A Magnetic Energy Recovery Switch Based Terminal Voltage Regulator for the Three-Phase Self-Excited Induction Generators in Renewable Energy Systems

  • Wei, Yewen (New Energy Research Center, Electric Power College, South China University of Technology) ;
  • Kang, Longyun (New Energy Research Center, Electric Power College, South China University of Technology) ;
  • Huang, Zhizhen (New Energy Research Center, Electric Power College, South China University of Technology) ;
  • Li, Zhen (New Energy Research Center, Electric Power College, South China University of Technology) ;
  • Cheng, Miao miao (College of Electrical and Information Engineering, Hunan University)
  • Received : 2014.10.06
  • Accepted : 2015.05.08
  • Published : 2015.09.20

Abstract

Distributed generation systems (DGSs) have been getting more and more attention in terms of renewable energy use and new generation technologies in the past decades. The self-excited induction generator (SEIG) occupies an important role in the area of energy conversion due to its low cost, robustness and simple control. Unlike synchronous generators, the SEIG has to absorb capacitive reactive power from the outer device aiming to stabilize the terminal voltage at load changes. This paper presents a novel static VAR compensator (SVC) called a magnetic energy recovery switch (MERS) to serve as a voltage controller in SEIG powered DGSs. In addition, many small scale SEIGs, instead of a single large one, are applied and devoted to promote the generation efficiency. To begin with, an expandable mathematic model based on a d-q equivalent circuit is created for parallel SEIGs. The control method of the MERS is further improved with the objective of broadening its operating range and restraining current harmonics by parameter optimization. A hybrid control strategy is developed by taking both of the stand-alone and grid-connected modes into consideration. Then simulation and experiments are carried out in the case of single and double SEIG(s) generation. Finally, the measurement results verify that the proposed DGS with SVC-MERS achieves a better stability and higher feasibility. The major advantages of the mentioned variable reactive power supplier, when compared to the STATCOM, include the adoption of a small DC capacitor, line frequency switching, simple control and less loss.

Keywords

I. INTRODUCTION

With ever-increasing concerns over environmental pollution and energy shortages, the development of renewable energy resources have attracted wide interest due to its advantages of being abundant in nature and nearly pollutant free. Small scale wind turbines and hydro turbines are widely installed in distributed generation system (DGS) for remote or isolated areas without grid coverage. The self-excited induction generator (SEIG) is usually applied in DGSs due to its reduced installation cost, lower maintenance requirements, absence of a power supply for excitation and natural protection against system overcurrent [1]. However, when compared with a synchronous generator, the voltage instability and poor efficiency of a SEIG limit its application a lot. In order to steady the voltage, fixed-capacitors (FCs) and dynamic reactive power compensators (DRPCs) are needed for building no-load voltage and for compensating reactive power when a load is fluctuating. Moreover, a feasible approach for promoting generation efficiency is to keep each SEIG outputting its rated power.

Some DRPCs, like thyristor switched capacitors (TSCs), thyristor controlled reactors (TCRs) and static synchronous compensators (STATCOMs), have already been designed to regulate the terminal voltage of induction generators. In [2] and [3], the TSC and TCR are applied in a SEIG power system and a proportional integral (PI) closed-loop feedback is used to realize reference voltage tracking. These articles provide a valuable method for line frequency control. However, triple sized reactors and big capacitors are employed and unacceptable current harmonics are produced at the same time. The STATCOM, as a popular DRPC, is capable of generating inductive or capacitive reactive power. Even though it has a low current distortion rate and a good dynamic response characteristic, it suffers from high frequency switching and a complicated space vector pulse width modulation (SVPWM) control [4]-[6]. Thyristor controlled series capacitors (TCSC) [7], static synchronous series compensator (SSSC) [8] and unified power flow controller (UPFC) [9] have also succeeded in continuous reactive power regulation or power factor correction (PFC). However, they are actually compounded by TSCs or TCRs or STATCOMs and are unfit for low power applications in view of their installation cost.

