Degradation Diagnosis of Insulation Paper Using CO and $CO_2$ Gases in Oil Immersed Transformers  

Sun Jong-Ho (한국전기연구원)
Yi Sang-Hwa (한국전기연구원)
Kim Kwang-Hwa (한국전기연구원)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers C / v.53, no.10, 2004 , pp. 523-529 More about this Journal
Abstract
Faults of cellulosic insulations greatly affect the life span of oil immersed transformers because their performance recovery is impossible. Therefore, the reliable diagnosis technologies are needed for detection of the faults. Dissolved gas analysis technologies using CO and $CO_2$ gases have been widely used for fault diagnosis of cellulosic insulations. In this research, we described Degradation diagnosis of insulation paper CO and $CO_2$ gases in oil immersed Transformers using. We considered the distribution characteristics of CO, $CO_2$ gases' concentrations and ratios of $CO_2$/CO not only in serviced transformers but in experiments with typical fault causes such as heat, partial discharge and moisture. As result, the reliability of diagnosis results for the cellulosic insulations can be improved when the concentrations of CO, $CO_2$ and the ratio of CO/$CO_2$ satisfy each diagnosis criterion at a tim
Keywords
Oil Immersed Transformers; Gas Dissloved Analysis; Cellulosic Insulations;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 氣協同硏究會, '油中ガス分析による油入機器の保守管理', 第36券, 1980
2 H. Anetai et al., 'A Diagnosis on the Overheating Deterioration of Insulating Paper in Transformers by Gas Analysis', JIEE A Vol. 100 No. 7, pp. 409-414, 1980
3 M. Shirai et. al., 'Thermodynamical Study on the Thermal Decomposition of Insulating Oil', JIEE A Vol. 97 No. 7, pp. 331-338, 1977
4 S. Hirabayashi et. al., 'Gas Generation by Corona Discharge in Insulating Oil', Mitsubishi Report, Vol. 45, No. 8, pp. 1015-1023, 1971
5 E. J.Murphi, 'Gases Evolved by the Thermal Decomposition of Paper', Conference on Insulation, April 1943
6 H. Tsukioka et al., 'Study on Gases Decomposed by Heating of Insulating Paper in Mineral Oil', JIEE 55-A70, 1980
7 IEC 60243-1, 'Methods of test for electric strength of solid insulating materials', 1988
8 Paul J. Griffin, 'Criteria for the interpretation of data or dissolved gases in oil from transformer', Electrical Insulating Oil, STP 998, pp. 89-106, 1988
9 한전전력연구원, '절연유중 용존가스 분석기술', 1998, 10
10 R. R. Rogers, 'IEEE and IEC Codes to Interpret Incipient Faults in Transformers using Gas in Oil Analysis.' IEEE Transactions on Electrical Insulation. Vol. 13. No. 5. pp. 349-354. October 1978   DOI   ScienceOn
11 E. Dornenburg et al., 'Monitoring oil-cooled transformers by gas analysis', Brown-Boveri Rev. No. 61, pp. 238-247, May 1974
12 IEEE Std C57.104-1991, 'Guide for the detection and determination of generated gases in oil-immersed transformer and their relation to the serviceability of the equipment', 1991
13 IEC Publication 60599, Interpretation of the Analysis of Gases in Transformers and Other Oil-Filled Electrical Equipment in service, 1999
14 한전전력연구원, '765kV 변전기기 예방진단 시스템 개발', 2001. 11