Experimental Study of a Seismic Reinforcing System without Power Interruption and Movement for Electric Panel on the Access Floor  

Jang, Jung-Bum (한국전력공사 전력연구원)
Lee, Jong-Rim ((주)파워엔텍)
Hwang, Kyeong-Min (한국전력공사 전력연구원)
Ham, Kyung-Won (한국전력공사 전력연구원)
Publication Information
Journal of the Earthquake Engineering Society of Korea / v.13, no.3, 2009 , pp. 1-10 More about this Journal
Abstract
The seismic reinforcing system is developed to prevent damage to electric panels which are installed on the access floor and are essential to the operation of various basic facilities such as electric power and communication etc., from earthquakes. The seismic capacity of seismic reinforcing system is verified through the shaking table test. The seismic reinforcing system is intended for the electric panel on the access floor, and installation is possible without movement and power interruption of the electric panel. The enveloped response spectrum is adopted considering the location of the electric panel in the building as input motion for the shaking table test. The shaking table tests are carried out with two electric panels that can be considered representative of general electric panels, and two types of access floors such as wood panel and steel panel, which are commonly used in the industrial field. As a result of tests, it is confirmed that the seismic reinforcing system secures the seismic safety of electric panels by preventing the overturning of electric panels during and after the shaking table tests. In the event that the seismic reinforcing system is applied to the electric panel on the access floor, damage to the electric panel from an earthquake can be effectively prevented, which can greatly contribute to the stable operation of domestic basic facilities.
Keywords
Electric Panel; Seismic Capacity; Access Floor; Shaking Table Test;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Wilcoski, J., “Demonstration of CERL equipment fragilityand protection procedure by fragility testing of a power transformer bushing,” Seminar Technical Papers, ATC-29-1, 1997
2 이종림, 김왕춘, 여근택, 황윤곤, 장정범, 변전소 배전반 무정전 내진보강시스템 개발, 한국전력공사, 2008
3 US DOE, Seismic evaluation procedure, 1997
4 IEEE Power Engineering Society, IEEE Recommended practice for seismic design of substations, IEEE Std 693, 2005
5 Murota, N., Feng, M.Q. and Liu, G.Y., Experimental andanalytical studies of base isolation systems for seismic protection of power transformers, Technical Report MCEER-05-0008, MCEER, 2005. 9
6 Skinner, I.R., Robinson, H.W., and McVerry, H.G., An introduction to seismic isolation, John Wiley & Sons Ltd, 1993
7 FEMA 202, Earthquake resistant construction of electrictransmission and telecommunication facilities serving the federal government report, 1990
8 IEEE Power Engineering Society, IEEE Recommended practice for seismic qualification of class 1E equipment for nuclear power generating stations, IEEE Std 344, 1987
9 방재연구소, 전력시설물의 지진취약도함수 국산화 연구, 2008.
10 Villaverde, R., and Pardoen, G., Ground motion amplification at base of bushings mounted on electric substation transformer, A Technical Report of Research Supported by PEER/PG&E Under Award, No. PGE-09566, Department of Civil Engineering, University of California, Irvine, 1999
11 장정범 등, “변압기의 내진성능 향상을 위한 마찰진자 면진장치의 시험 연구”, 한국지진공학회 논문집, 제12권, 제2호, 1-8, 2008   과학기술학회마을   DOI
12 Gilani, A.S., Chavez, J.W., Fenves, G.L. and Whittaker, A.S., Seismic evaluation of 550kV porcelain transformer bushings, PEER, 1999
13 한국전력공사, 송변전설비 내진설계 실무지침서, 2003
14 (사)일본전기협회, 변전소 등에 있어서 전기설비의 내진설계지침, JEAG 5003, 1999
15 지식경제부, 지진발생 시 765kV 변전설비의 내진성능평가 및 안전조치기술 개발, 2008