DOI QR코드

DOI QR Code

Stability Analysis and Improvement of the Capacitor Current Active Damping of the LCL Filters in Grid-Connected Applications

  • Xu, Jinming (College of Automation Engineering, Nanjing University of Aeronautics and Astronautics) ;
  • Xie, Shaojun (College of Automation Engineering, Nanjing University of Aeronautics and Astronautics) ;
  • Zhang, Binfeng (College of Automation Engineering, Nanjing University of Aeronautics and Astronautics)
  • Received : 2015.12.02
  • Accepted : 2016.04.06
  • Published : 2016.07.20

Abstract

For grid-connected LCL-filtered inverters, dual-loop current control with an inner-loop active damping (AD) based on capacitor current feedback is generally used for the sake of current quality. However, existing studies on capacitor current feedback AD with a control delay do not reveal the mathematical relation among the dual-loop stability, capacitor current feedback factor, delay time and LCL parameters. The robustness was not investigated through mathematical derivations. Thus, this paper aims to provide a systematic study of dual-loop current control in a digitally-controlled inverter. At first, the stable region of the inner-loop AD is derived. Then, the dual-loop stability and robustness are analyzed by mathematical derivations when the inner-loop AD is stable and unstable. Robust design principles for the inner-loop AD feedback factor and the outer-loop current controller are derived. Most importantly, ensuring the stability of the inner-loop AD is critical for achieving high robustness against a large grid impedance. Then, several improved approaches are proposed and synthesized. The limitations and benefits of all of the approaches are identified to help engineers apply capacitor current feedback AD in practice.

Keywords

I. INTRODUCTION

In distributed power generation systems based on renewable energies, a grid-connected inverter is used to inject power into the grid. However, the pulse-width-modulation (PWM) results in a lot of switching harmonics. In order to avoid polluting the ac grid, an inverter should ensure a grid current with a low distortion. Thus, a filter is required. An LCL-type filter is capable of attenuating switching harmonics in the grid current with a lower inductance than an L filter. As a result, it has been widely used to satisfy harmonic limitations. However, due to the inherent resonance of an LCL filter, the inverter has a hard time realizing good stability and a high bandwidth. Studies of inverter-side current or grid current controls have indicated that performance with a single current feedback is related to the ratio of the resonance and control frequencies so that the filter and controller parameters cooperate properly [1]. However, because of some non-ideal factors like variations of the LCL parameters and grid impedance, an inverter with a single current feedback is difficult to design and tends to perform poorly in the case of wide parameter variations. Using a passive resistor in series with a capacitor is a simple way to improve the inverter performance at the cost of power losses [2]. Alternatively, during the last decade, researchers have tried to use active damping (AD) to improve performance. AD methods include capacitor current feedback [3]-[6], capacitor voltage feedback [7] and [8], grid current feedback [9] and [10] and multi-state feedback [11] and [12]. Among them, capacitor current feedback is broadly discussed.

For capacitor current feedback AD, the proportional feedback of the capacitor current is shown to be capable of damping resonance and improving performance when the control delay is ignored [3]-[6]. A design method based on zero-pole cancellation was proposed in [3], while the parameters are determined by balancing the peak attenuation and phase margin [4]-[6]. However, the control delay in a digital signal processor (DSP) should be considered. In [13], a dual-loop current control with both capacitor current and grid current feedbacks was investigated for three different resonance frequencies. It was shown that the proportional feedback of the capacitor current did not stabilize the system at low resonance frequencies. However, the detailed relations between the stability and the resonance frequency were not given. As a result, a guideline for an optimized design was lacking. In [14], the virtual impedance method demonstrated that the proportional feedback of the capacitor current no longer acted like a virtual resistor at high resonance frequencies (above 1/6 of the control frequency, as analyzed in [15]). However, the relationships among the dual-loop stability, the AD and the control delay were not clearly identified. In [16], the stability criterion of the capacitor current feedback AD was derived. However, the dual-loop stability was missing. In [17], the stable region was derived in the case of a one-sample delay. However, the robustness was ignored, and the impact of the AD on the dual-loop stability was simply mentioned with few words. The state-of-art studies show that:

Considering that studies on dual-loop control are lacking, it is not surprising that approaches enhancing performance are still lacking or not well documented. The authors of [14] discussed one way of moving the sampling instant toward the reloading instant of the PWM reference in order to extend the frequency range where the AD behaved as a virtual resistor. However, aliasing harmonics as analyzed in [14] and [18] affected the sampling accuracy. In [19], a real-time loading approach is used to reduce the delay. Closed-loop pole maps were given to identify robustness. However, theoretical demonstrations were missing. In addition to the two approaches depending on the DSP working mode, the use of an extra phase compensator seemed to be an alternative choice. In [15], [17], [20] and [21], researchers tried several kinds of compensators such as the proportional plus derivative, as well as high-pass and delay-based filters. All of them feature phase leading and the designs had to make a balance between robustness and noise disturbance.

