• Title/Summary/Keyword: 가스절연

Search Result 482, Processing Time 0.035 seconds

Development of External UHF PD Sensor for the Detection of Partial Discharge in $SF_6$ Gas-insulated Switchgear (가스절연 개폐장치의 PD검출용 UHF 대역 외장형 센서 제작 및 감도 특성)

  • Lee, Chang-R.;Hong, C.Y.;Choi, B.H.;Yoon, J.H.;Nam, G.C.;Jung, J.G.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1799-1801
    • /
    • 2004
  • We have developed the external-type PD sensors for detecting of the electromagnetic waves up to ultra high frequency (UHF) bands, propagating in various type of GIS. Sufficiently high sensitivity and accuracy for practical use were achieved for the external PD sensor. The experience at the fields and the criteria for the judgment are also discussed in detail.

  • PDF

Comparison of the characteristics related to the structure of external-type UHF UWB PD sensors for GIS (GIS용 외장형 광대역 극초단파 부분방전 센서의 구조에 따른 특성 비교)

  • Hwang, Chul-Min;Koo, Ja-Yoon;Park, Ki-Jun;Koo, Sun-Geun;Yoon, Jin-Yul;Lee, Young-Sang
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1769-1771
    • /
    • 2004
  • 가스절연 개폐장치(GIS)용 극초단파 부분 방전 측정장치에 다양하게 사용 할 수 있는 외장형 부분 방전 (PD) 센서를 제작하였다. Fat-dipole, 대수주기(log-periodic), spiral 및 log-spiral 형 패치안테나를 이용한 외장형 PD 센서의 주파수 특성과 검출감도를 기본 Dipole형 센서와 비교하였다. 제작된 센서는 170kV 단상 GIS의 스페이서에 장착하여 5 pC PD에 대한 각 센서의 주파수 특성과 감도를 측정 하였다.

  • PDF

A Study on the Interrupting Capability of the Fault Current in the E.H.V. Transmission System. (SF6 가스절연 개페장치 일)

  • 강길건
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.40 no.1
    • /
    • pp.18-23
    • /
    • 1991
  • Recently SLAMECKA suggested the mathematical dynamic arc model of the SF6 gas circuit breaker [1]. The author applied the above dynamic arc model to the E.H.V. transmission line and investigated the interrupting capability of the SF6 gas circuit breaker. In particular the Runge-Kutta-England numerical method suitable for the use in systems that involve nonlinear dynamic arc and traveling wave was used by converting the current source into the voltage source in the DOMMEL's method [2]. The successful computer resultls were obtained and it was found that the arc time constant and the second derivative of the arc conductance are closely related to the interrupting capability of the SF6 gas circuit breaker.

  • PDF

Heat Transfer and Pressure Drop Characteristics of Heat Exchanger for a Gas-insulated Transformer (가스절연 변압기용 열교환기의 열전달 및 압력손실 특성 연구)

  • Ham, Jin-Ki;Lee, Joon-Yeob;Kim, Young-Ki;Song, Seok-Hyun
    • Proceedings of the KSME Conference
    • /
    • 2004.11a
    • /
    • pp.1046-1051
    • /
    • 2004
  • A plate-fin-tube heat exchanger used for a $SF_{6}$ gas-insulated transformer is extremely important since the dissipation of the heat generated from inside coils has a significant effect on the performance as well as the durability of the transformer. The heat exchanger consists of corrugated plate fins and staggered array tube bundles for coolant. In order to find out heat transfer and pressure drop characteristics, series of numerical analyses for plate fins with enhanced surface geometries were conducted. Based on the results of the numerical analyses, an improved model of the plate fin has been proposed.

  • PDF

The Characteristic Evaluations of Oxygen Gas Assisted Dry Micro Electrical Discharge Machining (고압 $O_2$ 가스를 이용한 기체 미세방전가공의 특성 평가)

  • Yoo B.H.;Min B.K.;Lee S.J.
    • Proceedings of the Korean Society of Precision Engineering Conference
    • /
    • 2005.06a
    • /
    • pp.1571-1574
    • /
    • 2005
  • Generally, the kerosene or the deionized water has been used for dielectric fluid in the electrical discharge machining. The spark occurs when the voltage is over the breakdown voltage and induces high temperature. In this study, the Oxygen gas is used as the dielectric. The voltage behavior in the dry Micro Electrical discharge machining is compared with that of the conventional Micro Electrical discharge machining. The dry Micro EDM has some advantages. The electrode wear isvery smaller than that of the conventional Micro EDM. The contamination in the dry Micro EDM can be drastically reduced comparing to that of the conventional Micro EDM. The Oxygen gas can be replaced as the dielectric successfully.

