Optimum Controller Design of a Water Cooler for Machine Tools Based on the State Space Model

상태공간 모델링에 의한 공작기계용 수냉각기의 최적제어기 설계

  • Jeong, Seok-Kwon (Department of Refrigeration and Air-conditioning, Pukyong National University) ;
  • Kim, Sang-Ho (Graduate School of Refrigeration and Air-conditioning, Pukyong National University)
  • 정석권 (부경대학교 냉동공조공학과) ;
  • 김상호 (부경대학교 대학원 냉동공조공학과)
  • Received : 2011.08.04
  • Published : 2011.12.10

Abstract

Typical temperature control methods of a cooler for machine tools are hot-gas bypass and compressor variable speed control. The hot-gas bypass system has been widely used to control the cooler temperature in many general industrial fields. On the contrary, the compressor variable speed control is focused on special fields such as aerospace and high precision machine tools which need high precision control. The variable speed control system usually has two control variables such as target temperature and superheat. In other words, the variable speed control system is basically multi-input multi-output(MIMO) system. In spite of MIMO system, the proportional integral derivative(PID) feedback control methodology that based on single-input single-output (SISO) system is generally used for designing the variable speed control system. Therefore, it is inevitable to describe transfer functions for dynamic behaviors of every controlled variables and decide the PID gains with tremendous iteration process. Moreover, the designed PID gains do not provide optimum system performances. To solve these problems, high performance controller design method based on a state space model is suggested in this paper. An optimum controller is designed to minimize both control errors and energy inputs. This method was more simple to describe dynamic behaviors and easier to design the cooler controller which is MIMO system.

Keywords

References

  1. Lee, S. W., Yeom, H. K., and Park, K. J., 2009, Performance of Hot Gas Bypass Type Oil Cooler System, Journal of Korean Society for Precision Engineering, Vol. 26, No. 3, pp. 73-80.
  2. Beak, S. M., Choi, J. H., Byun, J. Y., Moon, C. G., Lee, H. S., Jeong, S. K., and Yoon, J. I., 2009, Characteristics of Temperature Control by Hot-gas Bypass Flow Rate on Industrial Water Cooler, Journal of the Korean Society of Marine Engineering, Vol. 33, No. 8, pp. 1129-1136. https://doi.org/10.5916/jkosme.2009.33.8.1129
  3. Jung, Y. M., Byun, J. Y., Yoon, J. I., and Jeong, S. K., 2009, A Study on High Precision Temperature Control of an Oil Cooler for Machine Tools Using Hot-gas Bypass Method, Journal of the Korean Society of Marine Engineering, Vol. 33, No. 7, pp. 1003-1011. https://doi.org/10.5916/jkosme.2009.33.7.1003
  4. Beak, S. M., Moon, C. G., Yoon, J. I., Jeong, S. K., and Kim, E. P., 2011, The Characteristic of Capacity Control Using a Variable Speed Compressor in an Industrial Cooler, The Korean Society for Power System Engineering, Vol. 15, pp. 37-41.
  5. Li, H., You, S. S., and Jeong, S. K., 2008, Feedforward Control of Capacity and Superheat for a Variable Speed Refrigeration System, Applied Thermal Engineering, Vol. 29, pp. 1067-1074.
  6. Beak, S. M., Moon, C. G., Kim, E. P., Jeong, S. K., and Yoon, J. I., 2011, The Characteristic Study of Capacity Control of an Industrial Cooler Using an Inverter Compressor with Varing the Ambient Temperatures, Journal of the Korean Society of Marine Engineering, Vol. 35, pp. 238-243. https://doi.org/10.5916/jkosme.2011.35.2.238
  7. Li, H., You, S. S., Yoon, J. I., and Jeong, S. K., 2008, An Empirical Model for Independent Control of Variable Speed Refrigeration System, Applied Thermal Engineering, Vol. 28, pp. 1918-1924. https://doi.org/10.1016/j.applthermaleng.2007.12.008
  8. Li, H. and Jeong, S. K., 2007, Design and Analysis of Fuzzy Control in a Variable Speed Refrigeration system, International Journal of Air-Conditioning and Refrigeration Engineering, Vol. 15, No. 2, pp. 61-69.
  9. Jeong, S. K., Byun, J. Y., Kim, S. H., and Yoon, J. I., 2011, Precise Temperature Control of Oil Cooler with Hot-gas Bypass Manner for Machine Tools Based on PI and Feedforward Control, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 23, No. 2, pp. 111-119. https://doi.org/10.6110/KJACR.2011.23.2.111
  10. Kim, S. H. and Jeong, S. K., 2011, High Performances Controller Design of a Cooler for Machine Tools Based on the State Space Model, Proceeding of SAREK, pp. 19-23.
  11. Park, S. H. and Shin, S. C., 2001, A Study on the Development of the Zonal Division Model and the State Feedback Controller for the Temperature Control of the Indoor Zone Via VAV Unit, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 13, No. 10, pp. 947-959.
  12. Kang, C. G. et al., 2010, Modern control engineering, 5th Edition, Kyobo, p. 893.