In consideration of the SEIG, two kinds of mathematic models have been concluded from a lot of articles published in recent years [10]-[14]. For 3-Ф SEIGs, every phase is simplified as a voltage source, a series resistance and a series inductance, and this is named the RX model [15]. The RX model is convenient for steady state analysis but it cannot reflect the dynamic characteristic and it increases the complicacy of modeling in parallel SEIG systems. By considering the variation of the magnetizing inductance caused by loads perturbations, state space modeling is studied in reference [16]. An open matrix model, which is fit for any number of parallel SEIGs, is presented in [17]. This is devoted to an analysis of the steady state and transient performance. With the application of the synchronous rotating coordinate conversion (SRCC), the active power and reactive power current component are easy to work out.

This paper proposes a hybrid renewable energy DGS, which mainly utilizes small-scale wind and water power generation, employs parallel connected SEIGs for energy transformation and a novel SVC device called a magnetic energy recovery switch (MERS) for voltage regulation. First, an expandable model is set up for n parallel SEIGs based on the SRCC. Then, the operating principle is introduced for the MERS. In order to broaden its operating range and to restrain current harmonics, an improved control method is studied by parameter optimization. The control strategy, when the DGS stands alone or is connected to a grid, is developed. Simulations and experiments are carried out to validate the performance of the MERS as a voltage regulator. The obtained experimental results support that the proposed DGS with a SVC-MERS has better stability and a higher feasibility.

 

II. MATHEMATIC MODEL OF PARALLEL SEIGS

Since the integration of many small-scale SEIGs is more flexible and efficient under load changes, n different SEIGs are applied here and the d-q equivalent circuit of the proposed DGS is shown in Fig. 1. The MERS, denoted by CMERS, works as a controllable capacitance. The FC, denoted by CFC, is used to build the terminal voltage when the SEIG is not loaded. The variable load of the DGS is simplified as an inductance (L) and a resistance (R). The parameters are introduced for the SEIG in Table І in which j is the sequence number.

Fig. 1.D-q axis equivalent circuit of the proposed parallel SEIGs using MERS to regulate terminal voltage

TABLE ІVARIABLE DESCRIPTION FOR SEIG

Based on the state space model and the open matrix model which are mentioned above, a kind of state space matrix is proposed to model parallel SEIGs as shown by equation (1). If j can be 1, 2, to n, the matrix of variables are defined as follows:

Coefficient matrixes, such as [Gj], [Zj] and [Bj], are expressed in Appendix. For each SEIG, the relationship between Lmj and Imj can be represented by the following equation:

Where aj0~aj4 are constants. However, they are not fixed in different SEIGs. This model is used for simulation in chapter V.

 

III. MAGNETIC ENERGY RECOVERY SWITCH

In view of current bi-directional control, the full-bridge type MERS is adopted in this paper. Paper [18] points out that the equivalent capacitance can theoretically be regulated from 0 to infinity by changing the firing angle. It has been employed to correct the power factor or to stabilize terminal voltage of the inductions generator [19]-[22]. However, some shortcomings have gradually emerged such as an incomplete mathematical model, unacceptable harmonics, hard to realize accuracy control and a limited operating range. This section aims to rebuild the mathematic model and to broaden the regulating range.

A. Principle and Mathematic Model

A schematic of the single phase MERS is shown on the left-top corner of Fig. 2. It consists of four insulated-gate bipolar transistors (IGBTs) (G1~G4), a small DC capacitor (Cdc) and a reactor (Llim.). In order to prevent the capacitor from being shorted, no more than two IGBTs can be opened at the same time. With the phase delay control, the parallel MERS works as a controllable capacitor and its equivalent circuit is also presented below the schematic in Fig. 2. CMERS is the equivalent capacitance. Rline is the line resistance. UL, UR, US and UMERS are the voltage of the power source, load, line resistance and MERS, respectively. IMERS represents the current. The waveforms of US, UMERS and IM are plotted on the right side of Fig. 2 in which the dotted line is the fundamental current.

Fig. 2.Schematic and waveforms of single phase MERS.

In reference [19], a MERS is used as a series compensator to regulate the power factor of an AC system and a mathematic model is built by taking the current phase for a reference. In terms of shunt compensation, this model needs to be rebuilt by taking the source voltage phase for a reference instead of the current phase. In addition, the traditional control always gets a high rate of current distortion and overvoltage of the DC capacitor [19]-[22]. These disadvantages lead its regulating range being limited a lot.

Taking the phase of US as a reference, G1 and G3 are turned on with an alpha (α) delayed. Then, Cdc starts to be charged. When VC is less than VC-min, G3 is turned off but G1 is kept open until the US phase comes to π+α. When G2 and G4 are turned on, the next half cycle can carry out with a similar process except that the current flow is reversed.