Under these circumstances, research on the stability and improvement of dual-loop control with capacitor current AD is lacking. Therefore, this paper aims to provide a deep study of such AD. The model of a digital control system is more complex than that of the analog control system in [22]. This study focuses on the dynamics and stability at frequencies below the control frequency. Either the s-domain or z-domain model can be used. Digital PWM is seen as a zero-order hold (ZOH) in the s-domain and z-domain models [1], [9], [14]-[17]. In addition, for an accurate representation of the digital control delay, an exponential function of the delay time should be used in the s-domain model [14], [15], [17]. It is noted that if the dynamics and stability at higher frequencies are concerned, the s-domain model is no longer proper due to the nonlinear dynamics of power switches. In this case the z-domain model should be carefully used. In [23]-[25], researchers have made some contributions to the accuracy of the z-domain model. However, this topic is not the emphasis of this paper.

This paper derives the detailed constraints of the LCL-filter, controller and DSP working mode to ensure good stability and high robustness. Based on theoretical derivations, several suitable approaches are proposed to maintain better stability and performance. A grid-connected LCL-filtered inverter is built to verify the theoretical analysis.

 

II. SYSTEM DESCRIPTION

Fig. 1 shows the structure of a grid-connected inverter with an LCL filter consisting of an inverter-side inductor L1, a filter capacitor C1 and a grid-side inductor L2, where Udc denotes the DC voltage, uinv denotes the inverter output voltage, iL1 is the inverter-side current, ug is the grid voltage, and ig represents the grid current. In practical applications, the DC side can be connected to an input source (e.g., a PV array or a DC bus) in a single-stage system or to a DC-DC converter in a dual-stage system. The current amplitude reference Iref is produced by the DC voltage control, which is used to keep the DC voltage at Uref. A phase-locked loop (PLL) is adopted to obtain the phase information (θ) of ug. Then, Iref is multiplied by sinθ to generate the instantaneous current reference iref. With proper current control, a signal um is generated for the digital PWM. Here, um is called the modulation wave (also called the PWM reference [14]). Fig. 2 gives the current control, where kPWM denotes the transfer function from um to the inverter voltage uinv, and kAD is a proportional factor.

Fig. 1.Grid-connected LCL-filtered inverter.

Fig. 2.Structure of capacitor current and grid current feedback dual-loop control.

The transfer function from uinv to ig is expressed as:

A pair of under-damped poles appears at the resonance frequency ωres. The expression of ωres is:

 

III. STABILITY WITH CAPACITOR-CURRENT FEEDBACK ACTIVE DAMPING

A. Capacitor-Current-Feedback AD without a Delay

The equivalent structure of the inner-loop AD control is shown in Fig. 3, where the transfer function from uinv to iC1 is:

Fig. 3.Equivalent structure of capacitor current AD.

As shown from Fig. 3, the open-loop transfer function is:

If the control delay is not considered, kPWM is just a proportional factor (i.e., Udc/Vtri, where Vtri is the amplitude of the triangle carrier [6]). Then, Bode plots of (4) with respect to different values of kAD are shown in Fig. 4. Due to the high peak, two 0dB-crossing points are produced. However, according to the Nyquist stability criterion in the Bode plots (in Appendix A), the AD control works stably because the phase curve does not cross the ±180°-lines between the two 0dB-crossing frequencies. Moreover, as can be seen from Fig. 4 (i.e., the colored points), the phase margins (PMs) at the two 0dB-crossing frequencies are −90° and 90°. That is, the capacitor current AD fails to suppress the resonance peak once another 90° advance or lag is added to the open-loop phase. Unfortunately, the control delay yields a fairly large lag in the phase.

Fig. 4.Bode plots of (4) without the control delay.

B. Stable Region of the AD in a Digital Control System

In a digital system, there is always a delay between the signal sampling and the modulation wave reloading. In addition, the PWM inverter can be seen as a zero-order hold model. That is, kPWM in a digital system is:

where |kPWM| is Udc/Vtri [14], Ts is the control period, and Td is the delay between the sampling of iC1 and the reloading of um. The total control delay is the sum of Td and Ts/2. The control delay makes the phase curve of (4) lower than that shown in Fig. 3. As a result, the PM is decreased and the system stability is endangered. The phase lag caused by (5) at frequency f is:

where fs is the control frequency, which is equal to 1/Ts.

To evaluate the stability, the 0dB-crossing frequencies should be calculated first. By letting the magnitude of (4) be equal to 1, the two 0dB-crossing frequencies in rad/s are exactly the solutions of the following equations:

Then, the two 0dB-crossing frequencies in Hz are:

Accordingly, considering the control delay, the phase of (4) at a higher 0dB-crossing frequency fx1 is:

Then, the PM at fx1 is:

Since the open-loop transfer function in (4) does not have a right-half-plane pole, the stability can be guaranteed as long as no positive or negative crossings occur. Therefore, the way to ensure stability is PMx1> 0°, i.e.:

As can be seen from (11), the stable region of the capacitor current AD is closely related to the sampling and computation delay time, the control frequency, the resonance frequency and the feedback factor. Note that if (11) is fulfilled, the phase at the lower 0dB-crossing frequency fx2 is much smaller than 180°. Therefore, the PM at fx2 is satisfactory.

As can be seen from (8), if kAD is small, fx1 and fx2 both become approximately equal to fres. It is obtained from (11):

Accordingly, a critical value of the resonance frequency can be obtained:

If (13) is satisfied, it is possible for the capacitor current feedback to work stably with a proper kAD. Especially, for Td=Ts (i.e., a one-sample delay), the critical value of α is exactly 1/6. Meanwhile, for Td=0.5Ts, the critical value of α is exactly 1/4. It is emphasized that (13) is a necessary condition, and that the parameter kAD still has to satisfy (11).

