Abstract
A self-blast type gas circuit breaker has been studied in this study to improve efficiency of interrupting performance of short line fault(SLF). Hot gas flows of gas circuit breaker have been simulated to evaluate interruption performance using CFD. Design parameters such as various types of expansion chamber and nozzles are suggested by using simulation results. Simulated results and experimental ones are compared with previous (ones that of in under development and with capacitor) GCB. Modified new shape of an expansion chamber and nozzle has been suggested to improve the efficiency of gas flow and to provide guidelines for designing self-blast breaker with a higher interruption capability.