Abstract

This study performed simulation tests to prevent induced lightning that occurs to a 22.9 kV-Y distribution line. A simulated distribution line reduced to 1/50 of an actual distribution line was installed to measure the induced voltage according to the change in grounding resistance. It was found that the induced voltage increased as the grounding resistance increased but that the range of its increase was small. This study examined the reliability of the proposed lightning preventive distribution line using the Minitab program (Minitab 17). When a grounding resistance of $300{\Omega}$ was maintained for each electric pole, the Anderson Darling (AD) was 0.410, the smallest, and the P value was analyzed to be 0.323, verifying that the reliability and stability were excellent. Therefore, these results will be utilized as a basis for the substantiation of a lightning preventive distribution line before its installation.

Keywords

References

  1. IEEE Std 142-2007, "IEEE Recommended Practice for Electric Power Distribution for Industrial Plants", pp.145-167, 2007.
  2. IEEE Std 1243-1997, "IEEE Guide for Improving the Lightning Performance of Transmission Lines", 1997.
  3. J. S. Kim, Y. B. Park and D. Y. Kim, "Analysis on the Induced Lightning Shielding Effect according to the Neutral Wire Installation Structure of a 22.9 kV Distribution Line", Trans. KIEE. Vol.59P, No.2, pp. 191-196, 2010.
  4. IEEE Std 1410-2004, "IEEE Guide for Improving the Lightning Performance of Electric Power Overhead Distribution Lines", 2004.
  5. S. Rusck, "Induced Lightning Over-voltages on Power-Transmission Lines with Special Reference to the Over-Voltage Protection of Low Voltage Networks", Trans. Royal Institute of Technology, Stockholm, Sweden, No.120, pp.1-118, 1958.
  6. P. Chowdhuri, "Voltages Surges Induced on Overhead Lines by Lightning Strokes", Proc. IEE, Vol.116, pp.561-565, 1969.
  7. P. Chowdhuri, "Analysis of Lightning-induced Voltages on Overhead Lines", IEEE Transactions on Power Delivery, Vol.4, No.1, pp.479-492, 1989.
  8. C.A. Nucci, F. Rachidi, M. V. Ianoz, C. Mazzetti, "Lightning-induced Voltages on Overhead Lines", IEEE Trans. on Electromagnetic Compatibility, Vol.35, No. 1, pp.75-88, 1993. https://doi.org/10.1109/15.249398
  9. M. A. Uman, V. A. Rakov, M. I. Fernandez, C. T. Mata, K. J. Rambo, M. V. Stapleton and R. R. Sutil, "Direct Lightning Strikes to the Lightning Protective System of a Residential Building: Triggered-Lightning Experiments" IEEE Transactions on Power Delivery, Vol.17, pp.575-586, 2002. https://doi.org/10.1109/61.997942
  10. M. A. Uman, M. Paolone, F. Rachidi, A. Borghetti, C. A. Nucci, M. Rubinstein and V. A. Rakov, "Lightning-Induced Voltages on Complex Distribution Systems: Models, Advanced Software Tools and Experimental Validation", Journal of Electrostatics, Vol.60, Issues 2-4, pp.163-174, 2004. https://doi.org/10.1016/j.elstat.2004.01.001
  11. Daewon Electric Corp., "A Feasibility Study on Using the Overhead Ground Wire both as a Neutral Line and Ground Wire", Power Industry R & D Projects Final Report, 2007.
  12. J. S. Kim and C. S. Choi, "Accident Cause Analysis and Prevention Countermeasure of 22.9 kV-Y Extra-high Voltage Distribution Lines", Proceedings of Spring Conference of the Korean Soc. Saf., 2014.
  13. KEPCO, "Design Criteria of Distribution Line 3500 (Grounding), 3800(Lightning Protection)", 2014.