DOI QR코드

DOI QR Code

Experimental Study of a Seismic Reinforcing System without Power Interruption and Movement for Electric Panel on the Access Floor

무정전-무이설 방식의 전기판넬 내진보강시스템 시험연구

  • Published : 2009.06.30

Abstract

The seismic reinforcing system is developed to prevent damage to electric panels which are installed on the access floor and are essential to the operation of various basic facilities such as electric power and communication etc., from earthquakes. The seismic capacity of seismic reinforcing system is verified through the shaking table test. The seismic reinforcing system is intended for the electric panel on the access floor, and installation is possible without movement and power interruption of the electric panel. The enveloped response spectrum is adopted considering the location of the electric panel in the building as input motion for the shaking table test. The shaking table tests are carried out with two electric panels that can be considered representative of general electric panels, and two types of access floors such as wood panel and steel panel, which are commonly used in the industrial field. As a result of tests, it is confirmed that the seismic reinforcing system secures the seismic safety of electric panels by preventing the overturning of electric panels during and after the shaking table tests. In the event that the seismic reinforcing system is applied to the electric panel on the access floor, damage to the electric panel from an earthquake can be effectively prevented, which can greatly contribute to the stable operation of domestic basic facilities.

본 연구에서는 전력, 통신 등 다양한 주요 기간설비의 운영에 필수적인 전기판넬의 내진성능개선을 위하여 내진보강시스템을 개발하고, 이 시스템의 내진성능평가를 위하여 진동대시험을 수행하였다. 본 연구에서 개발된 전기판넬 내진보강시스템은 이중바닥시스템(Access floor) 상에 설치된 전기판넬을 대상으로 운전하에서 무정전, 무이설 방식으로 내진보강이 가능하다는 장점을 지니고 있다. 진동대시험을 통해 전기판넬 내진보강시스템의 성능평가를 위하여 지진하중으로서 건물 내 여러 층에 설치되는 전기판넬의 특성을 고려하여 포괄응답스펙트럼을 입력하였다. 진동대시험은 널리 상용화되어 있는 스틸과 우드판넬 등 두 형식의 이중바닥시스템과 일반 전기판넬을 대표할 수 있는 동특성이 다른 두 종류의 전기판넬을 고려하여 총 4회 수행하였다. 진동대시험결과, 내진보강시스템은 진동대시험 중 및 후에도 전도 등으로 인한 전기판넬의 파손을 방지하는 등 전기판넬의 내진안전성을 확보하여 주는 것으로 나타났다. 따라서, 이중바닥시스템 상에 설치된 전기판넬에 개발된 내진보강시스템을 적용하는 경우, 지진으로 인한 전기판넬의 파손을 효과적으로 방지하여, 국내 주요 기간설비의 안정적 운영에 크게 기여할 수 있을 것으로 판단된다.

Keywords

References

  1. 장정범 등, “변압기의 내진성능 향상을 위한 마찰진자 면진장치의 시험 연구”, 한국지진공학회 논문집, 제12권, 제2호, 1-8, 2008 https://doi.org/10.5000/EESK.2008.12.2.001
  2. 방재연구소, 전력시설물의 지진취약도함수 국산화 연구, 2008.
  3. (사)일본전기협회, 변전소 등에 있어서 전기설비의 내진설계지침, JEAG 5003, 1999
  4. FEMA 202, Earthquake resistant construction of electrictransmission and telecommunication facilities serving the federal government report, 1990
  5. Murota, N., Feng, M.Q. and Liu, G.Y., Experimental andanalytical studies of base isolation systems for seismic protection of power transformers, Technical Report MCEER-05-0008, MCEER, 2005. 9
  6. Skinner, I.R., Robinson, H.W., and McVerry, H.G., An introduction to seismic isolation, John Wiley & Sons Ltd, 1993
  7. Wilcoski, J., “Demonstration of CERL equipment fragilityand protection procedure by fragility testing of a power transformer bushing,” Seminar Technical Papers, ATC-29-1, 1997
  8. Villaverde, R., and Pardoen, G., Ground motion amplification at base of bushings mounted on electric substation transformer, A Technical Report of Research Supported by PEER/PG&E Under Award, No. PGE-09566, Department of Civil Engineering, University of California, Irvine, 1999
  9. Gilani, A.S., Chavez, J.W., Fenves, G.L. and Whittaker, A.S., Seismic evaluation of 550kV porcelain transformer bushings, PEER, 1999
  10. 한국전력공사, 송변전설비 내진설계 실무지침서, 2003
  11. 지식경제부, 지진발생 시 765kV 변전설비의 내진성능평가 및 안전조치기술 개발, 2008
  12. 이종림, 김왕춘, 여근택, 황윤곤, 장정범, 변전소 배전반 무정전 내진보강시스템 개발, 한국전력공사, 2008
  13. US DOE, Seismic evaluation procedure, 1997
  14. IEEE Power Engineering Society, IEEE Recommended practice for seismic design of substations, IEEE Std 693, 2005
  15. IEEE Power Engineering Society, IEEE Recommended practice for seismic qualification of class 1E equipment for nuclear power generating stations, IEEE Std 344, 1987

Cited by

  1. Characteristics and factors that influenced damage to dams in the M s 8.0 Wenchuan earthquake vol.10, pp.3, 2011, https://doi.org/10.1007/s11803-011-0071-3
  2. The Experimental Study on Seismic Capacity of 154 kV & 345 kV Main Transformer Bushings vol.22, pp.2, 2018, https://doi.org/10.5000/EESK.2018.22.2.087