Winding Temperature Measurement in a 154 kV Transformer Filled with Natural Ester Fluid

  • Kweon, Dongjin (Transmission & Distribution Laboratory, Korea Electric Power Research Institute) ;
  • Koo, Kyosun (Transmission & Distribution Laboratory, Korea Electric Power Research Institute)
  • 투고 : 2012.03.13
  • 심사 : 2012.06.25
  • 발행 : 2013.01.02

초록

This paper measures the hot spot temperatures in a single-phase, 154 kV, 15/20 MVA power transformer filled with natural ester fluid using optical fiber sensors and compares them with those calculated by conventional heat run tests. A total of 14 optical fiber sensors were installed on the high-voltage and low-voltage windings to measure the hot spot temperatures. In addition, three thermocouples were installed in the transformer to measure the temperature distribution during the heat run tests. In the low-voltage winding, the hot spot temperature was $108.4^{\circ}C$, calculated by the conventional heat run test. However, the hot spot temperature measured using the optical fiber sensor was $129.4^{\circ}C$ between turns 2 and 3 on the upper side of the low-voltage winding. Therefore, the hot spot temperature of the low-voltage winding measured using the optical fiber sensor was $21.0^{\circ}C$ higher than that calculated by the conventional heat run test.

키워드

참고문헌

  1. C. P. McShane, "New dielectric coolant concepts for distribution and power transformers," IEEE Pulp and Paper Industry Technical Conference, pp. 55-62, 1999.
  2. C. P. McShane, J. Corkran, K. Rapp, and J. Luksich, "Natural ester dielectric fluid development," IEEE PES Transmission & Distribution Conference and Exhibition, pp. 18-22, 2006.
  3. C. P. McShane, J. Luksich, K. J. Rapp, J. L. Corkran and G. A. Gauger, "Aging of paper insulation in natural ester dielectric fluid," IEEE PES Transmission and Distribution Conference and Exposition, Vol. 2, pp. 675-679, 2001.
  4. C. C. Claiborne and D. B. Cherry, "Status update on the use of natural ester (vegetable oil) dielectric fluids in transformers," 73rd Annual International Doble Client Conference, 2006.
  5. S. D. Smith, "Design and test experience with natural ester fluid for power transformers," IEEE PES Transmission and Distribution Conference and Exhibition, pp. 35-36, 2006.
  6. R. Ahuja and R. M. Del Vecchio, "Comparison of the thermal performance of FR3, a natural ester-based coolant, with transformer oil," CIGRE SC A2 and D1 Joint Colloquium on Power Transformers, 2007.
  7. F. Bachinger and P. Hamberger, "Steady state and transient thermal behavior of transformers filled with various insulating liquids," CIGRE SC A2 and D1 Joint Colloquium on Power Transformers, 2007.
  8. D. Martin, N. Lelekakis and V. Davydov, "Condition monitoring of vegetable oil-filled power transformers," Asia Pacific TechCon Conference, pp. 271-286, 2010.
  9. Temperature rise for liquid-immersed transformers, IEC Std. 60076-2, 2011.

피인용 문헌

  1. Multi-field Coupling Simulation and Experimental Study on Transformer Vibration Caused by DC Bias vol.10, pp.1, 2015, https://doi.org/10.5370/JEET.2015.10.1.176
  2. A review of critical evaluation of natural ester vis-a-vis mineral oil insulating liquid for use in transformers: Part II vol.23, pp.3, 2016, https://doi.org/10.1109/TDEI.2016.005371