For a known value of ωres, the range of the feedback factor is obtained from (8) and (11):

where KAD is equal to kAD|kPWM|, and KADMax is the maximum value of KAD. The calculation steps are given in Appendix B.

Therefore, when the system parameters satisfy (15), the inner AD control is stable. On the other hand, if (15) is not fulfilled, a negative crossing in the open-loop phase appears so that a closed-loop transfer function with an inner AD control has two unstable poles.

To verify the analysis, the system parameters are given in Table I and the delay Td is 0.5Ts. Then, with the use of (13), α and ωdiv are calculated. The ratio α is 0.267 with C1=7μF (ωres>ωdiv), while it is 0.172 with C1=17μF (ωres<ωdiv). The variation trend of PMx1, subjected to different values of KAD, is given in Fig. 5. Therefore, it is unable to maintain stability when ωres is above the critical frequency, as shown by the solid line. On the other hand, the proportional capacitor current feedback is able to work with a proper KAD for ωres<ωdiv. By substituting the LCL parameters and ωdiv into (14), the limit of KAD is then obtained as KAD<7.48. As indicated by the dashed line, a larger KAD also results in instability of the inner AD control.

TABLE ISYSTEM DEFAULT PARAMETERS

Fig. 5.Plots of PMx1 with respect to different KAD.

 

IV. STABILITY AND ROBUSTNESS WITH DUAL-LOOP CURRENT CONTROL

A. Impact of Inner-Loop Stability on Dual-Loop Control

In this section, the overall stability including the outer and inner control loops will be analyzed. Fig. 6 shows the equivalent control structure of Fig. 2, where the transfer function from iC1 to ig is expressed as:

Fig. 6.Equivalent structure of dual-loop current control.

The open-loop transfer function from iref to ig is:

Proportional-resonant and proportional-integral regulators are two commonly used regulators [3], [6]. Given that the effect of the resonant or integral element on the stability margin is small, Gc(s) is usually treated as a proportional regulator (i.e., kp) in the analysis of stability [14], [17]. The specific expression of the open-loop transfer function is:

where KP is equal to kp|kPWM|.

Note that Gc(s) and (16) do not have poles with a positive real part. Thus, if the inner AD is stable, (17) and (18) have no poles on the right half of the s-plane (or outside the unit circuit in the z-plane). Meanwhile, if the inner AD is unstable, (17) and (18) have two poles on the right half of the s-plane.

1) Case I: the Inner AD Control is Stable

As can be seen from the above analysis, (18) has no poles on the right half of the s-plane if the inner-loop AD control is stable. Taking C1=17μF in Table 1 as an example, as shown in Fig. 7(a), the phase curves of the system all cross the –180° line only at the resonance frequency ωres when KAD

Fig. 7.Open-loop Bode plots with dual-loop current control for different ωres and kAD, (a) ωres<ωdiv and (b) ωres≥ωdiv. (See Appendix D for more detail)

As can be seen from (19), with a decrease of KAD or an increase of KP, the gain margin decreases and the system eventually loses stability.

2) Case II: the Inner AD Control is Unstable

When the AD control is unstable, (18) has two poles on the right half of the complex s-plane. A positive crossing with the –180° line is needed according to the Nyquist stability criterion in the Bode plot. Recalling the stable regions shown in (15), there are two kinds of unstable regions for the inner AD control: 1) ωres≥ωdiv; 2) ωres<ωdiv and KAD> KADMax.

First, when ωres≥ωdiv (taking C1=7μF as an example), the inner AD control is always unstable. As shown in Fig. 7(b), the phase curves of the system always cross the –180°-line at ωdiv and then at ωres. This kind of phase crossing is called the first crossing situation in this study. A positive crossing with –180° at around ωres needs to be designed to offset the above two poles under this situation. Therefore, the design constraints are:

As can be seen from (20), KP should be neither small nor large in the first crossing situation. Otherwise, the overall system is unstable. The lower and upper limits of KP are separately determined by the two inequalities in (20).

Second, for ωres<ωdiv and KAD> KADMax, the inner AD control is always unstable. Taking C1=17μF as an example, as shown in Fig. 7(a), the phase curves of the system always cross the –180°-line at ωres and then again at ωdiv. This is called the second crossing situation in this study. A positive crossing with –180° at around ωdiv is needed in order to offset the above two poles under this situation. Therefore, the design constraints are:

As can be seen from (21), the constraints for the second crossing situation are opposite those of the first crossing one.

B. Robustness Analysis

1) Case I: the Inner AD Control is Stable

In a weak grid, the grid impedance Lg makes the real resonance frequency ωres_Lg smaller than ωres [26]-[29]. The increase of Lg can be seen as an increase of the grid inductance L2. In (19), replace L2 with L2+Lg. It can be seen that GM(ωres_Lg) is a monotonically-increasing function about L2 (or Lg). As a result, GM(ωres_Lg) is always larger than 0 with an increase of Lg because the initial margin is greater than 0 when Lg is 0, i.e., (19). Therefore, when the inner-loop AD control is stable, the dual-loop system exhibits a high robustness when the grid impedance changes.

