초록
An experimental study was conducted to examine the effectiveness of a suction-blowing fan that could not only remove polluted air by suction but also create the air-curtain by blowing. In order to create the air-curtain, rotors were installed on the surface of the shroud. These blows fresh air into the polluted region. The fresh air is spouted backward 45o on the basis of the axial direction using a double-ducted bellmouth. In the same suction operating condition, the suction region was extended by increasing the blowing velocity. However, the increasing rate of suction region was reduced when the blowing velocity was increased steadily. Thus, an efficient blowing velocity should be determined depending on the suction operating condition. In addition, the blowing requires additional input power. In a fixed suction operating condition, the input power was linearly increased in proportion to the blowing flowrate. When the suction-blowing fan was operated in the same input power as the suction fan, the suction region was increased more than 30% based on the 0.6m/sec velocity.