Since its waveform is obviously symmetrical to the vertical axis in Fig. 2, the MERS current can be defined as equation (4) by the fast Fourier transform (FFT).

Where IRMS-n is the RMS value of the nth harmonic. ω = 2πf, f is the system frequency. The MERS voltage is formulated as:

Where θ =ωt, XCdc = 1/(ωCdc), equation (4) can be unfolded and expressed as equation (5) by using the FFT again.

In addition, the RMS value of the fundamental voltage can be described as:

Finally, the equivalent capacitive reactance is obtained as:

B. Variable Reactive Power Characteristic

In view of the negligible line resistance, the reactive power of the MERS branch is denoted by:

Where E is the RMS value of the source voltage, XMERS = kx ‧XC and XL = k0 ‧XC , k0 is a constant, and kx is a variable decided by α and VC-min as deduced in equation (7). F is defined as a function with double variables, Q0 =ωCE2.

The complexity of XMERS brings great difficulty in terms of ascertaining the function F. To study the characteristic of the output reactive power, a single phase MERS has been modeled in PSIM with the parameters shown in Table II.

TABLE IISINGLE PHASE MERS SPECIFICATIONS

An array of simulation results, by means of regulating α and VC-min continuously and separately, has been measured. It has been traced out to compare with the theoretical curves obtained from equation (7) and (8) a shown in Fig. 3. The features of Qout between α and VC-min include: (i) While VC-min is equal to zero, Qout keeps growing exponentially with a rising α. (ii) While α is fixed as a constant, Qout decreases linearly as VC-min increases. With the utilization of the linear fitting method, the proposed function F can be described as:

In which Kα, Tx and KV can be figured out by using the least square method (LSM).

Fig. 3.Equivalent capacitance feature of single phase MERS.

C. Control Parameters Optimization

Although the scope of the variable capacitance is theoretically unlimited, it only operates in a small range on account of the unavoidable ascending current harmonics in practical applications. Nevertheless, optimizing the selection of the control parameters may make it possible to reduce the production of current harmonics and it is a unique method for widening the adjusting range of a MERS to some extent. Another challenge when charging current, is the voltage of the DC capacitor which becomes too high. This is caused by the increasing to withstand itself and the IGBTs. Moreover, the current limiting reactor has a significant impact on the current quality and compensation range of the capacitive reactive power. Two solutions, regarding all of these problems, have already been enforced and they have achieved a distinct effect in terms of improving the performance of a MERS. They are introduced in detail below:

1) Make the Match of the Control Parameters - (α, VC-min): In reference [21] and [22], the expected Qout is carried out through altering α or VC-min asynchronously. This implies that VC-min is forced to zero when α is adjustable and vice versa. This simple manner has disadvantages such as: (i) it is not possible to restrain current harmonics once the aim of Qout is ascertained. (ii) The maximum α, as well as the largest Qout, is mainly confined due to the finite ability of capacitive pressure. (iii) The growth rate of the current total harmonic distortion (THD) appears too fast to be accepted as introduced in reference [15].

In consideration of the rebuilt MERS voltage equation (6), the combination control method upon α and VC-min is probably effective in perfecting the system performance. Due to an increase of α or VC-min , which leads to an entirely opposite effect on the reactive power production, there are at least two ways to get the expected Qout. In other words, any Qout can be acquired either by regulating VC-min, by adjusting α, or by changing them both at the same time. There are many operating points on the equivalent power line (EPL) which get the same reactive power. Thus, one can be selected to suppress current harmonic or to avoid DC-capacitor overvoltage or breakdown. To realize the same reactive power output, two points on an EPL (5.31kVar) are applied and the characteristics via comparing the MERS voltage and current have been displayed in Fig. 4. The MERS peak voltage of point (250, 0V) is higher than that of point (280, 58V). The amplitude of the right side current appears lower than that of the left current. However, the triple harmonic is apparently reduced at point VC-min ≠ 0. This proves that there really exists an optimum point, by combining α and VC-min, on an EPL to meet the special requirements for improving MERS performance.

Fig. 4.Comparison of MERS peak voltage and current harmonics at different operation points.

