Browse > Article

Development of The Standard Current Transformer with Wide Ratio Error and Its Application  

Kwon, Sung-Won (한국표준과학연구원 기반표준부 전자기그룹)
Jung, Jae-Kap (한국표준과학연구원 기반표준부 전자기그룹)
Lee, Sang-Hwa (한국표준과학연구원 기반표준부 전자기그룹)
Kim, Mun-Seog (한국표준과학연구원 기반표준부 전자기그룹)
Kim, Myung-Soo (한국표준과학연구원 표준보급부)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers C / v.55, no.6, 2006 , pp. 302-307 More about this Journal
Abstract
Standard current transformer(CT) with the nominal ratio errors in the range of - 10 % to + 10 % has been developed. Linearity of the CT ratio error measuring system (CT comparator) has been tested by using wide ratio error standard current transformer(WRE CT). The developed WRE CT can be used to evaluate the linearity of the CT comparator by comparing both the theoretical values and experimental values of the WRE CT. The developed method has been successfully applied for calibration and correction in the CT comparator belonging to industry.
Keywords
Current Transformer; Wide Ratio Error; Ratio Error Measuring System; Linearity; Correction;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 J.D. Ramboz, O. Petersons, 'A Calibration Service for Current Transformers', NIST Special Publication, Vol. 250(36), pp. 66, 1991
2 W. J. M. Moore, N. L. Kusters, 'Direct Reading Ratio- Error Sets for the Calibration of Current Transformers', IEEE Trans. Instrum. Meas., Vol. IM-19, No. 3, pp 161, 1970
3 R. L. Kahler, 'An Electronic Ratio Error Set for Current Transformer Calibrations', IEEE Trans. Instrum. Meas., Vol. IM-28, No. 2, pp 162, 1979
4 권성원, 정재갑, 김문석, 김규태, 류제천, '열전형 전류 변환기의 교류-직류 변환차이 자동측정시스템 개발', 한국 센서학회지, Vol. 14, No. 5, pp. 350, 2005
5 정재갑, 권성원, 김규태, 김명수, '외부부담이 전압변성기의 비오차와 위상각오차에 미치는 영향에 대한 연구', 대한전기학회지, Vol. 53C, No. 3, pp 137, 2004   과학기술학회마을
6 KSC 1706, '계기용변성기'
7 정재갑, 권성원, 이상화, 박영태, '전류변성기의 비오차와 위상각오차의 계산값과 실험값의 차에 의한 측정시스템 유용성 검증기술에 관한 연구', 대한전기학회지, Vol. 53C, No. 4, pp 213, 2004   과학기술학회마을