DOI QR코드

DOI QR Code

Numerical Simulation of a System Heat Pump Adopting an Integral Optimum Regulating Controller

적분형 최적 레귤레이터 적용 시스템 히트펌프 제어 시뮬레이션 연구

  • Kim, Yongchan (Department of Mechanical Engineering, Korea University) ;
  • Choi, Jong Min (Department of Mechanical Engineering, Hanbat National University)
  • Received : 2013.04.12
  • Published : 2013.07.10

Abstract

Small and medium-size buildings employ a multi-distributed individual air-conditioning system that utilizes package air conditioners instead of centralized cooling systems, which can allow easier building management and maintenance, along with a diversification of facility use. Inverter driven system heat pumps have been developed to achieve not only an easy distribution control, allowing free combination of indoor units with different models and different capacities, but also wide applications to intelligent air conditioning. However, the control algorithms of the system heat pump are limited in the open literature, due to complicated operating conditions. In this paper, an inverter-driven system heat pump having two indoor units with electronic expansion valves (EEV) was simulated in the cooling mode. An integral optimum regulating controller employing the state space control method was also simulated, and applied to the system-heat pump system, to obtain efficient control of the MIMO (multi input multi output) system. The simulation model for the controller yielded satisfactory prediction results. The new control model can be successfully utilized as a basic tool in controller design.

Keywords

References

  1. Kang, H., Joo, Y., Chung, H., Kim, Y., and Choi, J., 2009, Experimental study on the performance of a simultaneous heating and cooling multi-heat pump with the variation of operating mode, International Journal of Refrigeration, Vol. 32, pp. 1452-1459. https://doi.org/10.1016/j.ijrefrig.2009.02.015
  2. Choi, J. M. and Kim, Y., 2003, Capacity modulation of an inverter-driven multi-air conditioner using electronic expansion valves, Energy, Vol. 28, pp. 141-155. https://doi.org/10.1016/S0360-5442(02)00113-5
  3. Chua, K. J., Chou, S. K., and Yang, W. M., 2010, Advances in heat pump systems : a review, Applied energy, Vol. 87, pp. 3611-3624. https://doi.org/10.1016/j.apenergy.2010.06.014
  4. Ma, G. and Li, X., 2007, Exergetic optimization of a key design parameter in heat pump systems with economizer coupled with scroll compressor, Energy Conversion Management, Vol. 48, No. 4, pp. 1150-1159. https://doi.org/10.1016/j.enconman.2006.10.007
  5. Chaiwongsa, P. and Wongwises, S., 2008, Experimental study on R-134a refrigeration system using a two-phase ejector as an expansion device, Applied Thermal Engineering, Vol. 28, pp. 467-477. https://doi.org/10.1016/j.applthermaleng.2007.05.005
  6. Chen, J. and Yu, J., 2008, Performance of a new refrigeration cycle using refrigerant mixture R32/R134a for residential air-conditioner applications, Energy Buildings, Vol. 40, No. 11, pp. 2022-2027. https://doi.org/10.1016/j.enbuild.2008.05.003
  7. Chen, W., 2008, A comparative study on the performance and environmental characteristics of R410A and R22 residential air conditioners, Applied Thermal Engineering, Vol. 28, No. 1, pp. 1-7. https://doi.org/10.1016/j.applthermaleng.2007.07.018
  8. Murr, R., Thieriot, H., Zoughaib, A., and Clodic, D., 2011, Multi-objective optimization of a multi water-towater heat pump system using evolutionary algorithm, Applied Energy, Vol. 88, pp. 3580-3591. https://doi.org/10.1016/j.apenergy.2011.04.013
  9. Caillat, J. L., Ni, S., and Daniels, M., 1998, A computer model for scroll compressors, Proceeding of International Compressor Engineering Conference at Purdue, pp. 47-55.
  10. He, X. Liu, S., and Asada, H. H, 1997, Modeling of vapor compression cycles for multivariable feedback control HVAC system, Journal of Dynamic Systems, Measurement, and Control, Vol. 119, pp. 183-191. https://doi.org/10.1115/1.2801231
  11. Choi, J. M., 2002, Study on the transient performance and optimal control of a variable speed multi-heat pump, Ph. D Thesis, Korea.
  12. Holman, J. P., 1987, Heat Transfer, McGraw-Hill Press.
  13. Travis, D. P., Baron, A. B., and Rohsenow W. M., 1970, Forced convection condensation inside tubes : a heat transfer equation for condenser design, ASHRAE Trans. Vol. 72, pp. 157-165.
  14. Gungor, K. E. and Winterton, R. H. S., 1986, A general correlation for flow boiling in tubes and annuli, Int. J. of Heat and Mass Transfer, Vol. 29, No. 3, pp. 351-358. https://doi.org/10.1016/0017-9310(86)90205-X
  15. McQuiston, F. C., 1978, Finned tube heat exchanger; state of the art for the air side, ASHRAE Transaction, Vol. 84, pp. 85-93.
  16. Myers, R. J., 1967, The effect of dehumidification on the air-side heat transfer coefficient of a fined tube coil, University of Minnesota, Master's Thesis.
  17. Landau, L., 1990, System Identification and control design, Prentice-Hall Inc.
  18. Ogata K., 1997, Modern control engineering, 3rd Ed., Prentice-Hall Inc.