초록

Purpose: The purpose of this study is to identify the effect of Progressive Space Organization (ante-rooms) in Negative Pressured Isolation Unit(NPIU) such as National and Regional Isolation Units in Korea in order to build basic data for the evidence based design of Airborne Infection Isolation Units which should prepare and respond effectively to the public health crisis due to the hazardous airborne infectious disease. Methods: 1) Gas(SF6) test and analysis on the 23 Korean Isolation Units under operation. 2) Assessment of the isolation level of the space components by checking the Gas concentration. 3) Analysis of the Isolation Effectiveness according to Space Organizational levels. Results: 1) The higher segregation level is, the lower Gas(SF6) concentration is. 2) Too many segregations(anterooms) of Isolation Unit are not efficient for the prevention of infectious bacillus spread. For example, 4 level of segregation has similar segregation effect to the 3 level of segregation. Implications: Many anterooms in front of the isolated patient bedroom will guarantee the safe environment against the danger of hazardous airborne nosocomial infection. On the other hand, too many segregations is inefficient, expensive, inconvenient, narrow(unflexible) and so on. This study can be used as basic data for further development of design guidelines of isolation units.

키워드

참고문헌

  1. Centers for Disease Control and Prevention(CDC) and Healthcare Infection Control Practices Advisory Committee(HICPAC), 2003. Guidelines for Environmental Infection Control in Health-Care Facilities
  2. European Network for Highly Infectious Diseases, Manual for the safe and appropriate management of Highly Infectious Disease patients in isolation facilities
  3. Kowalski, Wladyslaw, 2002, Immune Building Systems Technology - Appendix A : Database of Biological Weapon Agents
  4. The Facility Guidelines Institute(FGI), 2014, Guidelines For Design and Construction of Health Care Facilities.
  5. Victorian Advisory Committee on Infection Control, 2007, Guidelines for the classification and design of isolation rooms in health care facilities
  6. 권순정, 2016.10, 중증 호흡기 감염병 진료를 고려한 음압격리병동부의 건축계획, 한국의료복지건축학회지, 22권 3호
  7. 김영주, 김희갑, 2007, 환경통계학
  8. 법제처, 감염병의 예방 및 관리에 관한 법률, 2015.12.29
  9. 보건복지부, 한국의료복지건축학회, 2013, 지역거점 공공병원 병동부 건축계획기준개발
  10. 아주대학교 산학협력단, 2012, 2012년도 공중보건위기사업단 운영 최종보고서
  11. 연세대학교 의료법윤리학연구원, 2013, 의료기관 시설기준 개선방안 연구용역 최종보고
  12. 질병관리본부, 2011, 국가지정입원치료(격리)병상 운영과 관리
  13. 질병관리본부, 2011, 지역별 거점병원 운영과 관리
  14. 한양대학교 산학협력단, 2013, 2013년도 공중보건위기사업단 운영 최종보고서
  15. 日本醫療福祉施設協會, 2013, 病院空調設備의 設計 및 管理指針(HEAS-02-2013)
  16. 放射線醫學綜合硏究所, 라돈 濃度測定.線量平價委員會, 1998, 日本勞動厚生省, 2004, 感染症指定医療機関の施設基準の手引き

피인용 문헌

  1. An Exploratory Research to Propose Design for Infection-Free School vol.21, pp.3, 2016, https://doi.org/10.12813/kieae.2021.21.3.025
  2. 거주 후 평가를 통한 국가지정 입원치료병상 시설 개선 방향 도출에 관한 연구 vol.27, pp.3, 2016, https://doi.org/10.15682/jkiha.2021.27.3.39