should be made through various methods.

Numerical Study on the Definition of the Exhaust Effectiveness of Smoke under Fire in a Large Space (대공간 화재시 배연효율 정의에 관한 수치해석적 연구)

  • Kim, Jung-Yup;Jang, Kyung Jin;Han, Hwataik
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.26 no.11
    • /
    • pp.535-540
    • /
    • 2014
  • This paper investigates the exhaust effectiveness of smoke, in the case of fire in a large atrium space. Numerical analysis was conducted to simulate transient fire growth in a test room, modeled by the Murcia atrium fire test. Various indices representing the exhaust performance of the exhaust system were obtained, such as the height of the smoke layer, and the instantaneous and accumulative capture efficiency of the smoke. The residual life time of smoke from the fire was also obtained, by injecting tracer gases at the fire location, depending on the airflow rate, and the location of the exhausts. The capture efficiency based on smoke concentration at the exhausts exhibits how much smoke can be removed by the exhaust system; whereas, the exhaust effectiveness based on residual life time indicates how rapidly the smoke can reach the exhaust locations, before being exhausted. The definitions and meanings of the indices to be used in representing the exhaust performance of a smoke exhaust system installed in a large space are discussed.

Derivations of Positive Pressure Condition for Development of Foldable Safe Pathway in Railway Tunnel Fires (철도터널화재용 접이식 대피통로 개발을 위한 양압 조건 도출)

  • Kim, JiTae;Ro, Kyoungchul
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.20 no.1
    • /
    • pp.284-289
    • /
    • 2019
  • The Korea Foldable safe pathway system is an evacuation support system to get temporary evacuation route in railway tunnel and large space fires. A prevention smoke screen is unfolded in fires and it is needed to prevent heat and smoke from fire source. Therefore, ventilation system for positive pressure condition is equipped with foldable safe pathway system. Numerical analyses of temperature and pressure distribution with distance from fire source were performed considering fire scenario of new train vehicle. The smoke temperatures did not exceed $200^{\circ}C$ that distance from the fire source was more than 20 m and smoke pressure was reduced with distance from fire source. Maximum smoke pressure was 14 Pa and average pressure was 6 Pa in position of prevention smoke screen. As results, to install foldable safe pathway system, ventilation system is need to maintain 6 Pa positive pressure condition.

A study on the performance standards of autonomous fire extinguishing system (자율형 초동진압용 소화체계 성능기준에 관한 연구)

  • Kim, Namkyun;Kim, Hwiseong;Park, Jinouk;Park, Byoungjik;Kim, Yangkyun;Yoo, Yongho
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.22 no.6
    • /
    • pp.655-667
    • /
    • 2020
  • The final purpose of this study is to present the performance evaluation criteria (draft) of the autonomous initial suppression digestion system. In this study, in order to present the performance standards for the autonomous initial suppression fire extinguishing agent system currently in the development stage, the legal performance standards for fire extinguishing equipment currently applied to domestic buildings and the performance standards of similar overseas previous research were compared and analyzed. In addition, based on this, the minimum performance standards required for the digestive system for autonomous initial suppression were presented. When the performance of the digestive system for autonomous initial suppression is evaluated based on the results of this study and applied, it is judged that it is possible to respond more quickly in the situation of fire.

Flame Resistance Performance of Glass Fiber and Polyester Fiber Architectural Membranes (건축용 유리섬유 및 폴리에스테르섬유 막재의 난연특성)

  • Kim, JiHyeon;Song, Hun
    • Fire Science and Engineering
    • /
    • v.30 no.1
    • /
    • pp.17-23
    • /
    • 2016
  • Membrane structures can be used to create diverse lightweight structural forms using ductile membranes made of coated fabric. Using membrane structures, it is possible to construct large covered spaces relatively quickly and economically, and hence, they are being applied within various applications. The structures are light-weight, transparent, flexible in their application, economical and easy to maintain, and as such, their usage is being expanded. However, despite their prevalence, the standard for membrane material performance in terms of fire safety is still inadequate, and the development of membrane materials with excellent flame resistance performance is being demanded. This study determined flame resistance performance of architectural membranes, including PTFE, PVDF, PVF and ETFE film membranes, through flammability testing and incombustibility testing.

A Study on Measures to Improve Smoke Control Performance in Case of Fire in a Clean room as an LCD Manufacturing Process (LCD 제조공정 클린룸의 화재시 CFD를 이용한 제연성능 개선대책에 관한 연구)

  • Son, Bong-Sei;Jang, Chan-Hee
    • Fire Science and Engineering
    • /
    • v.26 no.5
    • /
    • pp.41-47
    • /
    • 2012
  • As a core process in the manufacture of state-of-the-art industrial technologies such as semiconductor and LCD, a clean room is the most important process which can affect the performance and quality of products drastically. Nevertheless, scientific research on comprehensive safety measures from a fire protection standpoint is not being carried out in Korea. This study aims to derive measures to improve smoke control systems by identifying performance and problems of smoke systems installed in clean rooms as an LCD manufacturing process and analyzing fire and evacuation simulations considering several scenarios. As a result of analysis of fires and smoke in a clean roomas an LCD manufacturing process, it is found to be necessary to stop air handling units through interlocking in case of a fire and exhaust smoke out of the room through the top of FAB in consideration of buoyancy of smoke. It is also found to be necessary to install quick response sprinkler heads and accessories to accelerate the response time, because the heat-accumulating performance of sprinkler heads decreases in this application. Despite its low density of dwelling due to the automation process, clean room is characterized by an array of complex production equipment and working environment requiring dustproof clothes, which makes it difficult to acquire evacuation safety performance. Thus, thorough control of danger factors in processes and periodic education and training are required. It is also necessary to establish a level of domestic technologies equivalent to the level of standards of advanced countries in fire protection.