2) Case II: the Inner AD Control is Unstable

For the first crossing situation, with an increase of L2 (or Lg), ωres_Lg is always larger than ωdiv or it is decreased to less than ωdiv, depending on the LCL parameters. On the one hand, if the minimum value of ωres_Lg is larger than ωdiv, the criterion to ensure stability is GM(ωres_Lg)<0, in the case of the minimum value of ωres_Lg. By replacing L2 with L2+Lg in (20), the value of Kp has to be largely reduced to ensure that GM(ωres_Lg)<0. Thus, the robustness is poor. On the other hand, if the minimum value of ωres_Lg is less than ωdiv, the criterion for robustness is given in (22) because either (19) or (21) has to be fulfilled with the decrease of the real ωres_Lg.

Given that GM(ωres_Lg) is monotonically increasing and ωres_Lg is decreasing with an increase of Lg, (22) is equivalent to the condition GM(ωdiv)=0. However, the LCL parameters always change in practice. Thus, there is no accurate solution for (22), and the robustness is difficult to guarantee.

For the second crossing situation, ωres_Lg is always less than ωdiv with an increase of L2 (Lg). Thus, GM(ωres_Lg) is always larger than 0, given that (21) is fulfilled in the initial design. Because KADMax_Lg (i.e., the new upper limit of KAD considering Lg) increases with an increase of Lg, it is worth noticing that the second crossing situation changes to the situation where the inner AD control is stable. At this time, GM(ωdiv) does not need to be considered. Thus, in order to ensure robustness in this case, it is necessary to make sure that GM(ωdiv) is always less than 0 when KAD>KADMax_Lg. Through the detailed derivations in Appendix C, another range of KAD can be obtained:

C. Discussion

According to the above studies, if the inner AD control is stable, the design of the dual-loop is the simplest and the system exhibits a high robustness. If the inner AD control is unstable, the design constraints are more complex. Only the second crossing situation can conduct a robust design. In addition, for stability purposes, the amplitude curve needs to have multiple crossings with the 0dB-line if the inner AD control is unstable so that the phase margins at all of the 0dB-crossing frequencies are hard to optimize. As a summary of Section IV, ensuring the stability of the inner AD control is meaningful to reduce the difficulty in the dual-loop design, and the dual-loop current control can achieve a high robustness even under the weak grid case without conducting a compromised design.

 

V. APPROACHES TO IMPROVE INNER-LOOP AD STABILITY

Because inner-loop AD stability is critical to optimization of the system control design and improvements of the system performance, several approaches are proposed and investigated based on the expressions of ωres, ωdiv and kADMax.

A. Increasing the Control Frequency fs

As can be seen from (13) and (14), ωdiv and kADMax become larger with an increase of fs. As a result, the system parameters make it easy to satisfy the inner AD criterion in (15). However, it is difficult to increase fs a lot because the maximum value of fs is limited by the complexity of the program and the operation capability of the DSP being used.

B. Reducing the Resonance Frequency ωres

The value of kADMax is increased by decreasing ωres. As a result, this approach makes the inner AD stability easier to achieve. However, changing ωres means changing either the inductance or capacitance. At present, the increases in the filter volume, weight and cost with an increase of capacitance is relatively small compared to an increase of inductance. Thus, increasing C1 is a promising way to decrease ωres.

However, increasing C1 affects the rejection of low-order grid current harmonics. To analyze the impact of C1 on low-order grid current harmonics, the transfer function from ug to ig is expressed as:

where the grid voltage proportional feedforward is considered. In the low-frequency region, s2 and s3 in the denominator can be ignored compared with the other items. Therefore, the magnitudes of (24) at low frequencies increase with an increase of C1. As shown in Fig. 8, increasing C1 results in the current harmonics caused by ug to exhibit a tendency to amplify. In summary, this approach has some limitations when the grid voltage contains many low-order harmonics.

Fig. 8.Impact of grid voltage harmonics on the grid current with the increase of C1.

C. Reducing the AD Feedback Factor kAD

According to (15), reducing kAD is suitable only when ωres<ωdiv. By ensuring that KAD is less than KADMax, the inner-loop AD becomes stable. However, as seen from Fig. 7, reducing kAD is not conducive to suppressing the resonance peak of the LCL filter. As a result, the grid current may contain resonance harmonics even if the system is stable. Another effect of reducing kAD can be seen from (24). With s2 and s3 removed, the magnitudes of (24) at low frequencies decrease with a reduction of kAD.

D. Reducing the Sampling and Computation Delay Td

Another way to increase ωdiv is to reduce Td, and as in the case of increasing fs, KADMax also increases. Reducing Td needs to modify the DSP program. Taking a DSP TMS320F28035 from Texas Instruments as an example, the existing methods are divided into two types. One is the real-time sampling approach, which is carrier out by shifting the sampling instant close to the loading instant of the modulation wave, as shown in Fig. 9(a). The sampling delay can be reduced to the time of the DSP sampling and the calculation of the modulation wave. However, this method is challenged by the sampling aliasing problem [14], [18]. The other method is the real-time loading approach by shifting the loading instant of the modulation wave close to the sampling instant, as shown in Fig. 9(b). Similarly, the sampling delay is reduced to the time of the DSP sampling and the calculation of the modulation wave. However, this method is challenged by the reliability, e.g., the problem of driver shoot-through [19]. The approach in [19], with the use of dual channel sampling, is able to solve the driver shoot-through problem, and the control delay can be considered completely compensated.

Fig. 9.Two basic approaches to reduce Td, (a) real-time sampling and (b) real-time loading.

