Effects of cement type and sand to cement ratio on the properties of PSC grout

시멘트 종류 및 잔골재 시멘트 비율이 PSC 구조물용 그라우트의 기본 물성에 미치는 영향

  • Park, Gi-Joon (Department of civil & environmental engineering, Sejong University) ;
  • Moon, Do-Young (Department of civil engineering, Kyungsung University)
  • 박기준 (세종대학교 건설환경공학과) ;
  • 문도영 (경성대학교 토목공학과)
  • Received : 2014.06.02
  • Accepted : 2014.07.10
  • Published : 2014.07.31

Abstract

This study examined the effects of the cement type and sand to cement ratio on the properties of grout for offshore PSC structures. Types I and III cement were used and the sand to cement ratio was varied from 0.5 to 1.5. When type I cement was used, considerable bleeding occurred on the all S/C after 3 hours and 20 hours. When type III cement was used, bleeding was reduced but the flowability decreased. A comparison of a superplasticizer containing naphthalene with that containing polycarboxylate showed that the problem of flowability could be solved using polycarboxylate.

본 연구는 시멘트 종류와 잔골재 시멘트 비율(S/C)이 PSC 구조물용 그라우트의 기본 물성에 미치는 영향을 조사하였다. 시멘트는 1종 (보통) 시멘트와 3종 (조강) 시멘트를 사용하였고, S/C를 0.5, 1.0 그리고 1.5로 변화하여 그 영향을 평가하였다. 1종 시멘트의 사용 시 모든 S/C에서 3시간과 20시간이 지났을 때 다수의 블리딩이 발생하였다. 반면에 3종 시멘트의 사용 시, 블리딩이 현저히 줄어들었지만 유동성이 낮아지는 문제점이 발생하였다. 또한, 고성능감수제의 종류를 나프탈렌계와 폴리칼본산계 두 종류를 비교한 결과 3종 시멘트를 사용한 경우의 저하된 유동성 문제를 폴리칼본산계 고성능감수제의 사용으로 해결할 수 있었다.

Keywords

References

  1. K. Lau, I. Lasa, M. Paredes, "Corrosion Failure of Post-Tensioned Tendons in Presence of Deficient Grout", NACE International, March, 2013.
  2. A. A. Al-Manaseer, L. D. Keil, "Physical Properties of Cement Grout Containing Silica Fume and Superplasticizer", ACI Materials Journal, Vol. 89, No. 2, pp. 154-160, March-April, 1992.
  3. J. Bastien, J. Dugat, E. Prat, "Cement Grout Containing Precipitated Silica and Superplasticizers for Post-Tensioning", ACI Materials Journal, Vol. 94, No. 4, pp. 291-295, July-August, 1997. DOI: http://dx.doi.org/10.14359/311
  4. W. H. Huang, "Properties of cement-fly ash grout admixed with bentonite, silica fume, or organic fiber", Cement and Concrete Research, Vol. 27, No. 3, pp. 395-406, March, 1997. DOI: http://dx.doi.org/10.1016/S0008-8846(97)00032-X
  5. S. Miyazawa, T. Yokomuro, E. Sakai, A. Yatagai, N. Nito, K. Koibuchi, "Properties of concrete using high C3S cement with ground granulated blast-furnace slag", Construction and Building Materials, Vol. 61, pp. 90-96, June, 2014. DOI: http://dx.doi.org/10.1016/j.conbuildmat.2014.03.008
  6. K. S. Kim, J. D. Ha, D. S. Kim, G. Y. Shin, K. H. Ryu, "A Study on the Bleeding Property of Flowed Concrete Due to Different Types of High Range Water Reducing Admixtures", Journal of the Korea Concrete Institute, pp. 321-326, 1997