DOI QR코드

DOI QR Code

An Experimental Study for the Improvement of Ventilation Conditions and Effectiveness in the Manufacturing Industry by Increasing the Mixing Factor (K-Factor)

혼합계수(K-Factor) 증가에 따른 사업장의 환기 조건 및 효율 개선에 관한 연구

  • Lee, Yun-ho (Department of Public Health, Graduate School, The Catholic University of Korea) ;
  • Lee, Seokwon (Samsung Health Research Institute, Samsung Electronics Co., Ltd.) ;
  • Lee, Kyoungho (Samsung Health Research Institute, Samsung Electronics Co., Ltd.) ;
  • Kim, Hyunwook (Department of Public Health, Graduate School, The Catholic University of Korea)
  • Received : 2019.08.20
  • Accepted : 2019.09.25
  • Published : 2019.09.30

Abstract

Objectives: This study aims to identify whether ventilation conditions and their effectiveness can be significantly improved in an experimental chamber by increasing the mixing factor (K-Factor). Methods: In a chamber with a volume of $1m^3$, air velocity was measured at six different points with four roof fans in the upper part of the chamber being operated in order. The impact of the ventilation conditions was analyzed when the flow rates were increasing and the first inlet of the chamber was either open or closed. Smoke patterns were also observed at four corner points where ventilation was limited. Kruskal Wallis and Mann-Whitney tests were performed to compare air velocities measured in the chamber. Results: The air velocities measured at only the third point increased significantly from $0.03{\pm}0.03m/s$ (door open) and $0.05{\pm}0.06m/s$ (door closed) with two fans, $0.08{\pm}0.08m/s$ with three fans, and $0.09{\pm}0.09m/s$ with four fans operating (p<0.05). However, air velocities at the four corner points did not significantly increase. Smoke patters also showed that the open inlet of the chamber had no effect on improvement of ventilation conditions and effectiveness. Conclusions: In this study, the air velocities at six points in the chamber did not significantly increase despite the increase in the mixing factor and flow rates of ventilation in the controlled environment. Therefore, the inflow of outdoor air throughout an open inlet and installation of a forced ventilation system can potentially increase the indoor air velocity and improve ventilation condition without an increase in the mixing factor.

Keywords

References

  1. America Conference of Governmental Industrial Hygienists. Industrial ventilation A Manual of recommended Practice for Design 27th edition. ACGIH 2010;4-5;4-1-5-34
  2. Baek UG, Pea YG, Kim BN, Kim BG. The study of Concept for Effective Ventilation Condition in the Site - Shipbuilding Site Welding Process. KOSHA 2004
  3. Chen F, Chen H, Xie J, Shu Z, Mao J. Air Distribution in room ventilated by fabric air dispersion system. Build Environ 2011;46: 2021-9
  4. Chou P, Chiang C, Chuah Y, Wang W. Effects of Window Position on the Air Flow Distribution in a Cross-Ventilated Residential Bedroom. INDOOR BUILT ENVIRON 1998; 7:301-7
  5. Chung I, Derek D. Using numerical simulation to predict ventilation efficiency in a model room. ENERG BUILDINGS 1998; 28:43-50 https://doi.org/10.1016/S0378-7788(97)00061-3
  6. Crowl D, Louvar J. Chemical Process Safety Fundamentals with Applications 3rd Edition. Prentice Hall 2011;103-9
  7. Gao J, Zhao J, Li X, Gao F. Evaluation of a Zonal Model for Large Enclosures Using Computational Fluid Dynamics. J ASIAN ARCHIT BUILD 2007; 6:379-85 https://doi.org/10.3130/jaabe.6.379
  8. Gant S, Kelsey A, Gobeau N. Factors Influencing the Indoor Transport of Contaminants and modeling implications. Health &Safety Laboratory 2006
  9. Gobeau N, Lea C, Kelsey A, Saunders J. Investigation of the factors Influencing pesticide distribution in naturally-ventilated buildings. Health & Safety Laboratory 2005
  10. Ha HC, Kim TH, Kim JC, Shim GJ, Kim et al. Survey on Operation and Maintenance of Hot - wire Anemometers. J Korean Soc Occup Environ Hyg 1999; 9:123-33
  11. Hajdukiewicz M, Geron M, Keane M. Formal calibration methodology for CFD models of naturally ventilated indoor environments, Build Environ 2013;59:290-302 https://doi.org/10.1016/j.buildenv.2012.08.027
  12. Huang CH, Lin PY. Influence of spatial layout on airflow field and particle distribution on the workspace of a factory, Build Environ 2014;71:212-22 https://doi.org/10.1016/j.buildenv.2013.09.014
  13. International Electric Code. 60079-10-1 Explosive atmospheres - Part 10-1: Classification of areas - Explosive Gas atmospheres. 2009
  14. Jung JH, Park DJ, Ha HC, Lee JH, Hwang SM et al. Risk Assessment of NG Facility for reviewing the electrical area classification. KOSHA 2013
  15. Jung UG, Park HH. The study of Concept for Effective Ventilation Condition in the Site - Electronic Cleanroom Process. KOSHA 2007
  16. Kim TH, Kim HW, Park DU, Baek NW. Industrial Ventilation, Shingwang, 1999. ISBN: 89-7069-470-6.
  17. KOSHA. Guidelines of Industrial Ventilation W-1-2014. KOSHA 2014
  18. Lim ES, Kazuhide I, Mats S. Performance evaluation of contaminant removal and air quality control for local ventilation systems using the ventilation index Net Escape Velocity. Build Environ 2014; 79:78-89 https://doi.org/10.1016/j.buildenv.2014.04.020
  19. Meisenzahl l. Vortex Ventilation in the Laboratory Environment. J Occup Environ Hyg 2014; 11:672-9 https://doi.org/10.1080/15459624.2014.902952
  20. Meroney R, Hill D, Derickson R, Stroup J, Weber K, Garrett P. CFD Simulation of ventilation and smoke movement in a large military firing range. J WIND ENG IND AEROD 2015; 136:12-22 https://doi.org/10.1016/j.jweia.2014.10.011
  21. Son BS, Park JA, Kim MC, Byun SH, Park SC et al. Industrial Ventilation - Theory and Practice. Donghwa Technology 2001
  22. US Air Force. AFOSH Standard 161.2. 1977