E. Adding a Proper Phase Compensator

Since the control delay causes phase lag, adding a phase compensator in the feedback loop is able to improve the inner AD stability. The phase compensator can be a lead or high-pass filter. Fig. 10 gives the improved control, where Gh(s) is the phase compensator. The equivalent open-loop transfer function is:

Fig. 10.Structure of AD control with phase compensator.

In order to not amplify high-frequency noises, |Gh(jω)| at frequencies close to and above fres should be 1. The two 0dB-crossing frequencies are approximately equal to those in (8). Accordingly, PMx1 with Gh(s) is improved as:

The second-order high-pass filter (HPF) is expressed as:

where, ωh and ζ are the turn-over frequency and damping factor of the high-pass filter, respectively.

In order to make |Gh(jω)| at frequencies close to and above fres equal 1, ωh should be smaller than ωres. Moreover, considering variations in the filter parameters and grid impedance, the actual resonance frequency is largely reduced. In this case, ωh should ensure that the resonance components of the sampled signal are not filtered out by the high-pass filter because these components are necessary for active damping purposes [9]. Thus, ωh should be lower than the minimal value of ωres if the grid impedance varies widely. At the same time, ωh is also related with the compensation phase angle of (27). As shown in Fig. 11, the phase angle decreases with a decrease of ωh. In addition, if variations of filter parameters make ωres increase, the phase angle at the real ωres is decreased. As a result, the design of ωh needs to balance the robustness and the leading phase angle.

Fig. 11.Compensation angle of HPF with different ωh.

For the design of ζ, if a small value of ζ is used, the gain of (27) around ωh may exceed 1. Consequently, the high pass filter will potentially arouse harmonics in the case of noise disturbances. Thus, ζ should be larger than 0.6.

To obtain new values of ωdiv and KADMax, the compensation effect by adding Gh(s) is approximately seen as the decrease of Td. That is, the new delay time is equal to Td−Td_decreased, where the reduction Td_decreased can be calculated as:

F. Summary

The features of all of the approaches are synthesized in Table 2. Since the benefits and limitations are clearly known, the use of several approaches together may be a promising option. For instance, the reasonable decrease in both ωres and kAD (i.e., Approaches B & C) can result in a good balance among volume, cost and current harmonics rejection. This combination is not discussed further since it is just a specific choice of parameters. In addition to the above combination, adding an HPF in real-time sampling (i.e., Approaches D & E) is supposed to solve the aliasing of digital sampling without affecting the active damping of the LCL resonance.

TABLE IIFEATURES OF DIFFERENT APPROACHES

 

VI. VERIFICATIONS

In order to verify the correctness of the analysis and the feasibility of the presented approaches, experiments are done in a single-phase inverter. The system parameters are in Table 1 with C1=7 μF. The power switches are IGBTs K75T60 from Infineon. The digital sampling and control are implemented in a TI TMS320F28035 DSP. During the tests, the DC side is linked to a voltage source set at 400V. The AC side is connected to the commercial 220V/50Hz power grid. IGBTs IKW40N120T2 from INFINEON are used as the power switches. A photo of the inverter prototype is shown in Fig. 12.

Fig. 12.Photo of inverter prototype.

A. Design of the Parameters for the Tests

Firstly, a design without considering the digital delay is shown in Fig. 13 (the solid line). In this case a PI controller is used [1]. The design of the active damping factor follows [4] and [5]. The specific design results are that the proportional gain KP is 7.2, the integral time constant Ti of the PI controller is 0.0006, and the AD factor KAD is 13. From Matlab, PM is 61.2° and GM is 8.71dB.

Fig. 13.Bode plots with typical dual-loop current control for different control delay.

However, when the delay Td is considered (either Ts or 0.5Ts), the inner AD control no longer satisfies (15) so that a system with only inner AD control is unstable. As a result, the phase crosses the -180° line many times when Td is a one-sample delay (Ts, dash-dotted line in Fig. 13) or half of that (0.5Ts, dotted line in Fig. 13). If the design without a delay is still followed, the system cannot work stably because the required –180°-crossing does not exist. As discussed above, for the sake of stability and robustness, it is better to use improved approaches rather than simply adjusting the control parameters.

1) With Approach A: According to (15), the reassignment of the control frequency fs should satisfy:

With the use of (30), fs should be higher than 24.4 kHz to ensure that the inner-loop AD control is stable. From the view of signal sampling, fs should be an integer multiple of the switching frequency. Thus, fs has to be 30 kHz. However, in a DSP with the traditional implementation, the program needs to realize the detection and protection of various variables as well as the calculation of the PWM reference in 0.5/fs (16.7μs). In tests, the operating time required for each interrupt is measured to be 16~18μs. Thus, the burden of the DSP is too heavy if fs is increased higher. In addition, other interrupts in the DSP program also need time to run. In summary, for the prototype, Approach A is not applied.

2) With Approach B: Based on the requirement of (30), C1 has to be increased to 100μF. However, an excessive increase in C1 will amplify the effect that low-order harmonics in the grid voltage have on the grid current. For the prototype, Approach B will not be considered.

3) With Approach C: Approach C is not suitable for the case study because ωres is higher than ωdiv.