2) Choose a Suitable Reactor: Generally speaking, a reactor is devoted to slow down the growth of the charging/discharging current for a parallel MERS. A large inductive reactance would neutralize the emitted capacitive reactive power which will in turn narrow the compensation range. Therefore, the proportionality coefficient k0 mentioned in equation (8) should be prudently selected.

Table III, in which the 3rd harmonic is excluded from the current, reflects the relationship between k0 , THDi and Qout by simulation. Both the THDi and Qout gradually decline at any of the same working points when k0 keeps ascending. Regardless of how the reactor changes, the THDi increases alone with α or VC-min becomes larger and larger. In conclusion, the coefficient k0 is determined by the maximum THD of the MERS current. Based on the above analysis, multiple purposes ought to be satisfied for the control parameters optimization and are stated as follows:

Where Q(α, Vc-min ) means the generated reactive power at any working point. The first formula is elicited from equation (9). The third formula limits any dc capacitor voltage not above VC-max. The last one implies that current distortion rate must be lower than the acceptable THDmax.

TABLE IIICHARACTERISTICS OF DIFFERENT REACTORS EMPLOYED

3) Search for the Most Suitable α and VC-min: With the application of synchronous control, response speed of a MERS as a DRPC is hard to accelerate unless the precision of every controlling cycle is enhanced. In view of the α changed in discrete from, the output reactive power must be discontinuous. Therefore, the expected Qout can be divided into two parts as follows:

Where Qα is generated by α. ΔQ is an error adjusted by VC-min.

Actually, α and VC-min are complementary in terms of producing continuous reactive power as shown in Fig. 5. The dotted line is a cluster of EPL. In the process of the reactive power changed from Qj-1 to Qj, α is first increased to reach the EPL Qα , and then VC-min is regulated to reach the target value, Qout. The third step is searching for the most suitable point based on equation (9). In Fig. 5, the bold solid lines mean the practical searching path for obtaining the most suitable working point. The special VC-min can be calculated by V0+KΔQ, in which V0 and K are constants which are worked out by the linear fitting method (LFM).

Fig. 5.Approach applied to search the most suitable EPL point

4) Improved Performance as a Shunt DRPC: With the proposed parameters optimization control, a lot of working points for the MERS are increased. When compared to reference [21], every Qout corresponds to an EPL line but not a single point. Furthermore, the regulating range of XMERS is broadened and satisfies the conditions of the THDi and VC-peak limitations of grid. The curves, as measured by simulation, reveal the effect as shown in Fig. 6(a) and Fig. 6(b). The dotted lines, with the application of the control method mentioned in reference [21], are measured for comparison. When the THDi is lower than 6.0% and VC-peak does not exceed double VC0, the maximum XMERS rises from 1.2 p.u to 1.4 p.u, and the minimum XMERS declines from 0.7 p.u to 0.35 p.u. VC0 is the capacitor peak voltage of the working point (00, 0V).

Fig. 6.Comparison of regulating range of XMERS.

D. Development of Three-Phase MERSs

For a 3-Ф system, three MERSs are used, as shown in Fig. 7, and connected in delta formation for eliminating the triple current harmonics. The load is equivalent to a changeable resistance and inductance. Power can also flow into the AC grid by operating switch ‘S’ in case it is needed. Each MERS is controlled independently and IGBTs in the same position but in different MERSs are switched by three-phase symmetrical signals. Therefore, only four control signals needs to be supplied even though double the number of switches is used when compared to STATCOMs. In addition, the MERS works in the line frequency and generates less switching loss. With the help of FCs, the 3-Ф MERSs can supply a large range of reactive power for SEIG power systems. A kind of multiple SEIGs power system is going to be studied and tested by simulation and experiments in section V.

Fig. 7.Schematic of SEIG-based power system using a three phase MERSs as a voltage or reactive power regulator.

 

IV. SYSTEM CONTROL

In order to achieve voltage phase detection and magnitude measurement, the phase lock loop (PLL) technique is studied in this section. Then, a d-q model of the three phase delta-connected MERSs is created and a uniform control strategy is proposed for voltage regulation under the state of stand-alone operation and power factor correction in the case of connection to the grid.

