초록
Recently, time synchronous has become important for satellite launch control facilities, multiple thermal power plants, and power system facilities. Information from time synchronous at each of these industrial sites requires time synchronization to control or monitor the system with correlation. In this paper, IRIG-B codes, which can be used for time synchronous, are used as specifications in IRIG standard 200-16. Signals from IRIG-B120 (Analog), IRIG-B000 (Digital), and one PPS are output from GPS receiver. Using the signal from IRIG-B120 (Analog), it passes through the signal from the analog amplifier and generates one PPS signal using the field-programmable gate array. The FPGA is used cyclone EPM570T100I5N. According to IEEE regulations, the error of one PPS is specified within 1us, but in this paper, the error is within 100ns. The output of the one PPS signal was then compared and tested against the one PPS signal on the GPS receiver to verify accuracy and reliability. In addition, the proposed time synchronous is simple to construct and structure, easy to implement, and provides high time precision compared to typical time synchronous. The output of the one PPS signals and IRIG-B000 signal will be used in many industry sectors.