4) With Approach D: For this approach, the key question is how to determine the value of the delay time. At first, the lower limit of ωdiv is calculated as 3.826×104 rad/s by the bottom inequality in (30). Then, by substituting the lower limit of ωdiv into (13), the upper limit of Td is obtained. In the case of the parameters in Table 1 (C1=7 μF), the upper limit of Td is 0.116Ts. Therefore, the stability of the inner-loop AD control can be realized by using the real-time sampling or loading approach. It should be noted that the aliasing-induced harmonics in the real-time sampling are fairly large with a larger Td [14]. Thus, Td should be as small as possible. For the case study, the time of iC1 sampling and um calculation in the DSP is measured to be 4μs which is a little less than 0.1Ts. For a conservative design, Td is 0.1Ts in the test.

5) With Approach E: First, according to (26), to make the inner AD control stable, the basic principle is that the leading phase provided by the high-pass filter should be at least 56°. In case of ζ=0.6, ωh should be above 3000·2π rad/s. By increasing ζ, the phase angle is increased. For the case study, ωh is 6000π rad/s and ζ is 0.65, when |Gh(jωres)| is 66°.

In summary, the reassigned filter and control parameters are shown in Table III. Approaches D and E are further discussed and tested experimentally, while Approaches A and B are simply tested by simulations.

Table IIIPARAMETERS REASSIGNED FOR EVERY APPROACH

Fig. 14 shows the effects of the improved approaches. The real-time sampling (Td=0.1Ts, PM=34°, GM=5.9dB) and real-time loading (Td≈0, PM=34.7°, GM=6.43dB) approaches both solve the instability caused by the typical dual-loop control. The phase curve with Approach D crosses the –180° line only once, and the stability is easy to guarantee. With Approach E, the phase curve also crosses the –180° line only once, but the gain and phase margins are greatly reduced (PM=4.18°, GM=0.96dB). It is noticed that reductions of the stability margins are yielded because the cut-off frequency is needlessly increased. By adjusting Gc(s) to reduce the cut-off frequency, GM and PM are improved while the bandwidth is still the same as that with Approach D.

Fig. 14.Bode plots with different improved approaches.

B. Simulation Results

Approaches A and B are tested by simulations. As shown in Fig. 15, the traditional control results in resonance in the grid current while Approaches A and B both have the capability to stabilize the system.

Fig. 15.Simulation waveforms with different Approaches.

C. Experimental Results

Fig. 16 shows the results with the traditional dual-loop current control. The inverter cannot work stably, and there are a lot of resonance harmonics in the grid current, which could potentially trigger inverter protection.

Fig. 16.Experimental waveforms with traditional dual-loop current control.

Fig. 17 shows experimental waveforms with the improved approaches. It can be seen that the inverter runs stably with the real-time sampling approach. However, the grid current is affected by aliasing due to the discrete sampling. There are some low-frequency harmonics in the grid current. For the real-time loading approach, a better grid current quality is achieved because the signal sampling is located at the beginning of the control period, which is similar to the traditional control. With Approach E, as shown in Fig 17(c), the stability is improved. Note that a small amount of harmonics can be found in the current waveform, especially at the zero-crossing points, because the stability margins are not satisfactory if Gc(s) is unchanged. By slightly reducing the gain of Gc(s), the high-frequency oscillations at the zero-crossing points in Fig. 17(c)) disappear (the waveforms are not shown again).

Fig. 17.Experimental waveforms with improved approaches. (a) Approach D real-time sampling. (b) Approach D real-time loading. (c) Approach E.

It should be mentioned that inverter non-ideal factors (dead-time, turn-on-off delay time, conduction voltage drop, etc.) are harmful to the grid current quality. On the premise that the current control is stable with a proper stability margin, using some compensation methods can further improve the grid current quality [30]-[32].

 

VII. CONCLUSIONS

An in-depth study on the stability of capacitor current feedback AD for grid-connected LCL-filtered inverters is done in this paper. Then, stability criterions for the inner-loop AD and the dual-loop current control are given. Moreover, the robust design of the dual-loop current control is discussed both when the inner-loop AD is stable and when it is not. Analysis shows that ensuring the stability of the inner-loop AD is beneficial for simplifying the difficulty in dual-loop control design and for improving system robustness. Based on the theoretical analysis, several approaches are presented to improve system stability and robustness. Finally, the correctness of the investigations and the effectiveness of the improved approaches are verified in a practical application. Among the improved approaches, the use of a high-pass filter and the approach of reducing the delay are able to optimize the system using the control parameters designed without considering the delay. It is noted that the phase margin with the high-pass filter approach can be further improved by slightly adjusting the current controller without compromising the bandwidth. Given that DSP capability is much better than in the past, the real-time loading approach or the real-time sampling approach with a high-pass filter is a promising way to simplify the parameter design and to improve the performance.