A. Phase Lock Loop Technique

Assume that the input three phase voltages are three cosine functions with the same amplitude (Um), but with phases delayed 1200 in sequence. Therefore, a new equation is obtained as:

Where θ is the synchronous phase of the voltage, and θ* is the actual phase. When the error between θ and θ* becomes very small, vd and vq tend to be Um and Um‧ (θ-θ*), respectively. Therefore, a closed loop control is proposed to gain a precise voltage phase and amplitude as shown in Fig. 8.

Fig. 8.Schematic of applied closed loop control.

The transfer function of this control loop is revealed as H(s). Bode diagrams of H(s) are depicted in Fig. 9 according to different control parameters, kP and kI. The performance of ζ=0.707 is more stable and is selected here.

Where, ζ is defined as follows:

Fig. 9.Bode diagrams of H(s) for different values of ζ.

Furthermore, the three phase currents are also assumed to be cosine functions, but with the same magnitude (Im). The d-q current components are described as:

Where IAP and IRP refer to the active power current component and the reactive power current component, respectively.

B. Control Strategy

With the use of the mentioned PLL, the d-q model of a 3-Ф delta-connected MERSs can be described as:

Where Ed, Eq, UMERSd, UMERSq, IMERSd and IMERSq refer to the grid voltage, MERS voltage and MERS current, respectively. Only the lower formula of equation (15) is studied on account of the negligible active power current component.

To realize stability regulation, a negative feedback function is introduced and defined as:

Where KMERS and TMERS are the proportionality coefficient and the time constant, respectively. The working state of this DGS can be described by a switch function as:

Then, the reference current (I*MERSq) can be expressed as:

Where UREF means the reference phase voltage of the DGS, and IFCq, ILq and Isiq are the reactive power current components of each of these branches. Ku and Tu are the proportionality coefficient and time constant of this voltage control loop. In addition, Qout is obtained on the basis of equations (8) ~ (10) as:

From equation (8), the primary operating point (α, 0) is ascertained by:

Then, VC-min can be worked out by equation (9).

The proposed control strategy is shown in Fig. 10. The voltage or current signals are detected from the DGS at first and transformed to d-q axis signals using the SRCC. The reference current, I*MERSq, is determined by two different operating modes. Then, equation (16) and (18) are applied to get the control variable, UMERSq. The expected Qout can be achieved with equation (19) and used for EPL confirmation. Lastly, the control parameters are optimized and the control signals are generated to drive the 3-Φ MERSs to provide DRPC for the DGS.

Fig. 10.Schematic of the proposed control strategy.

 

V. SIMULATION AND EXPERIMENTS VERIFICATION

A small-scale DGS with two SEIGs has been developed as well as an equivalent simulation model based on equation (1) and the same parameters used in PSIM. The 3-Φ MERSs and groups of FCs are employed to supply continuous reactive power. First, the proposed control strategy is demonstrated in a developed 3-Φ MERSs when it connects to a power grid directly. With the novel DRPC device, the adjustment of the system voltage or reactive power are verified by both the simulation and experiment results when only one SEIG is powered and the double SEIGs are powered, respectively.

A. Experimental System Construction

A principle diagram of the experimental DGS is shown in Fig. 11. A self-excited induction motor (SEIM) is selected to simulate a wind turbine as a prime mover. SW1, SW2, SW3 and S, are used to realize the different running modes.

Fig. 11.Diagram of the system construction of experimental DGS.

The system specifications are revealed in Table IV. A photograph of the designed 3-Φ MERSs is shown in Fig. 12(a), and Fig. 12(b) shows a simulation of the wind power system. Expert III, which works as a central controller with an integrated DSP (C6713), is applied here. PE-View 9 is a kind of special control soft for Expert III. The testing equipment includes a TPS 2024 (200MHz), a FLUKE 43B POWER QUALITY ANALYZER, etc. In order to achieve practical performance, the parameters of the induction motor are measured and used in the simulation model, as shown in Appendix Table V.

TABLE IVSPECIFICATIONS OF THE EXPERIMENTAL DGS

Fig. 12.Photographs of the experimental devices.

TABLE VMAIN PARAMETERS OF SEIGS

B. Verification of the Proposed DRPC

Fig. 13 shows a flow diagram of the applied program. This part only takes the situation of S=0 into account to show that the MERSs can produce a continuously variable reactive power. Some necessary constants are ascertained separately: THDmax =6.0%, VC-peak=1000V, Q0=2.268kvar, ζ=0.707, KMERS=1.15, TMERS=0.0025, and Eq =0. Then, experimental results are obtained as shown in the following pictures.

