Abstract
Purpose: The study is to measure indoor air pollutants concentration of existing housing and to analyze the causes and assess in accordance with the government's criteria. The research result could be used as data for public health through indoor air quality management of existing housing and more as a reference for new housing. Method: It was investigated 24 middle class housings of metropolitan area in summer which have been built for the past 30 years. Concentration of HCHO, TVOC was investigated in living room at morning and night and concentration of $CO_2$ was investigated in living room and master bedroom at morning and night. SKT100-X5 was used for concentration of HCHO, TVOC and ZGm053UK for concentration of $CO_2$. Result: Average concentration of TVOC was 1.31 times more than that of HCHO and standard deviation of that was 1.73 times higher. Average concentration of $CO_2$ was almost nearly close to 1,000ppm being criteria of the Ministry of Environment.