A pilot study of high flux membrane process for responding to influent turbidity changes in reservoir water

호소수 탁도변화 대응을 위한 고플럭스 막여과공정의 Pilot 연구

  • Kang, Joonseok (Graduate school of Water Resources, Sungkyunkwan University) ;
  • Seong, Jayeong (Graduate school of Water Resources, Sungkyunkwan University) ;
  • Yoo, Jewan (Graduate school of Water Resources, Sungkyunkwan University) ;
  • Kim, Hyungsoo (Graduate school of Water Resources, Sungkyunkwan University) ;
  • Lee, Jaekyu (Toray Advanced Materials Korea Inc.) ;
  • Jeon, Minhyuk (Toray Advanced Materials Korea Inc.) ;
  • Cheon, Jihoon (Toray Advanced Materials Korea Inc.)
  • 강준석 (성균관대학교 수자원전문대학원) ;
  • 성자영 (성균관대학교 수자원전문대학원) ;
  • 유제완 (성균관대학교 수자원전문대학원) ;
  • 김형수 (성균관대학교 수자원전문대학원) ;
  • 이재규 (도레이 첨단소재(주)) ;
  • 전민혁 (도레이 첨단소재(주)) ;
  • 천지훈 (도레이 첨단소재(주))
  • Received : 2020.07.31
  • Accepted : 2020.10.30
  • Published : 2020.12.15

Abstract

In the membrane process, it is important to improve water treatment efficiency to ensure water quality and minimize membrane fouling. In this study, a pilot study of membrane process using reservoir water was conducted for a long time to secure high flux operation technology capable of responding to influent turbidity changes. The raw water and DAF(Dissolved Air Flotation) treated water were used for influent water of membrane to analyze the effect of water quality on the TMP (Trans Membrane Pressure) and to optimize the membrane operation. When the membrane flux were operated at 70 LMH and 80 LMH under stable water quality conditions with an inlet turbidity of 10 NTU or less, the TMP increase rates were 0.28 and 0.24 kPa/d, respectively, with minor difference. When the membrane with high flux of 80 LMH was operated for a long time under inlet turbidity of 10 NTU or more, the TMP increase rate showed the maximum of 43.5 kPa/d. However, when the CEB(Chemically Enhanced Backwash) cycle was changed from 7 to 1 day, it was confirmed that the TMP increase rate was stable to 0.23 kPa/d. As a result of applying pre-treatment process(DAF) on unstability water quality conditions, it was confirmed that the TMP rise rates differed by 0.17 and 0.64 kPa/d according to the optimization of the coagulant injection. When combined with coagulation pretreatment, it was thought that the balance with the membrane process was more important than the emphasis on efficiency of the pretreatment process. It was considered that stable TMP can be maintained by optimizing the cleaning conditions when the stable or unstable water quality even in the high flux operation on membrane process.