Fig. 13.Schematic of the program running in PE-View 9

1) Performance of the Optimized Operating Point: With the parameter optimization control, the MERS current THD and VC-peak are adjusted by VC-min. Fig. 14 and Fig. 15 reveal the simulation and experimental results, respectively. In Fig. 14(a), both of the two points can generate the same reactive power (EPL=12.45kvar). However, the right figure shows the lower peak-peak MERS voltage and current distortion rates achieved at point (100, 15V). Fig. 14(b) demonstrates this feature when the EPL is equal 16.12kvar. Fig. 15(a) and Fig. 15(b) show the experimental results which show that the proposed method is effective.

Fig. 14.Simulation of parameters optimization control.

Fig. 15.Experiment of control parameters optimization.

In addition, different operating points and the corresponding Qout are applied to calculate some of the coefficients mentioned above using LFM and Kα =1.1, Tx =0.033, Kv =0.002, V0 =0.00, and K =0.05.

2) Reactive Power Compensation Range Extended: When the conditions of equation (10) are satisfied, the practical range of the reactive power compensation and the operating point are considered and experimented on. Fig. 16(a) shows the THDi and the capacitor peak voltage when the output reactive power rises and Fig. 16(b) gives its permit working point. The squares connected by solid lines are the experimental results with the proposed parameter optimization control. The squares connected by dotted lines are the experimental results using the control method before improvement. The filled squares reflect the peak voltage of the capacitor and unfilled ones refer to the MERS current THD.

Fig. 16.Steady state characteristics of MERSs.

The capacity of the reactive power compensation can be obtained and it can be regulated from 7.5kVar to 22.5kVar when the THDi<6% and the VC-peak<1000V as shown in Fig. 16(a).

In Fig. 16(b), the operating points of the improved MERS are broadened to the large area which is enclosed by four bold lines. In reference [21], the working point is only permitted on the α axis or the VC-min axis, and the range of the dynamic reactive power is just regulated from 8.0kVar to 16.0kVar. Therefore, both the minimum and maximum Qout are extended in this work.

C. Voltage Regulation for the SEIGs Powered DGS

In this part, the proposed control strategy is verified with the switches S, SW1 and SW3 closed as shown in Fig. 11. The MERSs and the FCs just work as power factor correctors (PFC) for the grid when load is changing. Then, S is open and the voltage of the SEIGs is regulated by the MERSs. Lastly, SW2 is also closed and the experimental results are separately measured when the load goes up or down.

1) Power Factor Correction of the Grid Connected SEIG: When a SEIG connects to a grid, the output voltage is always kept at a rated value since it is fixed by the grid voltage. The most important feature is the transient and steady state performance in terms of power factor correction when the MERSs are applied. With the load increasing or declining, the dynamic and stable characteristics are verified by simulation and experiment studies.

In order to achieve the best performance in terms of power factor regulation, the proportion of KMERS and TMERS needs to keep at 1:1000, which is verified by the simulation. Its effect is shown in Fig. 17(a) and Fig. 17(b) under the conditions of an increasing or decreasing load. Fig. 18(a) and Fig. 18(b) show the dynamic process in the experiments.

Fig. 17.Transient characteristics when the proportion between KMERS and TMERS is 0.001.

Fig. 18.Transient characteristic when KMERS =1.22 and TMERS =1350.0 in experiment.

By continuously increasing the load, the power factor of the grid is measured and as shown in Fig. 19. The load reactive power is dynamically compensated by the MERSs and FCs as revealed by the solid line of connected circles. The squares connected by solid line or dotted line, show the steady state process of the grid PFC in the simulation and experiment, respectively. Obviously, the power factor can always maintain a unit because the MERSs produce equivalent reactive power to make up for the SEIG leaded by increasing the load. When the output reactive power is lower than 7.5kVar or larger than 22.5kVar, the current THD is measured and shown in Fig. 20(a) and Fig. 20(b).

Fig. 19.Steady state performance on power factor regulation.

Fig. 20.Current THD for the boundary operating point.

2) Voltage Regulation for a Single SEIG: Fig. 21(a) and Fig. 21(b) show the processes of no-load voltage building with FCs excited and with MERSs. The simulation model shown in Fig. 7 has been built in PSIM. The parameters of this model are the same as those used in the experimental SEIGs as shown in Table V in the Appendix.

