Abstract
Free-standing structures that are especially high are more likely to receive brain attacks caused by lightning. Since special structures are generally part of national industrial structures, lightning strikes mostly cause socio-economic damage. Lightning protection facilities are installed to prevent such lightning damage, but in 2015, support cables on West Sea bridges were hit by lightning, causing a lot of economic damage. Accordingly, the design of a lightning protection system shall establish protective measures after analyzing the risk of debris falling onto the structure. In this thesis, lightning strikes are analyzed directly in relation to the modeling system that operates the actual information collection system for lightning strikes, depending on the location of the tall, free-standing structures, and practical lightning hazard information is provided by a meteorological station. In addition, we propose monitoring and applying a probability correction rate to the calculation of the lightning risk based on the number of lightning strikes directly reaching the ground in order to obtain an effective lightning risk assessment.
특수구조물 중에서 특히 높은 독립적 구조물은 낙뢰에 의한 뇌격을 받을 가능성이 높다. 특수 구조물은 대체적으로 국가 산업시설물에 속하므로 낙뢰로 인한 피해는 사회적 경제적 손실이 막대하다. 이러한 낙뢰 피해 방지를 위해 낙뢰 보호시설을 설치하였으나 2015년도에 서해 대교의 지지케이블에 낙뢰로 인한 화재가 발생하여 많은 경제적 손실을 초래하였다. 이에 낙뢰 보호 시스템의 설계는 구조물에 낙뢰 위험을 분석 한 후 보호 조치를 수립해야한다. 뇌격에 대한 위험도 평가에 대한 국제적 규격은 국제전기기술위원회(IEC) 규격이 전 세계적인 규격의 근간을 이루고 있으며, 특히 해외 국가규격이나 기준은 IEC 기준으로 낙뢰 위험도 평가를 실시하여 낙뢰 보호대책시 적용하고 있다. 국내에서도 KS C IEC 62305 규격을 적용하여 위험성평가와 피뢰보강을 위한 기초자료로 활용하고, 낙뢰 보호 시스템을 설계한다. KSC IEC 측정방법으로 국내 특수교 리스크 평가에 대한 결과로는 물리적 손상 및 전자계시스템 위험 특수교는 평가대상 전체 교량 77개 교량 중 7개 교량에서 허용위험도가 높은 것으로 보고되었다. 본 논문에서는 높고 독립적 구조물의 위치에 따라 낙뢰 수에 대한 실제 정보 수집 시스템을 운영하는 모델링 시스템을 제안하기 위해 실제적인 낙뢰 정보를 분석하고 기상 관측소에서 제공 한 낙뢰수와 높은 구조물에 직접 도달하는 위험한 낙뢰 수를 비교하여 검증하는 방법을 검토하였으며, 지상에 직접적으로 도달한 낙뢰수에 따른 낙뢰위험도 산출시 확률적 보정률을 모니터링하여 적용함으로써 실효적인 낙뢰위험도 평가를 할 수 있도록 제안하고자 한다.