Keywords

References

  1. Choi, Y.H. and Kweon, J.H.(2005). Investigation of Membrane Fouling in Microfiltration by Characterization of Flocculent Aggregates, J. Korean Soc. Environ. Eng., 28(3), 337-344.
  2. Gregory, J. (1998). Colloidal interactions, Matel. Sci. Forum, 25-26, 125-144. https://doi.org/10.4028/www.scientific.net/MSF.25-26.125
  3. Gregory, J. and Duan, J. (2001). Hydrolysing metal salts as coagulants, Pure Appl. Chem., 73(12), 2017-2026. https://doi.org/10.1351/pac200173122017
  4. Guigui, C., Rouch, J.C., Durand-Bourlier, L., Bonnelye, V. and Aptel, P. (2002). Impact of coagulation conditions on the in-line coagulation/UF process for drinking water production, Desalination, 147, 95-100. https://doi.org/10.1016/S0011-9164(02)00582-9
  5. Ha, G.R., Kim, H.S., Oh. Y.G., Kim, C.H., Quang, C.X.. Tam, P.T.T. and Lee, Y. H. (2007). Determination of optimal coagulant dosage in pre-coagulation/submerged MF for reducing membrane fouling, J. Korean Soc. Environ. Eng., 2007(5), 2087-2091.
  6. James, C.V., Mark, A.T. and Uday, G.K. (1995). The use of membrane filtration in conjuction with coagulation processes for improved NOM removal, Desalination, 102, 57-61. https://doi.org/10.1016/0011-9164(95)00041-Y
  7. Jin, Y.C., Choi, Y.H. and Kweon, J.H. (2011). Impact of characteristics of polymeric Al coagulants PACl and alum on membrane flux and fouling of microfiltration, J. Korean Soc. Water Wastewater, 25(2), 231-240.
  8. Jung, C.W., Shim, H.S. and Sohn, I.S. (2007). Effect of metal salt coagulant on membrane fouling during coagulation-UF membrane process, Korean Chem. Eng. Res., 45(5), 523-528.
  9. Kang, J.S. Park, S.G., Lee, J.J. and Kim, H.S. (2018). Effects of membrane fouling formation by feed water quality and membrane flux in water treatment process using ceramic membrane, J. Korean Soc. Water Wastewater, 32(2), 77-87. https://doi.org/10.11001/jksww.2018.32.2.077
  10. Kang, J. S., Park, S.G., Song, J.Y., Jeong, A.Y., Lee, J.J. and Kim, H.S. (2017). Evaluation of membrane fouling characteristics due to manganese and chemical cleaning efficiency in microfiltration membrane process, J. Korean Soc. Water Wastewater, 31(6), 539-549. https://doi.org/10.11001/jksww.2017.31.6.539
  11. Kim, J.H., Mun, B.S., Jang, H.J., Kim, J.H., and Kim, B.S.(2013). Increase of recovery ratio by two stage membrane process(the pressurized PVDF membrane followed by submerged PE membrane), Membr. J., 23(1), 45-53.
  12. Korea Environment Corporation. (2017). Development of membrane filtration water treatment facility technical inspection manual.
  13. Lee, B.G., Lee, K.S., Lee, K.K. and Kang, S.H. (2007). Characteristics of long term Period MF Membrane Pilot Plant Operation for Replacement of Sand Filtration, J. Korean Soc. Water Environ., B-3, 163-171.
  14. Lee, B.H., Kim, J.G. and Lee, K.H. (2000). Membrane fouling by iron and manganese in hollow-fiber microfiltration, J. Korean Soc. Civ. Eng., 7, 591-597.
  15. Lee, J.D., Lee, S.H., Jo, M.H., Park, P.K., Lee, C.H. and Kwak, J.W. (2000). Effect of coagulation conditions on membrane filtration characteristics in coagulation-microfiltration process for water treatment, Environ. Sci. Technol., 34, 17, 3780-3788. https://doi.org/10.1021/es9907461
  16. Lee, S.H., Kweon, J.H., Choi, Y.H. and Ahn, K.H. (2004). Effects of characteristics of flocculant aggregates on membrane fouling in microfiltration with coagulation pretreatment, J. Korean Soc. Water Wastewater, 18(6), 785-793.
  17. Lee, Y.T. and Oh, J.K. (1999). A study on the optimization of process and operation condition for membrane system in tap water treatment, Membr. J., 9(4), 193-201.
  18. Ministry of Environment. (2014). The study for applicability evaluation and the developmental direction of membrane water treatment facilities.
  19. Pernitsky, D.J. and Edzwald, J.K. (2003). Solubility of polyaluminuium coagulants, J. Water Supply Res. Technol., 52(6), 395-406. https://doi.org/10.2166/aqua.2003.0036
  20. Song, Y.K., Jung, C.W., Hwangbo, B.H. and Shon, I.S. (2001). Characteristics of Al(lll) hydrolysis species distribution on coagulation process, Korean Chem. Eng. Res., 44(5), 547-554.