Seismic Fragility Analysis of Substation Systems by Using the Fault Tree Method

고장수목을 이용한 변전소의 지진취약도 분석

  • 김민규 (한국원자력연구원 종합안전평가부) ;
  • 전영선 (한국원자력연구원 종합안전평가부) ;
  • 최인길 (한국원자력연구원 종합안전평가부) ;
  • 오금호 (국립방재연구소)
  • Published : 2009.04.30

Abstract

In this study, a seismic fragility analysis was performed for substation systems in Korea. To evaluate the seismic fragility function of the substation systems, a fragility analysis of the individual equipment and facilities of the substation systems was first performed, and then all systems were considered in the fragility analysis of the substation systems using a fault-tree method. For this research, the status of the substation systems in Korea was investigated for the classification of the substation systems. Following the classification of the substation systems, target equipment was selected based on previous damage records in earthquake hazards. The substation systems were classified as 765kV, 345kV, and 154kV systems. Transformer and bushing were chosen as target equipment. The failure modes and criteria for transformer and bushing were decided, and fragility analysis performed. Finally, the fragility functions of substation system were evaluated using the fault tree method according to damage status.

본 연구에서는 변전소 시스템의 지진취약도 분석을 수행하여 변전소에 대한 지진취약도 함수를 제시하였다. 변전소는 여러 개의 설비와 구조물이 복합적으로 구성되어 있는 시스템이므로 각 설비에 대한 지진취약도 분석을 수행하여 이를 바탕으로 고장수목을 작성하여 변전소 전체의 파괴확률을 산정함으로써 변전소에 대한 지진취약도 평가를 수행하였다. 이를 위하여 국내 변전소의 현황을 파악하여 지진피해추정을 위한 변전소의 분류형식을 결정하였으며, 결정된 대표변전소 형식에 대한 평가대상 기기를 선정하였다. 대표 변전소 형식으로는 765kV, 345kV, 154kV 변전소의 GIS형 변전소로 결정하였다. 각 변전소의 취약도 검토대상 기기로는 변압기와 절연 애자를 선택하였다. 각 변전소의 변압기와 절연애자의 파괴모드와 파괴기준을 설정하여 지진취약도 곡선을 도출하였다. 최종적으로 변전소에 대한 고장수목을 이용하여 각 기기의 지진취약도 곡선으로부터 변전소 전체의 파괴확률을 산정하여 정의된 손상상태별 변전소의 지진취약도 함수를 산정하였다.

Keywords

References

  1. (社)日本原子力學會標準, 原子力發展所의地震에起因한確率論的安全性評價實施基準, (2006)
  2. Ang, A. H-S., Tang, W. H., Probability concepts in engineering planning and design, J. Wiley and Sons, New York, , 1975
  3. Ang, A.H.-S., Pires, J.A. and Villaverde, R., A Model for the Seismic Reliability Assessment of Electric Power Transmission Systems, Reliability Engineering and System Safety, Vol. 51, 1996, pp. 7-22 https://doi.org/10.1016/0951-8320(95)00101-8
  4. Camensig, C., Bresesti, L., Clementel, S. and Salvetti, M., Seismic Risk Evaluation for High Voltage Air Insulated Substations, Reliability Engineering and System Safety, Vol 55, 1997, pp. 179-191 https://doi.org/10.1016/S0951-8320(96)00107-X
  5. FEMA(미국재난관리청), HAZUS99 User's Manual, 1999
  6. Hwang, H.H.M and Chou, T., Evaluation of Seismic Performance of and Electric Substation using Event/Fault Tree Technique, Probabilistic Engineering Mechanics, Vol. 13, No. 2, 1998, pp. 117-124 https://doi.org/10.1016/S0266-8920(97)00018-0
  7. Hwang, H.H.M and Huo, J-R., Seismic Fragility Analysis of Electric Substation Equipment and Structures, Probabilistic Engineering Mechanics, Vol. 13, No. 2, 1998, pp. 107-116 https://doi.org/10.1016/S0266-8920(97)00017-9
  8. Murota, N., Feng, M. Q. and Liu, G. Y., Experimental and Analytical Studies of Base Isolation Systems for Seismic Protection of Power Transformers, Technical Report MCEER-05-0008, MCEER, 2005
  9. Reed, J.W. and Kennedy, R.P., Methodology for Developing Seismic Fragilities, Palo Alto, California: Electric Power Research Institute (EPRI), prepared by Jack R. Benjamin and Associates, Inc., 1994, TR-103959
  10. 고현무,김영호,박영석,“지진 재해에 대한 전력 송전 네트워크 시스템의 신뢰성 평가 모형”, 한국지진공학회, Vol. 7, No. 2, 2003, pp. 93-102 https://doi.org/10.5000/EESK.2003.7.2.093
  11. 박영준,조호현,박원석,고현무,변압기의 병렬운전을 고려한 국내 345kV 초고압 전력망의 지진 재해 신뢰성 평가, 한국지진공학회 논문집, 제10권, 제3호, 2006, pp. 13-20 https://doi.org/10.5000/EESK.2006.10.3.013
  12. 조양희, 조성국, 진동시험에 의한 154kV 변압기 부싱의 동특성 분석 및 내진성능 평가,한국지진공학회 논문집,제10권 제5호, 2006, pp. 107-115 https://doi.org/10.5000/EESK.2006.10.5.107
  13. 한전전력연구원, 송변전설비의 내진설계기준 설정 연구, 2001

Cited by

  1. Probability‐based seismic reliability assessment method for substation systems vol.48, pp.3, 2019, https://doi.org/10.1002/eqe.3138