DOI QR코드

DOI QR Code

A Study on Current Ripple Reduction Due to Offset Error in SRF-PLL for Single-phase Grid-connected Inverters

단상 계통연계형 인버터의 SRF-PLL 옵셋 오차로 인한 전류 맥동 저감에 관한 연구

  • Received : 2014.08.14
  • Accepted : 2014.09.23
  • Published : 2014.11.28

Abstract

This paper presents an offset error compensation algorithm for the accurate phase angle of the grid voltage in single-phase grid-connected inverters. The offset error generated from the grid voltage measurement process cause the fundamental harmonic component with grid frequency in the synchronous reference frame phase lock loop (PLL). As a result, the grid angle is distorted and the power quality in power systems is degraded. In addition, the dq-axis currents in the synchronous reference frame and phase current have the dc component, first and second order ripples compared with the grid frequency under the distorted grid angle. In this paper, the effects of the offset and scaling errors are analyzed based on the synchronous reference frame PLL. Particularly, the offset error can be estimated from the integrator output of the synchronous reference frame PLL and compensated by using proportional-integral controller. Moreover, the RMS (Root Mean Square) function is proposed to detect the offset error component. The effectiveness of the proposed algorithm is verified through simulation and experiment results.

Keywords

References

  1. H. E. Park, E. S. Kim, and J. H. Song, "A SRF power flow control method for grid-connected single-phase inverter systems", JIEIE, vol. 24, no. 5, pp. 129-135, May 2010.
  2. W. C. Lee, "Maximum power point tracking control for a grid-tie photovoltaic inverter", JIEIE, vol. 23, no. 5, pp. 72-79, May 2009. https://doi.org/10.5207/JIEIE.2009.23.5.072
  3. S. M. Jung, Y. S. Bae, T. S. Yu, S. W. Choi, and H. S. Kim, "Single-phase utility-integrative for residential fuel cell generation system", KIPE, vol. 12, no. 1, pp. 81-88, Feb. 2007.
  4. Y. Xue, L. Chang, S. B. Kjaer, J. Bordonau, and T. Shimizu, "Topologies of single-phase inverters for small distributed power generators: an overview," IEEE Trans. Power Electron., vol. 19, no. 5, pp. 1305-1314, Sept. 2004. https://doi.org/10.1109/TPEL.2004.833460
  5. S. B. Kjaer, J. K. Pedersen, and F. Blaabjerg, "A review of single-phase grid-connected inverters for photovoltaic modules," IEEE Trans. Ind. Applicat., vol. 41, no. 5, pp. 1292-1306, Sept./Oct. 2005. https://doi.org/10.1109/TIA.2005.853371
  6. S. M. Silva, B. M. Lopes, B. J. C. Filho, R. P. Campana, and W. C. Bosventura, "Performance evaluation of PLL algorithms for single-phase grid-connected systems," in Proc. IAS, 2004, vol. 4, pp. 2259-2263.
  7. P. Rodriguez, J. Pou, J. Bergas, J. I. Candela, R. P. Burgos, and D. Boroyevich, "Decoupled double synchronous reference frame PLL for power converters control," IEEE Trans. Power Electron., vol. 22, no. 2, pp. 584-592, March 2007.
  8. M. Ciobotaru, R. Teodorescu, and F. Blaabjerg, "A new single-phase PLL structure based on second order generalized integrator," in Proc. PESC, 2006, pp.1-6.
  9. S. J. Lee, J. K. Kim, and S. K. Sul, "A new phase detecting method for power conversion systems considering distorted conditions in power system," in Proc. IAS, 1999, vol. 4, pp. 2167-2172.
  10. M. Ciobotaru, R. Teodorescu, and V. G. Agelidis, "Offset rejection for PLL based synchronization in grid-connected converters," in Proc. APEC, 2008, pp. 1611-1617.
  11. M. Karimi-Ghartemani, S. A. Khajehoddin, P. K. Jain, A. Bakhshai, and M. Mojiri, "Addressing DC component in PLL and notch filter algorithms," IEEE Trans. Power Electron., vol. 27, no. 1, pp. 78-86, Jan. 2012. https://doi.org/10.1109/TPEL.2011.2158238
  12. S. H. Hwang, L. Liu, H. Li, J. M. Kim, "DC offset error compensation for synchronous reference frame PLL in single-phase grid-connected converters," IEEE Trans. Power Electron., vol. 27, no. 8, pp. 3467-3471, April 2012.