References

  1. J. Dannehl, C. Wessels, and F. Fuchs, “Limitations of voltage-oriented pi current control of grid-connected PWM rectifiers with LCL filters,” IEEE Trans. Ind. Electron., Vol. 56, No. 2, pp. 380-388, Feb. 2009. https://doi.org/10.1109/TIE.2008.2008774
  2. X. Guo, X. You, X. Li, R. Hao, and D. Wang, “Design method for the LCL filters of three-phase voltage source PWM rectifiers,” Journal of Power Electronics, Vol. 12, No. 4, pp. 559-566, Jul. 2012. https://doi.org/10.6113/JPE.2012.12.4.559
  3. F. Liu, Y. Zhou, S. Duan, J. Yin, B. Liu, and F. Liu, “Parameter design of a two-current-loop controller used in a grid-connected inverter system with LCL filter,” IEEE Trans. Power Electron., Vol. 56, No. 11, pp. 4483-4491, Nov. 2009.
  4. Y. Tang, P. C. Loh, P. Wang, F. H. Choo, F. Gao, and F. Blaabjerg, “Generalized design of high performance shunt active power filter with output LCL filter,” IEEE Trans. Ind. Electron., Vol. 59, No. 3, pp. 1443-1452, Mar. 2012. https://doi.org/10.1109/TIE.2011.2167117
  5. J. Xu, S. Xie, and T. Tang, “Evaluations of current control in weak grid case for grid-connected LCL-filtered inverter,” IET Power Electron., Vol. 6, No. 2, pp. 227-234, Feb. 2013. https://doi.org/10.1049/iet-pel.2012.0192
  6. Y. Han, P. Shen, and J. M. Guerrero, “Stationary frame current control evaluations for three-phase grid-connected inverters with PVR-based active damped LCL filters,” Journal of Power Electronics, Vol. 16, No. 1, pp. 297-309, Jan. 2016. https://doi.org/10.6113/JPE.2016.16.1.297
  7. J.B. Kwon, S.J. Yoon, and S. Choi, “Indirect current control for seamless transfer of three-phase utility interactive inverters,” IEEE Trans. Power Electron., Vol. 27, No. 2, pp. 773-781, Feb. 2012. https://doi.org/10.1109/TPEL.2011.2161335
  8. M. Malinowski and S. Bernet, “A simple voltage sensorless active damping scheme for three-phase PWM converters with an LCL filter,” IEEE Trans. Ind. Electron., Vol. 55, No. 4, pp. 1876-1880, Apr. 2008. https://doi.org/10.1109/TIE.2008.917066
  9. J. Xu, S. Xie, and T. Tang, “Active damping-based control for grid-connected LCL-filtered inverter with injected grid current feedback only,” IEEE Trans. Ind. Electron., Vol.61, No.9, pp. 4746-4758, Sep. 2014. https://doi.org/10.1109/TIE.2013.2290771
  10. X Wang, F. Blaabjerg, and P. Loh, “Grid-current-feedback active damping for LCL resonance in grid-connected voltage source converters,” IEEE Trans. Power Electron., Vol. 31, No. 1, pp. 213-223, Jan. 2016. https://doi.org/10.1109/TPEL.2015.2411851
  11. L. A. Maccari Jr., J. R. Massing, L. Schuch, C. Rech, H. Pinheiro, R. C. L. F. Oliveira, and V. F. Montagner, “LMI-based control for grid-connected converters with LCL filters under uncertain parameters,” IEEE Trans. Power Electron., Vol. 29, No. 7, pp. 3776-3785, Jul, 2014. https://doi.org/10.1109/TPEL.2013.2279015
  12. J. Xu, S. Xie, and T. Tang, “Systematic current control strategy with pole assignment for grid-connected LCL-filtered inverters,” Journal of Power Electronics, Vol. 13, No. 3, pp. 447-257, May 2013. https://doi.org/10.6113/JPE.2013.13.3.447
  13. J. Dannehl, F. W. Fuchs, S. Hansen, and P. B. Thøgersen, “Investigation of active damping approaches for PI-based current control of grid-connected pulse width modulation converters with LCL filters,” IEEE Trans. Ind. Appl., Vol. 46, No. 4, pp. 1509-1517, Jul./Aug. 2010. https://doi.org/10.1109/TIA.2010.2049974
  14. D. Pan, X. Ruan, C. Bao, W. Li, and X. Wang, “Capacitor-current-feedback active damping with reduced computation delay for improving robustness of LCL-type grid-connected inverter,” IEEE Trans. Power Electron., Vol. 29, No. 7, pp. 3414-3427, Jul. 2014. https://doi.org/10.1109/TPEL.2013.2279206
  15. J. Xu, S. Xie, J. Kan, and B. Zhang, "Research on stability of grid-connected LCL-filtered inverter with capacitor current feedback active damping control," in Proc. ICPE-ECCE Asia, pp. 682-687, 2015.
  16. M. Orellana and R. Grino, "On the stability of discrete-time active damping methods for VSI converters with a LCL input filter," in Proc. IEEE IECON, pp.2378-2383, 2012.
  17. X. Li, X. Wu, Y. Geng, X. Yuan, C. Xia, and X. Zhang, “Wide damping region for LCL-type grid-connected inverter with an improved capacitor-current-feedback method,” IEEE Trans. Power Electron., Vol. 30, No. 9, pp. 5247-5259, Sep. 2015. https://doi.org/10.1109/TPEL.2014.2364897
  18. R. Li, B. Liu, S. Duan, C. Zou, and L. Jiang, “Analysis and suppression of alias in digitally controlled inverters,” IEEE Trans. Ind. Informat., Vol. 10, No. 1, pp. 655-665, Feb. 2014. https://doi.org/10.1109/TII.2013.2279498
