Evaluation of Shear Performance for CSB (Confined Socket Bolt) Shear Connector

CSB (Confined Socket Bolt) 전단연결재의 전단 성능 평가

  • 황승현 (한국건설기술연구원 구조연구본부) ;
  • 문주현 (경기대학교 건축공학과 ) ;
  • 홍종국 (국립순천대학교 건축학부 ) ;
  • 전종철 (뉴콘텍이앤씨(주)) ;
  • 심재일 (한국방재안전기술 )
  • Received : 2022.11.24
  • Accepted : 2023.02.23
  • Published : 2023.04.30

Abstract

This study evaluated a shear capacity of confined socket-bolt (CSB) shear connector developed for utilizing cast in placed pile (CIP) as a permanent underground wall. The push-out tests were performed in the specimens with different CIP types, CSB shear connector types, L/d, and concrete compressive strengths of concrete pile, and with or without waterproofing at interfaces between CIP and underground wall. Test results showed that the specimens with a H-shaped pile were fractured in the CSB shear connector, while the fracture concentrated in the concrete part of the specimens with a reinforced concrete pile was alleviated as the compressive strength of the concrete pile increased, resulting in the severe fracture of CSB shear connector. The maximum shear capacities of the specimens with high strength bolts and reinforcing bars used as CSB shear connector were approximately 1.22 and 1.20 times higher than those of the specimens with a H-shaped pile, respectively, and 1.10 and 1.16 times higher than those of the specimens with a reinforced concrete pile, respectively. Meanwhile, the maximum shear capacity was not significantly affected by the embedding length of the CSB shear connector and overlapping length of reinforcing bar. The predicted shear capacities calculated from the KDS standards were lower than the measured values of all specimens tested in this study.

이 연구에서는 흙막이용 CIP(cast in placed pile)를 영구적인 지하외벽으로 활용하기 위해 제시한 CSB(confined socket bolt) 전단연결재의 전단 성능을 평가하였다. CSB 전단 성능 평가를 위한 푸쉬아웃(push-out) 실험의 주요 변수는 CIP의 종류, CSB 전단연결재 종류, L/d, 무근 콘크리트, 방수재 및 철근콘크리트 말뚝의 압축강도로 설정하였다. 실험결과, H-형강 말뚝 실험체들의 파괴모드는 모두 CSB 전단연결재 파단에 의해 지배되었다. 철근콘크리트 말뚝 실험체들의 파괴모드는 철근콘크리트 말뚝의 압축강도가 증가할수록 콘크리트의 파괴보다 CSB 전단연결재의 파단에 의해 지배되었다. 고강도 볼트 및 이형철근의 CSB 전단연결재 실험체의 최대 내력은 일반강도 볼트의 CSB 전단연결재 실험체에 비해 H-형강 말뚝의 경우 약 1.22배 및 1.20배 높았으며, 철근콘크리트 말뚝의 경우 약 1.10배 및 1.16배 높았다. 그리고 푸쉬아웃 실험에서 최대 내력은 CSB 전단연결재의 길이 및 철근 중첩에 대한 영향이 미미하였다. KDS 기준에 의해 산정된 전단내력은 실험결과를 안전측으로 평가하였다.

Keywords

Acknowledgement

본 연구는 국토교통부/국토교통과학기술진흥원의 지원으로 수행되었음(RS-2021-KA161331).

References

  1. Balasubramanian, B., and Rajaram, B. (2016), Study on Behaviour of Angle Shear Connector in Steel-concrete Composite Structures, International Journal of Steel Structures, 16(3), 807-811. https://doi.org/10.1007/s13296-015-0094-0
  2. British Standars Institution (2004), Eurocode 4: Design of Composite Steel and Concrete Structures EN1994-1-1:2004, CEN-European Committee for Standardization, London, UK.
  3. Choi, Y. H., Heo, B. W., and Chae, J. Y. (2022), Structural Performance Evaluation of Shear Connectors for Basement Composite Walls, Journal of Korean Society of Steel Construction, 34(3), 173-184. (in https://doi.org/10.7781/kjoss.2022.34.3.173
  4. KDS 14 20 22 (2022), Concrete Structural Design Code - Shear and Torsion, Korea Construction Standard Center, Seoul, South Korea. (in Korean).
  5. KDS 14 31 10 (2017), Specifications for Structural Steel Buildings (LRFD), Korea Construction Standard Center, Seoul, Korea. (in Korean).
  6. Pallares, L., and Hajjar, J. F. (2010), Headed steel stud anchors in composite structures, Part I: Shear, Journal of Constructional Steel Research, 66(2), 198-212. https://doi.org/10.1016/j.jcsr.2009.08.009
  7. Pavlovic, M., Markovic, Z., Veljkovic, M., and Budevac, D. (2013), BoLted Shear Connectors vs. Headed Studs Behaviour in Push-out Tests, Journal of Constructional Steel Research, 88, 134-149. https://doi.org/10.1016/j.jcsr.2013.05.003
  8. Saleh, S. M., and Majeed, F. H. (2022), Shear Strength of Headed Stud Connectors in Self-Compacting Concrete with Recycled Coarse Aggregate, Buildings, 12(5), 1-13. https://doi.org/10.3390/buildings12050505
  9. Seo, S. Y., Kim, S. S., and Yoon, Y. D. (2010), The Effect of Composite Ratio and Wall Thickness on the Shear Behavior of Composite Basement Wall, Journal of the Korea Institute for Structural Maintenance and Inspection, 14(1), 93-101. (in Korean).
  10. Seo, S. Y., Kim, S. S., Yoon, Y. D., and Ha, K. J. (2008), Experimental Study on the Shear Strength of Form Tie Connector Linked by Stud Coupler, Journal of the Korea Concrete Institute, 20(5), 573-581. (in Korean).  https://doi.org/10.4334/JKCI.2008.20.5.573