Browse > Article
http://dx.doi.org/10.5293/KFMA.2011.14.4.019

A Experimental Study on the Performance of an Axial-Type Suction-Blowing Fan  

Choi, Hyoung-Jun (경상대학교 대학원)
Park, Young-Ha (경상대학교 대학원)
Ahn, Kook-Young (한국기계연구원 환경에너지연구본부)
Cho, Soo-Yong (경상대학교 항공기부품기술연구센터(기계항공공학부))
Publication Information
Abstract
An experimental study was conducted to examine the effectiveness of a suction-blowing fan that could not only remove polluted air by suction but also create the air-curtain by blowing. In order to create the air-curtain, rotors were installed on the surface of the shroud. These blows fresh air into the polluted region. The fresh air is spouted backward 45o on the basis of the axial direction using a double-ducted bellmouth. In the same suction operating condition, the suction region was extended by increasing the blowing velocity. However, the increasing rate of suction region was reduced when the blowing velocity was increased steadily. Thus, an efficient blowing velocity should be determined depending on the suction operating condition. In addition, the blowing requires additional input power. In a fixed suction operating condition, the input power was linearly increased in proportion to the blowing flowrate. When the suction-blowing fan was operated in the same input power as the suction fan, the suction region was increased more than 30% based on the 0.6m/sec velocity.
Keywords
Axial-Type Fan; Suction-Blowing Fan; Aerodynamic Design; Air Curtain; Performance Test;
Citations & Related Records
Times Cited By KSCI : 4  (Citation Analysis)
연도 인용수 순위
1 함진식, 2001, "흡기용 에어커텐이 렌지후드의 환기성능에 미치는 영향에 관한 연구," 대한건축학회논문집, 계획계 Vol. 17, No. 6, pp. 153-160.
2 조종현, 정양범, 조수용, 2009, "흡입성능향상을 위한 공기차단막의 효과에 관한연구," 한국실내환경학회지, Vol. 6, No. 1, pp. 27-37.
3 조종현, 김재실, 조수용, 2009, "흡입관 주위에 형성된 공기차단막이 흡입성능에 미치는 영향," 유체기계저널, Vol. 12, No. 5, pp. 25-32.   과학기술학회마을   DOI
4 Chokhar, I. A., Prozorov, D. S., Spotar, S. Y., 1993, "An Efficient Extraction of Fumes by Means of The Vortex Suction Device," Russian Academy of Science.
5 Hijikata, K. and Suzuki, Y., 1995, "Local Ventilation and Heat Transfer by Tornado-Like Vortex," ASME/JSME Thermal Engineering Conference, Volume 1.
6 Li Y. and Desante, A., 1996, "Derivation of Capture Efficiency of Kitchen Range Hoods in a Confined Space," Building and Environment, Vol 31, No. 5, p. 461.   DOI
7 김수용, 정상현, 최범석, 박무룡, 2000, "와류유동을 이용한 환기시스템개발," 한국기계연구원 연구보고서 2000-01-31.
8 최형준, 조종현, 조수용, 2010, "A Ventilation Device Using the Air Curtain and a Ventilation Fan," PCT/KR2010/001504
9 Horlock, J. H., 1973, "Axial Flow Compressor," Robert E. Krieger Publish Co.
10 조종현, 김재실, 조수용, 2008, "흡입관의 형상에 따른 흡입성능에 대한연구," 대한설비관리학회지, Vol. 13, No. 3, pp. 67-78.
11 조수용, 최범석, 오종학, 1999, "축류송풍기의 설계시 적용된 와류형식의 영향에 관한 실험적 연구," 유체기계저널, Vol. 2, No. 3, pp. 7-16.   과학기술학회마을
12 손상범, 주원구, 조강래, 남형배, 윤인규, 남임우, 1999, "축류 송풍기의 공력학적 설계," 유체기계저널, Vol. 2, No. 1, pp. 22-28.   과학기술학회마을
13 최형준, 김창수, 조종현, 조수용, 2010, "축류형 흡입송풍기 설계기술에 관한연구," 유체기계저널 13권, No.1, pp. 42-51.