Air-side Heat Transfer and Pressure Drop of a Fin-and-Tube Heat Exchanger Under Low Temperature Condition

저온 조건에서 핀-관 열교환기의 공기측 열전달 및 압력손실

  • Kim, Nae-Hyun (Department of Mechanical Engineering Incheon National University)
  • 김내현 (인천대학교 기계시스템공학부)
  • Received : 2017.01.02
  • Accepted : 2017.04.07
  • Published : 2017.04.30

Abstract

Currently, residential air conditioners operate as a heat pump during winter. In this case, the outdoor heat exchanger acts as an evaporator obtaining heat from cold air. On the other hand, it acts as a condenser during summer transferring heat to hot air. The outdoor temperature changes significantly from high to low. Generally, the air-side j and f factors are obtained at a standard outdoor temperature. Therefore, the applicability of the j and f factors under different outdoor conditions needs to be checked. In this study, tests were conducted for a two-row louver finned heat exchanger changing the outdoor temperature to subzero. The effects of the tube-side brine flow rate were also checked. The results showed that air-side j and f factors were essentially constant and independent of the outdoor temperature, suggesting that an extension of j and f factors obtained under standard conditions to a low outdoor temperature is acceptable. All j and f factors agreed within 9% and 3%, respectively. Tests were also conducted by changing the coolant flow rate. Both the j and f factors did not change according to the flow rate, suggesting that the tube-side heat transfer correlation is acceptable.

최근 들어 가정용 공조기가 겨울철에 히트 펌프로도 사용된다. 이 때 실외기는 저온의 외기와 열전달을 하며 관내의 냉매를 증발시킨다. 반면 여름철에 냉방기로 사용될 경우 실외기는 고온의 외기와 열전달을 통해 관 내의 냉매를 응축시킨다. 즉, 동일한 열교환기가 여름철에는 응축기로, 겨울철에는 증발기로 사용되고 외기 조건도 겨울철의 저온에서 여름철의 고온까지 넓은 범위에 놓이게 된다. 본 연구에서는 표준 설계 온도 조건에서 얻어진 j와 f 인자가 저온 운전 시에도 무리없이 적용 가능한지를 실험을 통하여 확인하였다. 이를 위하여 2열 루버 핀-관 열교환기에 대하여 외기 온도를 변화시키며 일련의 실험을 수행하였다. 또한 관 내측의 브라인의 유량이 미치는 영향도 살펴보았다. 실험 결과 외기의 온도 변화가 j와 f 인자에 미치는 영향은 무시할 만 하였다. 모든 j와 f 인자는 각각 9%, 3% 내에서 일치하였다. 따라서 표준 조건에서 얻어진 j와 f 인자를 저온 조건에 사용하여도 무리가 없다고 판단된다. 또한 관 내측 유량 변화가 j와 f 인자에 미치는 영향이 미미한 것으로 미루어 관 내측 상관식의 적용이 적절하다고 판단된다.

Keywords

References

  1. Wang, C.-C., Webb, R. L. and Chi, K.-Y., "Data reduction for air-side performance of fin-and-tube heat exchangers," Exp. Thermal Fluid Sci., vol. 21, no. 4, pp. 218-226, 2000. DOI: https://doi.org/10.1016/S0894-1777(00)00005-4
  2. Kim, N.-H., Oh, W.-K., Cho, J.-P., Park, H.-Y, Youn, B., "Data reduction on the air-side heat transfer coefficients of heat exchangers under dehumidifying conditions," Korean J. Air Conditioning Refrigeration, vol. 15, no. 1, pp. 73-85, 2003.
  3. Kim, N-H., Personal communication with Samsung Electronics, 2016.
  4. Mills, A. F., Basic Heat ad Mass Transfer, Irwin Pub., 1995.
  5. ASHRAE Standard 41.1, Standard Method for Temperature Measurement, ASHRAE, 1986.
  6. ASHRAE Standard 41.2, Standard Method for Laboratory Air-Flow Measurement, ASHRAE. 1987.
  7. ASHRAE Standard 41.5, Standard Measurement Guide, Engineering Analysis of Experimental Data, ASHRAE, 1975.
  8. ESDU 98005, Design and performance evaluation of heat exchangers: the effectiveness and NTU method, Engineering and Sciences Data Unit 98005 with Amendment A, London ESDU International plc., pp. 122-129, 1998.
  9. Park, B.-B., You, S.-M., Yoon, B., and Yoo, K.-C., "Experimental study of heat transfer and pressure drop characteristics for flow of water inside circular smooth and micro-fin tubes," Korean J. Air Conditioning Refrigeration, vol. 9, no. 4, pp. 454-461, 1997.
  10. Schmidt, T. E., "Heat transfer calculations for extended surfaces," J. of ASRE, Refrigeration Engineering, vol. 4, pp. 351-357, 1949.
  11. Dittus, F. W. and Boelter, L. M. K., "Heat transfer in automobile radiators of the tubular type," University of California Publications on Engineering, vol. 2, no. 13, pp. 443-461, 1930.
  12. Gnielnski, V., "New equations for heat and madd transfer in turbulent pipe and channel flow," Int. Chem. Eng., vol. 16, pp. 359-368, 1976.