  19. D. Yang, X. Ruan, and H. Wu, “A real-time computation method with dual sampling modes to improve the current control performances of the LCL-type grid-connected inverter,” IEEE Trans. Ind. Electron., Vol. 62, No. 7, pp. 4563-4572, Jul. 2015. https://doi.org/10.1109/TIE.2014.2327575
  20. Z. Zou, Z. Wang, and M. Cheng, “Modeling, analysis, and design of multifunction grid-interfaced inverters with output LCL filter,” IEEE Trans. Power Electron., Vol. 29, No. 7, pp. 3830-3839, Jul. 2014. https://doi.org/10.1109/TPEL.2013.2280724
  21. M. Wagner, T. Barth, R. Alvarez, C. Ditmanson, and S. Bernet, “Discrete-time active damping of LCL-resonance by proportional capacitor current feedback,” IEEE Trans. Ind. Appl., Vol. 50, No. 6, pp. 3911-3920, Nov./Dec. 2014. https://doi.org/10.1109/TIA.2014.2313661
  22. W. Lu, N. Zhao, J. Wu, A. El Aroudi, and L. Zhou, “Filterbased perturbation control of low-frequency oscillation in voltage-mode H-bridge DC/AC inverter,” Int. J. Circ. Theor. Appl., Vol. 43, No.7, pp. 866-874, July 2015. https://doi.org/10.1002/cta.1977
  23. B. Lei, G. Xiao, X. Wu, Y. Kafle and L. Zheng, “Bifurcation analysis in a digitally controlled H-bridge grid-connected inverter,” Int. J. Bifurcat. Chaos, Vol. 24, No. 1, pp. 1-15, Jan. 2014. https://doi.org/10.1142/S0218127414500023
  24. X. Wu, G. Xiao, and B. Lei, “Simplified discrete-time modeling for convenient stability prediction and digital control design,” IEEE Trans. Power Electron., Vol. 28, No. 11, pp. 5333-5342, Nov. 2013. https://doi.org/10.1109/TPEL.2013.2245514
  25. B. Lei, G. Xiao, X. Wu, and L. Zheng, “A unified “scalar” discrete-time model for enhancing bifurcation prediction in digitally controlled H-bridge grid-connected inverter,” Int. J. Bifurcat. Chaos, Vol. 23, No. 7, pp. 1-17, Jul. 2013. https://doi.org/10.1142/S0218127413501265
  26. S. Yang, Q. Lei, F. Z. Peng, and Z. Qian, “A robust control scheme for grid-connected voltage-source inverters,” IEEE Trans. Ind. Electron., Vol. 58, No. 1, pp. 202-212, Jan. 2011. https://doi.org/10.1109/TIE.2010.2045998
  27. D. Pan, X. Ruan, and C. Bao, “Optimized controller design for LCL-Type grid-connected inverter to achieve high robustness against grid-impedance variation,” IEEE Trans. Ind. Electron., Vol. 62, No. 3, pp. 1537-1547, Mar. 2015. https://doi.org/10.1109/TIE.2014.2341584
  28. J. Xu, S. Xie, and T. Tang, “Improved control strategy with grid-voltage feedforward for LCL-filter-based inverter connected to weak grid,” IET Power Electron., Vol. 7, No. 10, pp. 2660-2671, Oct. 2014. https://doi.org/10.1049/iet-pel.2013.0666
  29. P. Alemi, S.-Y. Jeong, and D.-C. Lee, “Active damping of LLCL filters using PR control for grid-connected threelevel T-type converters,” Journal of Power Electronics, Vol. 15, No. 3, pp.786-795, May 2015. https://doi.org/10.6113/JPE.2015.15.3.786
  30. J.M. Guerrero, M. Leetmaa, F. Briz, A. Zamarron, and R.D. Lorenz, “Inverter nonlinearity effects in high-frequency signal-injection-based sensorless control methods,” IEEE Trans. Ind. Appl., Vol. 41, No. 2, pp. 618-626, Mar./Apr. 2005. https://doi.org/10.1109/TIA.2005.844411
  31. H. Zhao, Q.M.J. Wu, and A. Kawamura, “An accurate approach of nonlinearity compensation for VSI inverter output voltage,” IEEE Trans. Power Electron., Vol. 19, No. 4, pp. 1029-1035, July 2004. https://doi.org/10.1109/TPEL.2004.830072
  32. J. Xu, T. Tang, and S. Xie, “Research on low-order current harmonics rejections for grid-connected LCL-filtered inverters,” IET Power Electron., Vol.7, No.5, pp. 1227-1234, May 2014. https://doi.org/10.1049/iet-pel.2013.0477

Cited by

  1. LCL-resonance damping strategies for grid-connected inverters with LCL filters: a comprehensive review 2017, https://doi.org/10.1007/s40565-017-0319-7
  2. Design of LCL-filter considering the control impact for grid-connected inverter with one current feedback only vol.10, pp.11, 2017, https://doi.org/10.1049/iet-pel.2016.0849
  3. Adaptive Feedforward Algorithm Without Grid Impedance Estimation for Inverters to Suppress Grid Current Instabilities and Harmonics Due to Grid Impedance and Grid Voltage Distortion vol.64, pp.9, 2017, https://doi.org/10.1109/TIE.2017.2711523
  4. Robust Grid Current Control With Impedance-Phase Shaping for LCL-Filtered Inverters in Weak and Distorted Grid vol.33, pp.12, 2018, https://doi.org/10.1109/TPEL.2018.2808604
  5. Research on Resonance Mechanism and Suppression Technology of Photovoltaic Cluster Inverter vol.11, pp.4, 2018, https://doi.org/10.3390/en11040938