  • PDF

Properties SiOF Thin Films Deposited by ECR Plasma CVD (ECR plasma CVD법에 의한 저유전율 SiOF 박막의 특성)

  • Lee, Seok-Hyeong;O, Gyeong-Hui
    • Korean Journal of Materials Research
    • /
    • v.7 no.10
    • /
    • pp.851-855
    • /
    • 1997
  • 본 실험에서는 저유전율 층간절연물질로서 SiOF박막을 ECR plasma CVD를 이용하여 증착하였다. 또한 증착시에 발생시킨 플라즈마의 특성 분석을 위하여 Langmuir probe를 반응챔버에 부착하여 플라즈마 밀도, 마이크로파 전력은 700W, 기판온도는 30$0^{\circ}C$에서 행하였다. 증착된 SiOF 박막을 분석한 결과, 가스유량비(SiF$_{4}$/O$_{2}$)가 0.2에서 1.6으로 증가하였을 때 불소의 함량은 약 5.3at%에서 14.5at%로 증가하였으며, 굴절률은 1.501에서 1.391로 감소하였고 이는 불소 첨가에 의한 박막의 밀도감소에 의한 것으로 생각된다. 또한 박막의 유전상수는 가스유량비가 1.0(11.8qt.% F함유)일 때 3.14였다.

  • PDF

$SF_6$ Gas Insulated Transformer ($SF_6$가스절연 변압기)

  • Cho, G.J.;Cho, K.D.;Ha, Y.S.;Cho, K.B.;Noh, C.W.
    • Proceedings of the KIEE Conference
    • /
    • 1991.07a
    • /
    • pp.304-309
    • /
    • 1991
  • We introduce the trend, of several countries, to the gas insulated transformer recently coming into the spot light by the advantages of less weight, GIS-lization, low noise level and easiness to decrease environmental pollutions, and the insulating gases. the cooling media and the insulating materials used for transformer. Hereinafter, additively the design of proto type $SF_6$ gas insulated transformer (insulation, cooling), which was developed by us(HICO) from 1987. 2 through 1990. 3, the manufacturing processes(leak protection, pressure, drying of main body), the accessories, the protective system, the cooling system, the method and the results of test and the evaluation of economics compared with conventional oil-filled transformer are represented.

  • PDF

Development of 220kV 1C*2000SQ Slip-on Type EB-G Ass'y (220kV 1C*2000SQ Slip-on Type EB-G 접속재 개발)

  • Kim, Young-Tek;Kim, Hyun-Ju;Kim, Han-Hwa;Park, Jeong-Ki;Kim, Duk-Hwan;Lee, Kang-Mi
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.1612-1613
    • /
    • 2011
  • 초고압 XLPE 케이블용 접속재는 고도의 신뢰성과 안정성이 요구되며, 국내외적으로 제품 경량화, 시공 공정 단순화 등 고객의 다양한 요구가 점차 증가하는 추세이다. 당사는 220kV 1C${\times}$2000SQ XLPE 케이블 접속재인 EB-G(가스중 종단접속함)를 Slip-on Type으로 적용함으로써 고객의 요구에 맞춰 단순한 내부절연구조에서 비롯되는 전기적 특성의 안정성과 신속한 시공성을 확보하게 되었다. 본고에서는 220kV급 접속재인 가스중종단접속함(EB-G)의 설계, 개발시험에 관하여 소개하고자 한다.

  • PDF

Criterion of Risk for 25.8 kV Gas Switchgear in Underground System (25.8 kV 가스절연개폐기(지중용)의 노후도 판정방법)

  • Kim, Dong-Myung;Kwon, Tae-Ho;Jeon, Gab-Yul;Kwon, Tae-Joon
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.349_350
    • /
    • 2009
  • 가스개폐기의 고장을 예방하기 위해서는 열화상태를 진단하여 고장을 일으키기 전에 교체하는 것이 가장 바람직하다. 이를 위해서는 제품의 제조상태, 불량가능성 등 이력사항을 진단하고 활선 진단을 통한 내부 상태를 파악한 후 위험도를 평가할 필요가 있다. 본 연구에서는 국내 배전개폐기의 열화 및 수명인자를 이용하여 개폐기 고장 위험을 예측할 수 있는 기법을 제시하였다.

  • PDF

A Suggestion to Choose Location of Bellows for Gas Insulated Switchgear (가스절연 개폐장치의 벨로우즈 위치선정을 위한 제언)

  • Hwang, Kyeong-Min;Jang, Jung-Bum
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.2000_2001
    • /
    • 2009
  • 최근 옥외 변전소 형식으로 많이 채택되고 있는 Gas Insulated Switchgear(GIS) 변전설비는 라인 구조물 형태로서, 온도응력에 대한 길이방향의 변형을 수용토록 하기 위하여 GIS 곳곳에 벨로우즈가 설치되어 있다. 특히, GIS는 강재 지지대로 높은 위치에 설치되어 지진 시 지반보다 높은 가속도를 받기 때문에 벨로우즈의 설치 위치가 GIS에 영향을 줄 가능성이 크다. 따라서 본 연구에서는 다양한 경우의 민감도 해석을 통하여 벨로우즈의 위치가 GIS의 내진성능에 미치는 영향을 분석하였으며, 그 결과 최적의 벨로우즈 위치조건을 도출하였다.

  • PDF