EA Study on the Operation Performance of Central Plant Equipment According to Part Load Characteristics

부분부하 특성을 고려한 열원기기의 운전성능 평가

  • 이왕제 (대전대학교 대학원 건축공학과) ;
  • 강은철 (한국에너지 기술연구원) ;
  • 이의준 (한국에너지 기술연구원) ;
  • 오병칠 (신흥대학교 건축설비설계과) ;
  • 신우철 (대전대학교 건축공학과)
  • Received : 2013.04.01
  • Published : 2013.07.10

Abstract

To fulfill the demands concerning energy efficiency for zero energy buildings, various technologies of architects and engineers are required. This study aims to estimate the thermal performance of heat source equipment in which part load characteristics are considered in an office building. Overestimation of heat source equipment was reviewed through literature survey, and heating and cooling loads depending on the capacity and division of the equipment were analyzed through a simulation program (DOE-2.1E). The conclusions gained from this study are as follows; 1) The more the division of equipment, the less the heating and cooling energy consumption. 2) When a large item of equipment is divided into two small items of equipment, the optimum application rate showed as 5:5 for chiller, and 7:3 for boiler, respectively.

Keywords

References

  1. Ministry of Land, Transport and Maritime Affairs, 2010, Green Cities and Buildings Activation Plan.
  2. Kim, Y. S., 1998, Evaluation for the Energy Conservation Design Requirement of Building Chilling System, Architectural Institute of Korea, Vol. 14, No. 10, pp. 219-228.
  3. Kim, Y. S., 1998, Evaluation for the Energy Conservation Design Requirement of Building Heating System, Architectural Institute of Korea, Vol. 14, No. 12, pp. 231-238.
  4. Jung, J. R., Kim, S. H., and Lee, K. H., 2000, A Study on the Application of Safety Factors for Optimal Sizing of Central Plant Equipment, Architectural Institute of Korea, Vol. 16, No. 3. pp. 77-84.
  5. Kim, S. H and Kim, D. G., 2007, Asurvey Survey Study on Optimal Cooling Equipment Capacity in Office Buildings, Architectural Institute of Korea Vol. 23, No. 8, pp. 247-254.
  6. DOE-2.1E manual
  7. Kim, K. S., Kim, Y. C., and Oh, M. D., 2006, Introduction of RTS Method and Load Calculation Program, SAREK, pp. 1067-1072.
  8. Ministry of Land, Transport and Maritime Affairs, 2010, Energy-saving Design Guidelines of Innovation City Public building.
  9. Http://www.kses.re.kr(The Korean Solar Energy Society)

Cited by

  1. A Detailed Analysis of the Part Load Ratio and Cooling Energy Characteristics of Chiller Operation in an Office Building vol.27, pp.11, 2015, https://doi.org/10.6110/KJACR.2015.27.11.567
  2. Detailed Analysis on Operation Characteristics and Cooling Energy Saving Effect of Chiller Staging in an Office Building vol.28, pp.4, 2016, https://doi.org/10.6110/KJACR.2016.28.4.137