DOI QR코드

DOI QR Code

수돗물 부식성 제어를 통한 수도관 부식방지 : 부식억제제별 효과와 영향에 대한 분석

Corrosion Control in Water Pipes by Adjusting the Corrosivity of Drinking Water : Effect and impact of the Corrosion Inhibitor

  • 투고 : 2016.12.21
  • 심사 : 2016.12.29
  • 발행 : 2016.12.31

초록

The tap water used in Seoul was found to be corrosive. Its corrosivity was effectively reduced by that the additions of alkali agent such as NaOH, $Ca(OH)_2$ and corrosion inhibitor such as $H_3PO_4$. For the corrosion test, carbon steel pipe 50 m long was exposed to the drinking water produced by a pilot plant at $36.5^{\circ}C$, similar to the existing process where it takes about 20 minutes to reduce the initial chlorine content of 0.5 mg/L to 0.05 mg/L. $CO_2$ and $Ca(OH)_2$ was added not only to control the Langelier index (LI) above -1.0 and but also, to increase the duration time of residual chlorine by about 6 times. The persistence effect of residual chlorine was in the order of $H_3PO_4$ > $Ca(OH)_2$ > NaOH. Measurements of weight loss showed that corrosion inhibition was effective in order of $Ca(OH)_2$ > $H_3PO_4$ > NaOH > no addition, where the concentrations of $Ca(OH)_2$ and phosphate were 5 ~ 10 mg/L (as $Ca^{2+}$) and 1 mg/L (as $PO{_4}^{3-}$), respectively.

키워드

참고문헌

  1. EPA, Drinking Water Requirements for States and Public Water Systems, http://www.epa.gov/dwreginfo/lead-and-copper-rule.
  2. Japan Drinking Water Corrosion Inhibitor Association, Corrosion Inhibitors in Water Pipes, http://www.kyusuihozen.gr.jp/akamizu/about_bouseizai.htm.
  3. K. Y. Song, 2014 Water Quality Monitoring Items Report, WQR-791(2014.4.7.), Seoul Water Institute (2014).
  4. K. Y. Song, 2014 Water Quality Monitoring Items Report, WQR-3401(2014.7.8.), Seoul Water Institute (2014).
  5. K. Y. Song, 2014 Water Quality Monitoring Items Report, WQR-5755(2014.10.6.), Seoul Water Institute (2014).
  6. H. S. Kwon, 2015 Water Quality Monitoring Items Report, DEC-20(2016.1.6.), Seoul Water Institute (2016).
  7. ASTM Standards G1, Standard Practice for Preparing, Cleaning, and Evaluating, Corrosion Test Specimens, Houston (1996).
  8. T. E. Larson, and R. V. Skold, J. Am. Water Works Ass., 49, 1294 (1957).
  9. L. S. McNeill, and M. Edwards, J. Am. Water Works Ass., 93, 88 (2001).
  10. Y. B. Park, Y. J. Choi, B. G. Huh, H. G. Park, and I. S. Park, Proceedings of the 2009 Spring Meeting and Power Plant Symposium on the Corrosivity Reducing Technologies and Control Methods of Drinking Water, p. 61, CSSK, Gwangju, Korea (2009).
  11. AWWARF & DVGW, Internal Corrosion of Distribution Systems, 2nd ed., p. 406, AWWARF, Denver (1996).
  12. J. C. Ahn, C. M. Park, and J. Y. Koo, J. Korean Soc. Water Wastewater, 19, 487 (2005).
  13. M. Batte, B. Koudjonou, P. Laurent, L. Mathieu, J. Coallier, and M. Prevost, Water Res., 37, 1351 (2003). https://doi.org/10.1016/S0043-1354(02)00476-1
  14. E. E. Stansbury, and R. A. Buchanan, Fundamentals of Electrochemical Corrosion, p. 62, ASM International, OH (2000).
  15. Y. B. Park, Y. J. Choi, B. G. Huh, H. G. Park, I. S. Park, and Y. S. Park, Proceedings of the 2009 Autumn Meeting and Symposium&Forum on the Effects of Water Vapor Dissolved Chlorime Gas for Stainless Steel Corrosion, p. 51, CSSK, Jeju (2009).
  16. EPA 815-R-99-013, Disinfection Profiling and Benchmarking Guidance Manual, p. 3-3, US EPA (1999).
  17. G. Bowman, and R. Mealy, The Fundamentals of Chlorine Chemistry and Disinfection (2007).
  18. http://www.epa.gov/dclead/zinc_ortho.htm, September 27th (2004).

피인용 문헌

  1. 수돗물 부식성 제어를 통한 수도관 부식방지기술: 석회수 분산화장치를 이용한 미네랄 공급 효과와 영향 분석 vol.32, pp.3, 2018, https://doi.org/10.11001/jksww.2018.32.3.235