Fig. 21.The process of no-Load voltage building by experiment.

The first step is to ascertain a couple of KU and TU to get the best transient characteristic. When KU =1.0 and TU =1000.0, the simulation results, including the waveforms of three phase voltage, are described in Fig. 22. The bold line means the RMS value of the grid voltage. Then, a group of special KU and TU is estimated and used in the experiment on the basis of the simulation results. Fig. 23 shows the experimental results when KU =3.88 and TU =3550.0.

Fig. 22.SEIG’s line-line voltage regulation by Simulation.

Fig. 23.Experimental results of SEIG voltage adjusting when KU =3.88 and TU =3550.0.

3) Voltage Regulation for Double SEIGs: With the parameters KU and TU tested above, the dynamic process of voltage regulation at the moment when a 4 kW SEIG is inserted in or cut off is shown in Fig. 24.

Fig. 24.Voltage regulating at the moment of 4kW SEIG inserted in or cut off.

Finally, the voltage regulation of the developed DGS is realized and the curves, as shown in Fig. 25, reflect the characteristic of its steady-state performance. Obviously, the grid voltage is dramatically reduced, as revealed by the dotted line with filled squares, unless the MERSs are installed. The solid line with unfilled circles shows that the output of the MERSs reactive power increases continuously with the rising load power. The unfilled squares which are connected by a solid line and a dotted line, verify that the voltage stability of the DGS can be maintained by the MERSs + FCs. In conclusion, the MERS works as a DRPC in SEIGs powered wind systems and it is verified by both simulation and experimental results.

Fig. 25.Stable performance of the developed DGS voltage.

 

VI. CONCLUSION AND FUTURE WORK

A simple full-bridge MERS which is especially applicable to small-scale DGSs has been studied in this article. A theoretical analysis and experiments are devoted to validate it as a DRPC and to illustrate its feasibility for voltage or reactive power regulation in SEIGs power systems. Both the steady state and transient state experimental results support the conclusion that the MERS is a valuable and reliable reactive power controller. When compared to STATCOMs, the major advantages of the MERS include the adoption of a small DC capacitor, line frequency switching, simple control, and reduced losses. The MERS can also realize reactive power control in micro-grids. This will be investigated at some point in the future.

References

  1. E. Touti, R. Pusca, J. P. Manata, J. F. Brudny, and A. Chaari, “On the use of a dimmer for a robust frequency control of a self-excited three-phase induction wind generator,” Journal of Power Electronics, Vol. 14, No. 3, pp. 580-591, May 2014. https://doi.org/10.6113/JPE.2014.14.3.580
  2. T. Ahmed, O. Noro, E. Hiraki, and M. Nakaoka, “Terminal voltage regulation characteristics by static VAR compensator for a three-phase self-excited induction generator,” IEEE Trans. Ind. App., Vol. 40, No. 4, pp. 978-988, Aug. 2004. https://doi.org/10.1109/TIA.2004.830783
  3. L. Spasojević, I. Papič, and B. Blažič, “Development of a control algorithm for a static VAR compensator used in industrial networks,” Journal of Power Electronics, Vol. 14, No. 4, pp. 754-763, Jul. 2014. https://doi.org/10.6113/JPE.2014.14.4.754
  4. B. Singh, S S. Murthy, and S. Gupta, “STATCOM-based voltage regulator for self-excited induction generator feeding nonlinear loads,” IEEE Trans. Ind. App., Vol. 53, No. 5, pp. 1437-1452, Oct. 2006.
  5. J.A. Barrado, R. Griñó, and H. Vald-Blavi, “Power-quality improvement of a stand-alone induction generator using a STATCOM with battery energy storage system,” IEEE Trans. Power Del., Vol. 25, No. 4, pp. 734-2741, Oct. 2010. https://doi.org/10.1109/TPWRD.2009.2037231
  6. T. Ahmed, K. Nishida, and M. Nakaoka, “A novel stand alone induction generator system for ac and DC power applications,” IEEE Trans. Ind. App., Vol. 43, No. 6, pp. 1465-1474, Nov. 2007. https://doi.org/10.1109/TIA.2007.908210
  7. P. K. Tiwari and Y R. Sood, “An efficient approach for optimal allocation and parameters determination of TCSC with investment cost recovery under competitive power market,” IEEE Trans. Power System, Vol. 28, No. 3, pp. 2475-2484, Aug. 2013. https://doi.org/10.1109/TPWRS.2013.2243848
  8. M. S. El-Moursi and A. M. Sharaf, “Novel controllers for the 48-pulse VSC STATCOM and SSSC for voltage regulation and reactive power compensation,” IEEE Trans. Power Syst., Vol. 20, No. 4, pp. 1985-1997, Nov. 2005. https://doi.org/10.1109/TPWRS.2005.856996
  9. S. An, J. Condren, and T.W. Gedra, “An ideal transformer UPFC model, OPF first-order sensitivities, and application to scree for optimal UPFC locations,” IEEE Trans. Power System, Vol. 22, No. 1, pp. 68-75, Feb. 2007. https://doi.org/10.1109/TPWRS.2006.889141
  10. G. K. Kasal and B. Singh, “Voltage and frequency controllers for an asynchronous generator-based isolated wind energy conversion system,” IEEE Trans. Energy Convers., Vol. 26, No. 2, pp. 402-416, Jun. 2011. https://doi.org/10.1109/TEC.2010.2102029
  11. S. Kumar and R. Narayan, “Effect of capacitive VAR on performance of three-phase self-excited induction generator,” International Journal of Emerging Technology and Advanced Engineering, Vol. 12, No. 2, pp. 253-258, Dec. 2012.
  12. R. C. Bansal, “Three-phase self-excited induction generators: An Overview,” IEEE Trans. Energy Convers., Vol. 20, No. 2, pp. 292-299, Jun. 2005. https://doi.org/10.1109/TEC.2004.842395
  13. S. Boora, “Analysis of self-excited induction generator under balanced or unbalanced conditions,” International Journal on Electrical and Power Engineering, Vol. 1, No. 3, pp. 59-63, Dec. 2010.
  14. D. Seyoum, C. Grantham, and M. F. Rahman, “The dynamic characteristics of an isolated self-excited induction generator driven by a wind turbine,” IEEE Trans. Ind. Appl., Vol. 39, No.4, pp. 936-944, Jul. 2003. https://doi.org/10.1109/TIA.2003.813738
  15. J. Cidrás and A. E. Feijóo, “A linear dynamic model for asynchronous wind turbines with mechanical fluctuations,” IEEE Trans. Power Syst., Vol. 17, No. 3, pp. 681-687, Aug. 2002. https://doi.org/10.1109/TPWRS.2002.800912
  16. G. S. Kumar and A. Kishore, “Dynamic analysis and control of output voltage of a wind turbine driven isolated induction generator,” in Proc. ICIT, pp. 494-499, 2006.
  17. F. A. Farret, B. Palle, and M. G. simoes, “State Space Modeling of Parallel Self-Excited Induction Generator for Wind Farm Simulation,” in Proc. IAS, pp. 2801-2807, 2004.
  18. T. Isobe, J. A. Wiik, T. Kitahara, S. Kato, and K. Inoue, “Control of series compensated induction motor using MERS,” in Proc. PEA&EC, pp. 1-10, 2007.
  19. J. A. Wiik, O. J. Fonstelien, and R. Shimada, “A MERS type Series FACTS Controller for Low Voltage Ride Through of Induction Generators in Wind Farms,” in Proc. PEA&EC, pp. 1-10, 2009.
  20. T. Kawaguchi, T. Sakazaki, and T. Isobe, “Offshore wind farm configuration using diode rectifier with MERS in current link topology,” IEEE Trans. Ind. Electron., Vol. 60, No. 7, pp. 2930-2937, Jul. 2013. https://doi.org/10.1109/TIE.2012.2217716
  21. M. M. Cheng, D. Shiojima, T. Isobe, and R. Shimada, “Voltage control of induction generator powered distributed system using a new reactive power compensator SVC-MERS,” in Proc. PEMCC, pp. 71-78, 2013.
  22. F. D. Wijaya, T. Isobe, K. Usuki, J. A. Wiik, and R. Shimada, “a new automatic voltage regulator of self-excited induction generator using SVC magnetic energy recovery switch (MERS),” in Proc. IEPESC, pp. 697-703, 2008.